2015-06-27 17:40:48 | 6/27/2015 |
| PROJECT: 1300 MANGONIA DR. |
| PERMIT#: 15040379 |
| CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| 2ND ELECTRICAL PLAN REVIEW |
| ACTION: DENIED |
| |
| REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW |
| COMMENTS: |
| |
| 1) PROVIDE A RISER DIAGRAM AND A SITE PLAN INDICATING |
| THE LOCATION OF THE MAIN DISCONNECT IN COMPLIANCE WITH |
| NEC 230.70 |
| THE INTENT OF THE CODE IS TO HAVE THE MAIN DISCONNECT |
| AS CLOSE AS PRACTICABLE TO THE SERVICE ENTRANCE. THE |
| RISER INDICATES A METER BY ITSELF AND A MAIN BREAKER |
| PANEL IN CLOSE PROXIMITY. THE FLOOR PLAN INDICATES THE |
| PANEL ON THE INSIDE OF THE HOUSE IN A HALLWAY. THE |
| RISER NEEDS TO INDICATE COMPLIANCE WITH THE NEC 230.70. |
| EITHER THE MAIN IS IMMEDIATELY NEXT TO THE METER OR THE |
| MAIN BREAKER PANEL IS INSTALLED IN CLOSE ENOUGH |
| PROXIMITY TO COMPLY WITH NEC 230.70. |
| |
| 2) PROVIDE A LOAD CALCULATION INDICATING THE 150AMP |
| PANEL IS ADEQUATE FOR THE LOAD TO BE SERVED. NEC |
| 408.30, NEC 220. |
| THE HEATING VS COOLING LOAD IS NOT REPRESENTED |
| ACCURATELY. REVISE ACCORDINGLY. |
| |
| 3) VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS |
| HAS A FAULT CURRENT RATING THAT IS SUFFICIENT AT |
| NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE |
| INTERRUPTED. NEC 110.9 |
| |
| 4) AT LEAST ONE LIGHTING OUTLET CONTAINING A SWITCH OR |
| CONTROLLED BY A WALL SWITCH SHALL BE PROVIDED AT OR |
| NEAR THE EQUIPMENT REQUIRING SERVICING. NEC 210.70(3) |
| |
| 5) PERMANENT LADDERS OR STAIRWAYS SHALL BE PROVIDED TO |
| GIVE SAFE ACCESS TO THE WORKING SPACE AROUND ELECTRICAL |
| EQUIPMENT INSTALLED ON PLATFORMS, BALCONIES, OR |
| MEZZANINE FLOORS OR IN ATTIC OR ROOF ROOMS OR SPACES. |
| NEC 110.33(B) |
| |
| 6) PROVIDE A DISCONNECT FOR A/C AHU IN ATTIC SPACE |
| ABOVE PANEL. NEC 440.14 |
| |
| 7) INDICATE THE LOCATION OF ALL REQUIRED SMOKE |
| DETECTORS. FBC-RESIDENTIAL 314 AND 315 |
| PROVIDE THE NAMES OF ALL ROOMS ON THE FLOOR PLAN. |
| |
| 8) INDICATE GFI PROTECTION ON RECEPTACLES WHERE |
| REQUIRED. NEC 210.8 |
| |
| 9) INDICATE GFI PROTECTION WITHIN SIGHT OF MECHANICAL |
| EQUIPMENT. NEC 210.63 |
| OUTLETS STILL MISSING. |
| |
| 10) ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER |
| RESISTANT AND AFCI PROTECTED. NEC 210.12, 406.11 |
| |
| 11) 210.52(C)(3) BATHROOM BRANCH CIRCUITS. IN ADDITION |
| TO THE NUMBER OF BRANCH CIRCUITS REQUIRED BY OTHER |
| PARTS OF THIS SECTION, AT LEAST ONE 20-AMPERE BRANCH |
| CIRCUIT SHALL BE PROVIDED TO SUPPLY BATHROOM RECEPTACLE |
| OUTLET(S). SUCH CIRCUITS SHALL HAVE NO OTHER OUTLETS. |
| |
| 12) 210.52 (D) BATHROOMS. |
| IN DWELLING UNITS, AT LEAST ONE RECEPTACLE OUTLET SHALL |
| BE INSTALLED IN BATHROOMS WITHIN (3 FT) OF THE OUTSIDE |
| EDGE OF EACH BASIN. |
| THERE IS A BATHROOM SHOWN ON THE FLOOR PLAN WITH TWO |
| BASINS. EACH BASIN REQUIRES A GFI RECEPTACLE TO BE |
| INSTALLED WITHIN 3FT. |
| |
| 13) DISCONNECT REQUIRED FOR WATER HEATER. NEC 422.31 |
| |
| 14) INDICATE WHAT IS EXISTING TO REMAIN AND WHAT IS |
| PROPOSED TO BE INSTALLED AS NEW. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| |
| ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| REVIEW. |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| 561-805-6717 OR [email protected] |
| |
| |
| |
| |
| |