Plan Review Details - Permit 15040374
Plan Review Stops For Permit 15040374
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-05-06 Cont ID  
Sent By rmcdouga Date 2015-05-06 Time 07:11 Rev Time 0.00
Received By rmcdouga Date 2015-05-06 Time 06:42 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-04-24 Cont ID  
Sent By rmcdouga Date 2015-04-24 Time 13:31 Rev Time 0.00
Received By rmcdouga Date 2015-04-24 Time 13:16 Sent To  
Notes
2015-04-24 13:31:51PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC 107.3.5.3 - PROVIDE WIND DESIGN LOADS/DESIGN
 PRESSURES PURSUANT TO FBC-R301.2. THE WIND SPEED DESIGN
 IS NOT CONSISTENT WITH THE ADOPTED MAP FBC 119, CITY
 AMENDMENTS. THIS PROJECT IS LOCATED WITHIN 600 FEET OF
 THE INTERCOASTAL WATERWAY. THE EXPOSURE CATEGORY IS D
 AND THE WINDSPEED IS 170 MPH VULT.
  
 2) SHEET S-1 INDICATES THAT THE ARRAY WILL BE MOUNTED
 ON THE FLAT ROOF PORTION OF THE STRUCTURE WITH A .125 :
 12 SLOPE. THE CALCULATIONS ON SHEET S-2 INDICATE THE
 SLOPE AS 5 : 12. PLEASE CLARIFY THE REASON THE 5 : 12
 SLOPE WAS USED. FBC 107.2.1
  
 3) SPECIFY THE TRIBUTARY AREA THAT WAS USED TO
 DETERMINE THE POSITIVE AND NEGATIVE DESIGN WIND
 PRESSURES. IT APPEARS THAT THE TRIBUTARY AREA PER
 ATTACHMENT WOULD BE 10 SQFT. (WORST CASE) FBC-R301.2.1
  
 IN ORDER TO REDUCE PLAN REVIEW TIMES AND PROVIDE
 CLARIFICATION, PLEASE SUBMIT A RESPONSE LETTER
 INDICATING HOW EACH OF THE REVIEW COMMENTS HAS BEEN
 ADDRESSED.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-04-24 Cont ID  
Sent By rmcdouga Date 2015-04-24 Time 11:49 Rev Time 0.00
Received By dhayes Date 2015-04-23 Time 16:52 Sent To B
Notes
2015-04-24 11:49:38APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN APPROVED
 PROVISIONALLY. FAILURE TO CORRECT THE LISTED
 DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED
 INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION
 FEE(S).
  
 THE FOLLOWING IS A CHECKLIST USED FOR FIELD INSPECTION.
  
 PLEASE PROVIDE ADDITIONAL INFORMATION WITH REGARDS TO
 THE FOLLOWING PAY PARTICULAR ATTENTION TO THE REQUIRED
 SIGNAGE. INDICATE THE REQUIRED SIGNAGE IN THE LOCATIONS
 INDICATED BELOW:
  
 _____ PROVE # OF PV MODULES AND MODEL # MATCH SPEC
 SHEETS [690.51]
 _____ PV MODULES ARE LISTED TO UL 1703 STANDARD [110.3]
 _____ ARRAY CONDUCTORS ARE NEATLY AND PROFESSIONALLY
 HELD IN PLACE, GROUPED AND SEPARATED [690.4 B]
 _____ CHECK CONNECTORS ARE POLARIZED,
 NON-INTERCHANGEABLE AND UNIQUE [690.33 A]
 _____ PROVE CONNECTORS STATE ?DO NOT DISCONNECT UNDER
 LOAD? [690.33 E 2]
 _____ CHECK THAT ELECTRICAL JUNCTION BOXES ARE READILY
 ACCESSIBLE, LISTED AND SUITABLE FOR ENVIRONMENT (NEMA)
 _____ ARRAY ATTACHMENTS ARE FASTENED AND SEALED
 ACCORDING TO ATTACHMENT DETAIL IN PLANS
  
