Plan Review Details - Permit 15040362
Plan Review Stops For Permit 15040362
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2015-04-20 Cont ID  
Sent By tklarge Date 2015-04-20 Time 08:35 Rev Time 0.00
Received By tklarge Date 2015-04-20 Time 03:32 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2015-04-13 Cont ID  
Sent By tklarge Date 2015-04-13 Time 04:27 Rev Time 0.00
Received By tklarge Date 2015-04-13 Time 03:35 Sent To  
Notes
2015-04-13 04:26:441) SUBMIT MANUF. SPECIFICATION SHEETS FOR ALL GAS
 APPLIANCES/EQUIPMENT. ALL APPLIANCES/EQUIPMENT SHALL BE
 LISTED AND LABELED PER THE 2010 FBCR SEC.G2404.3.
 2) INDICATE THE DELIVERY PRESSURE ( PSI ) OF THE GAS ON
 THE PLANS. 2010 FBCR SEC. G2413.1.
 3) INDICATE THE CORRESPONDING EHD FOR EACH SIZE OF THE
 CSST PIPING USED.
 4) SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE
 DRYER. COMPLY WITH 2010 FBCR SEC.G2407.5.1 OR
 G2407.5.2.
 5) SUBMIT A FLOOR PLAN THAT IS CLEAR AND LEGIBLE. THE
 ONE SUBMITTED HAS A FEW LARGE BLACK LINES ACROSS THE
 PAGE MAKING IT DIFFICULT TO SEE THINGS. WPB AMEND. TO
 2010 FBCR 107.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-04-20 Cont ID  
Sent By tklarge Date 2015-04-20 Time 08:36 Rev Time 0.00
Received By tklarge Date 2015-04-17 Time   Sent To  
Notes
2015-04-17 18:51:41SENT TO TK LARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-04-13 Cont ID  
Sent By tklarge Date 2015-04-13 Time 04:28 Rev Time 0.00
Received By tklarge Date 2015-04-10 Time 07:26 Sent To  
Notes
2015-04-11 07:26:55SENT TO PLUMBING UNDER $5K