Plan Review Details - Permit 15040365
Plan Review Stops For Permit 15040365
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2015-04-20 Cont ID  
Sent By tklarge Date 2015-04-20 Time 09:19 Rev Time 0.00
Received By tklarge Date 2015-04-20 Time 03:51 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2015-04-13 Cont ID  
Sent By tklarge Date 2015-04-13 Time 05:03 Rev Time 0.00
Received By tklarge Date 2015-04-13 Time 04:39 Sent To  
Notes
2015-04-13 05:03:411) SUBMIT MANUF. SPECIFICATION SHEETS FOR ALL GAS
 APPLIANCES/EQUIPMENT. ALL APPLIANCES/EQUIPMENT SHALL BE
 LISTED AND LABELED PER THE 2010 FBCR SEC.G2404.3.
 2) INDICATE THE CORRESPONDING EHD FOR EACH SIZE OF THE
 CSST PIPING USED.2010 FBCR SEC.G2413.1, G2413.3.
 4) SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE
 DRYER. COMPLY WITH 2010 FBCR SEC.G2407.5.1 OR
 G2407.5.2.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 Z/[email protected]
  
  