 CONDUCTORS
  
 _____ CONDUCTOR TYPES USE-2 OR PV WIRE FOR EXPOSED ARE
 90? C WET RATED AND SUNLIGHT RESISTANT [690.31(B)]
 [NOTE 2008 AND 2011 NEC RESTRICT EXPOSED SINGLE
 CONDUCTOR WIRING TO USE-2 AND LISTED PV WIRE]. IF IN
 CONDUIT: RHW-2, THWN-2 OR XHHW-2 90? C WET RATED
 CONDUCTORS ARE REQUIRED [310.15]
 _____ CHECK CONDUCTORS INSULATION RATINGS AT 90? C [UL
 1703] TO ALLOW OPERATION AT ARE 70? C+ NEAR MODULES AND
 IN CONDUIT EXPOSED TO SUNLIGHT (ADD 17-20? C TO AMBIENT
 TEMPERATURE-2005NEC), (SEE TABLE 310.15(B)(2) IN
 2008NEC OR TABLE 310.15(B)(3)(C) IN 2011NEC)
  
 NOTE: TEMPERATURE-DERATED AMPACITY CALCULATIONS ARE
 BASED ON 156% OF THE SHORT CIRCUIT
 CURRENT (ISC) AND THE DERATED AMPACITY OF THE
 OVERCURRENT DEVICE IS MATCHED [690.8,9]
  
 _____ STRAIN RELIEFS/CABLE CLAMPS ARE USED ON ALL CABLE
 AND CORDS [300.4, 400.10]
 _____ CONDUCTORS SHALL BE LISTED FOR THE APPLICATION
 AND ENVIRONMENT. USE OF FINE STRANDED, FLEXIBLE
 CONDUCTOR CABLES SHALL BE PROPERLY TERMINATED WITH
 TERMINALS RATED FOR THESE CONDUCTORS [690.31 (E)(4)]
  
  
 _____ EXPOSED CONDUCTORS SHALL BE READILY ACCESSIBLE
 AND IN A RACEWAY IF OVER 30 VOLTS ? RACEWAYS CANNOT BE
 INSTALLED ON MODULES. CONDUCTORS SHOULD BE INSTALLED
 NOT READILY ACCESSIBLE.
 _____ DC CONDUCTOR COLORS ARE THE SAME AS AC. GROUNDED
 CONDUCTORS SHALL BE WHITE AND EQUIPMENT GROUNDING
 CONDUCTORS ARE GREEN, GREEN/YELLOW OR BARE.
  
 NOTE: 1)
 UNGROUNDED PV ARRAY CONDUCTORS ON UNGROUNDED ARRAYS
 WILL NOT BE WHITE IN COLOR.
 NOTE 2) TRADITIONALLY ALL PV SOURCE ARRAY WIRING WILL
 BE BLACK. NON-BLACK COLORS HAVE PROVEN TO NOT BE AS
 DURABLE IN THE UV RICH ENVIRONMENT AS BLACK.
  
 GROUNDING:
  
 _____ CHECK MODULE CONNECTIONS AND ALLOW FOR REMOVAL
 WITHOUT INTERRUPT GROUNDED CONDUCTOR [690.4 C]
 _____ 2 WIRE OVER 50 VOLTS SHALL BE GROUNDED [690.41]
 _____ CHECK POINT OF SYSTEM GROUNDING CONNECTION
 [690.42] IS AT ANY POINT ALONG PV OUTPUT CIRCUIT
 _____ CHECK EQUIPMENT GROUNDING OF METAL PARTS ON SOLAR
 PANEL FRAMES ARE GROUNDED PER 250.134 AND 250.136
 _____ INSURE EITHER UNIVERSAL GROUNDING CLIPS (UGC) OR
 WEEBS? ARE LISTED AND IDENTIFIED FOR BONDING PANELS TO
 GROUNDED MOUNTING STRUCTURES [690.43]
 _____ EQUIPMENT GROUNDING CONDUCTOR (EGC) SHALL BE
 CONTAINED IN SAME RACEWAY WHEN LEAVING VICINITY OF
 ARRAY [690.43]
 _____ EGC SIZED NO SMALLER THAN #14 AND NOT SMALLER
 THAN LARGEST CURRENT CARRYING CONDUCTOR [250.122].
 _____ CHECK AC/DC IS BONDED AT INVERTER [690.C 1]
 _____ CHECK EQUIPMENT GROUNDING CONDUCTORS ARE SIZED IN
 ACCORDANCE WITH 690.45(A) 250.122 OR (B) WHEN NO GROUND
 FAULT EGC SIZED TO TWO (2) TIMES THE TEMP AND CONDUIT
 FILL CONDUCTOR AMPACITY.
 _____ ARRAY GROUNDING ELECTRODE CONDUCTORS (GEC) NOT
 SMALLER THAN #6 AND COMPLIES WITH 250.120(C)
 _____ SYSTEMS WITH AC ONLY (MICRO INVERTERS) THE
 GROUNDING ELECTRODE SYSTEM SHALL BE INSTALLED PER
 [690.47(A) IN ACCORDANCE WITH [250.50 THRU 250.60] AND
 [250.64]
 _____ SYSTEMS WITH BOTH AC AND DC SHALL BE INSTALLED
 PER [690.47 (C)(1) THRU (C)(8) AND SIZED PER 250.66
 (AC) 250.166 (DC)
 _____ INSPECT PREMISES GROUNDING AS IT SERVES AS THE AC
 GROUNDING FOR PV SYSTEMS [690.47 C 8]
 _____ IF GROUND OR POLE MOUNT GROUNDING ELECTRODE
 INSTALLED PER 250.52 AND WITHIN 6 FEET [690.47D
 EXCEPTION 2].
 _____ CHECK ELECTRODE IS CONNECTING DIRECTLY TO FRAMES
 AND STRUCTURES [690.47 D]
 _____ IF BREAKS IN RAILS OF MOUNTING STRUCTURE, CHECK
 FROM JUMPER [690.48]
 _____ BONDING, GROUNDED FITTINGS AND/OR BUSHINGS SHALL
 BE USED WITH METAL CONDUITS IF VOLTAGE IS OVER 250V DC
 [250.97]
  
 DISCONNECTING MEANS
  
 _____ DC DISCONNECTS SHALL BE LISTED FOR DC OPERATION,
 ARE NOT REQUIRED TO BE SUITABLE AS SERVICE EQUIPMENT
 AND SHALL MEET [690.17]. GENERALLY, MARINE, AUTOMOTIVE
 NOR TELECOMDEVICES ARE ACCEPTABLE AS THEY ARE NOT
 SUITED FOR USE.
 _____ DISCONNECTS SHALL BE READILY ACCESSIBLE EITHER ON
 THE OUTSIDE OF THE BUILDING OR INSIDE NEAREST THE FIRST
 POINT OF ENTRANCE [690.14(C)(1)]
 _____ NOTE MANY UL 1741 LISTED INVERTERS HAVE INTERNAL
 DC DISCONNECTS. INSPECT DC INPUT?S MAXIMUM CURRENT
 [690.53] DOES NOT EXCEED DISCONNECT LISTING AS THE
 DISCONNECT MAY BE A SEPARATELY MANUFACTURED PRODUCT
 (EITHER BY THE INVERTER MANUFACTURE OR OTHERS).
  
 AC GRID CONNECTION
  
 _____ POINT OF CONNECTION, SUPPLY SIDE. AN ELECTRICAL
 POWER PRODUCTION SOURCE CONNECTED SUPPLY SIDE OF THE
 SERVICE DISCONNECTING MEANS AS PERMITTED IN 230.82 (6)
 IS PERMITTED PER 705.12 (A) PERMITTING THE SUM OF THE
 RATINGS OF ALL OVERCURRENT DEVICES CONNECTED TO ALL
 POWER PRODUCTION SOURCES DO NOT EXCEED THE RATING OF
 THE SERVICE.
 _____ CIRCUIT BREAKER SHALL BE SUITABLE AS A BACKFEED
 BREAKER IF INSTALLED ON THE LOAD SIDE OF THE SERVICE
 DISCONNECTING MEANS ON THE PREMISES. NOTE: CIRCUIT
 BREAKER MARKED ?LINE? AND ?LOAD? HAVE BEEN EVALUATED
 FOR THE DIRECTION MARKED. CIRCUIT BREAKERS WITHOUT
 ?LINE? AND ?LOAD? HAVE BEEN EVALUATED IN BOTH
 DIRECTIONS.
 _____ CHECK THE SUM OF THE AMPERE RATING OF THE
 OVERCURRENT DEVICES IN CIRCUIT SUPPLYING POWER TO A
 BUSBAR OR CONDUCTOR DO NOT EXCEED 120% OF THE RATING OF
 THE BUSBAR AS CALCULATED IN [220.82 ~88] NEC 2008/11
 [705.12(D)(2)]
  
 APPROPRIATE SIGNS INSTALLED 690 VI - MARKINGS:
  
 _____ CHECK PROPER SIGN CONSTRUCTION 690.53 WITH
 MARKINGS AS FOLLOWS:
 690.53 (1) RATED MAXIMUM POWER POINT CURRENT
 690.52 (2) RATED MAXIMUM POWER POINT VOLTAGE
 690.53 (3) MAXIMUM SYSTEM VOLTAGE (I.E. ARRAY MAX
 VOLTAGE ? A CALCULATED VALUE 690.7)
 690.53 (4) SHORT CIRCUIT CURRENT (I.E. SEE 690.8(A) ? A
 CALCULATED VALUE
 690.53 (5) MAXIMUM RATED OUTPUT CURRENT OF THE CHARGE
 CONTROLLER (IF INSTALLED)
 NOTE: NEC2011 690.53 CALLS FOR A PERMANENT LABEL. LABEL
 SHALL BE ENGRAVED AND/OR SUNLIGHT RESISTANT (I.E.
 STICKERS MAY NOT MEET THE CODE)
 _____ THE INTERACTIVE SYSTEM (GRID TIED) POINT OF
 INTERCONNECTION SHALL BE MARKED IN AN ACCESSIBLE
 LOCATION AT THE POWER SOURCE DISCONNECTING MEANS WITH
 THE RATED AC OUTPUT CURRENT AND NOMINAL AC VOLTAGE
 [690.54].
 _____ IF ENERGY STORAGE IS EMPLOYED (I.E. BATTERIES)
 THE ENERGY STORAGE SHALL ALSO BE MARKED WITH MAXIMUM
 OPERATING VOLTAGE, INCLUDING ANY EQUALIZATION VOLTAGE
 AND THE POLARITY OF THE GROUNDED CIRCUIT CONDUCTOR
 [690.55].
 _____ CHECK FOR DIRECTORY I.E. A PERMANENT SIGN, PLAQUE
 OF DIRECTORY DENOTING ALL ELECTRICAL POWER SOURCES ARE
 POSTED AT A READILY ACCESSIBLE LOCATION PER [705.10] ON
 OR IN THE PREMISES IDENTIFYING PV POWER SOURCE SYSTEM
 ATTRIBUTES AT DC DISCONNECT [690.53(1~5)]
 _____ FACILITIES WITH STAND ALONE SYSTEMS. ANY
 STRUCTURE OR BUILDING WITH A PV POWER SYSTEM THAT IS
 NOT CONNECTED TO THE GRID IS CONSIDERED STAND ALONE.
 CHECK FOR A PERMANENT SIGN IDENTIFYING SERVICE
 DISCONNECT AND PV DISCONNECTING MEANS PER [690.56,
 705.10]
  
 CHECK THAT EQUIPMENT RATINGS ARE CONSISTENT WITH
 APPLICATION AND SIGNS:
 _____ CHECK THAT INVERTER HAS A RATING AS HIGH AS MAX
 VOLTAGE ON PV POWER SOURCE SIGN [690.53]
 _____ CHECK THAT DC-SIDE OCPDS ARE DC RATED AT LEAST AS
 HIGH AS MAX VOLTAGE ON SIGN
 _____ CHECK THAT SWITCHES AND OCPDS ARE INSTALLED
 ACCORDING TO MANUFACTURERS SPECIFICATIONS
  
 (I.E. MANY 600VDC SWITCHES NOW REQUIRE PASSING THROUGH
 THE SWITCH POLES TWICE IN A SPECIFIC WAY TO PROTECT FOR
 ARC FLASH AND BLAST).
  
 NOTE: ALL EQUIPMENT SHALL BE INSTALLED PER 110.3(B)
  
 _____ CHECK THAT INVERTER IS RATED FOR THE SITE AC
 VOLTAGE SUPPLIED AND SHOWN ON THE AC POINT OF
 CONNECTION SIGN [690.54]
 _____ CHECK THAT OCPD CONNECTED TO THE AC OUTPUT OF THE
 INVERTER IS RATED AT LEAST 125% OF MAXIMUM CURRENT ON
 SIGN, AND IS NO LARGER THAN THE MAXIMUM OCPD ON THE
 INVERTERLISTING LABEL [690.8 A3, B1]
  
  
  
 DAVID A. HAYES
 CITY OF WEST PALM BEACH
 ELECTRICAL PLANS EXAMINER
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-04-21 Cont ID  
Sent By   Date 2015-04-21 Time 13:03 Rev Time 0.00
Received By dhayes Date 2015-04-21 Time 12:20 Sent To Z
Notes
2015-04-21 13:03:094/21/2015
 PROJECT: PHOTOVOLTAIC SYSTEM 3121 WASHINGTON RD
 PERMIT#: 15040374
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) PROVIDE SITE PLAN INCLUDING THE FOLLOWING: WPB
 AMENDMENTS TO THE FBC 107.3.2
 THE LOCATION HOUSE ON THE PROPERTY.
 THE LOCATION OF THE PHOTOVOLTAIC DC DISCONNECT /
 INVERTER ON THE HOUSE.
 THE LOCATION OF THE ELECTRICAL UTILITY METER ON THE
 HOUSE.
 THE LOCATION OF THE ELECTRICAL SERVICE PANEL ON OR IN
 THE HOUSE.
  
 2) PROVIDE ALL SIGNAGE REQUIRED BY THE NEC 690
  
 3) INDICATE THE LOCATION OF EACH OF THE REQUIRED SIGNS
 IN RELATION TO THE NEW PHOTOVOLTAIC EQUIPMENT AND THE
 EXISTING ELECTRICAL EQUIPMENT. NEC 690
  
 4) PROVIDE MANUFACTURER PRODUCT APPROVALS ON EQUIPMENT
 INDICATING COMPLIANCE WITH LISTING REQUIRMENTS. NEC
 690,4(D)
  
 5) INDICATE A GROUNDING ELECTRODE DETAIL AT THE
 ELECTRICAL SERVICE AND INDICATE HOW THE SOLAR ARRAY
 GROUNDING ELECTRODE CONNECTS TO THE ELECTRICAL SYSTEM
 GROUNDING ELECTRODE SYSTEM.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-05-06 Cont ID  
Sent By rmcdouga Date 2015-05-06 Time 07:11 Rev Time 0.00
Received By rmcdouga Date 2015-05-01 Time   Sent To  
Notes
2015-05-01 16:17:47SENT TO R MCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-04-24 Cont ID  
Sent By rmcdouga Date 2015-04-24 Time 13:32 Rev Time 0.00
Received By rmcdouga Date 2015-04-23 Time 16:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-04-21 Cont ID  
Sent By   Date 2015-04-21 Time   Rev Time 0.00
Received By rmcdouga Date 2015-04-10 Time 08:26 Sent To  
Notes
2015-04-11 08:26:56SENT TO ELECTRIC

Review Stop Z ZONING
Rev No 1 Status N Date 2015-04-24 Cont ID  
Sent By dhayes Date 2015-04-24 Time 11:51 Rev Time 0.00
Received By dhayes Date   Time   Sent To  
Notes
2015-04-24 11:52:10ZONING REVIEEW NOT PERFORMED AND NOT REQUIRED PER
 SHIRLEY GRAHAM