Plan Review Details - Permit 15040316
Plan Review Stops For Permit 15040316
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-09-23 Cont ID  
Sent By rmcdouga Date 2015-09-23 Time 17:08 Rev Time 0.00
Received By rmcdouga Date 2015-09-23 Time 15:40 Sent To Z
Notes
2015-09-23 17:15:50APPROVED WITH EXCEPTIONS.
 1) SUBMIT ENERGY CALC. FORMS WITH OWNER/AGENT
 SIGNATURE.
 2) SUBMIT PRODUCT APPROVALS FOR WINDOWS (NOA
 NO.13-0430.09) AND ASPHALT SHINGLES (FL 10124-R15) THAT
 HAVE BEEN APPROVED IN WRITING BY THE DESIGNER OF
 RECORD.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-08-14 Cont ID  
Sent By rmcdouga Date 2015-08-14 Time 13:14 Rev Time 0.00
Received By rmcdouga Date 2015-08-13 Time 18:53 Sent To  
Notes
2015-08-14 11:44:01PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE ENERGY CALCULATION FORM IS REQUIRED TO BE SIGNED
 BY THE OWNER/AGENT. 2010 FBC ENERGY CONSERVATION SECT.
 101.4.3 & 103.2 (SEE COMMENT # 7 FROM FIRST REVIEW)
  
 2) PROVIDE A STRUCTURAL OVERHANG DETAIL AT THE GABLE
 END RAKED BEAM THAT SPECIFIES THE FRAMING CONNECTORS
 AND OTHER ATTACHMENT DETAILS. ALSO, SPECIFY THE LENGTH
 OF THE OVERHANG. FBC-R 301.1 (SEE COMMENT # 10 FROM
 FIRST REVIEW)
  
 3) THE SLEEPING ROOM WINDOWS ARE REQUIRED COMPLY WITH
 FBC-R 310 FOR EMERGENCY ESCAPE AND RESCUE OPENINGS.
 FBC-R310.1.2 THE MINIMUM NET CLEAR OPENING HEIGHT SHALL
 BE 24 INCHES (610 MM). THE BEDROOM WINDOWS SPECIFIED IN
 THE SCHEDULE ON SHEET 2 ARE 37-1/2" X 50-1/2" SINGLE
 HUNG WINDOWS. THE NET CLEAR OPENING HEIGHT FOR THESE
 WINDOWS IS LESS THAN 24". (SEE COMMENT # 3 FROM FIRST
 REVIEW)
  
 4) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE
 SINGLE HUNG WINDOWS (NOA NO. 13-0430.09) AND THE
 ASPHALT ROOF SHINGLES (FL 10124-R15) ARE REQUIRED TO BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD. FBC 107.3.4 (SEE COMMENT # 11 FROM FIRST
 REVIEW)
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-06-01 Cont ID  
Sent By rmcdouga Date 2015-06-01 Time 19:22 Rev Time 0.00
Received By rmcdouga Date 2015-06-01 Time 16:37 Sent To  
Notes
2015-06-01 19:22:00PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PLANS SPECIFY THAT THE EXPOSURE CATEGORY FOR
 THIS PROJECT IS B. THERE IS A CEMETARY TO THE WEST OF
 THIS LOCATION THAT IS SURFACE ROUGHNESS C. FOR THE
 DISTANCE OF 1500 FT TO THE WEST THE PREVAILING SURFACE
 ROUGHNESS C, THEREFORE THIS PROJECT IS EXPOSURE C.
 FBC-R 301.2.1.4.3
  
 2) A NOTE ON THE FOUNDATION PLAN STATES THAT THE
 CONCRETE SLAB WAS POURED UNDER PREVIOUS PERMIT
 #04070391. THAT PERMIT WAS NEVER APPROVED OR ISSUED AND
 THEREFORE NO INSPECTIONS WERE DONE ON THE FOUNDATION.
 THERE WAS A PERMIT (99121464) TO INSTALL A 4" THICK
 PATIO SLAB WITH THE DIMENSIONS OF 25' X 34' - 3", WHICH
 ARE THE DIMENSIONS OF THE PROPOSED ADDITION. THIS 4"
 PATIO SLAB WILL NOT BE ADEQUATE TO SUPPORT THE EXTERIOR
 WALLS OF THE ADDITION AND THE TERMITE PROTECTION
 REQUIREMENTS WOULD NEED TO BE ADDRESSED. FBC 107.2.1,
 FBC-R 301.1 AND 318
  
 3) THE SLEEPING ROOM WINDOWS ARE REQUIRED COMPLY WITH
 FBC-R 310 FOR EMERGENCY ESCAPE AND RESCUE OPENINGS.
 BASEMENTS, HABITABLE ATTICS AND EVERY SLEEPING ROOM
 SHALL HAVE AT LEAST ONE OPERABLE EMERGENCY ESCAPE AND
 RESCUE OPENING. WHERE BASEMENTS CONTAIN ONE OR MORE
 SLEEPING ROOMS, EMERGENCY EGRESS AND RESCUE OPENINGS
 SHALL BE REQUIRED IN EACH SLEEPING ROOM. WHERE
 EMERGENCY ESCAPE AND RESCUE OPENINGS ARE PROVIDED THEY
 SHALL HAVE A SILL HEIGHT OF NOT MORE THAN 44 INCHES
 (1118 MM) ABOVE THE FLOOR. WHERE A DOOR OPENING HAVING
 A THRESHOLD BELOW THE ADJACENT GROUND ELEVATION SERVES
 AS AN EMERGENCY ESCAPE AND RESCUE OPENING AND IS
 PROVIDED WITH A BULKHEAD ENCLOSURE, THE BULKHEAD
 ENCLOSURE SHALL COMPLY WITH SECTION R310.3. THE NET
 CLEAR OPENING DIMENSIONS REQUIRED BY THIS SECTION SHALL
 BE OBTAINED BY THE NORMAL OPERATION OF THE EMERGENCY
 ESCAPE AND RESCUE OPENING FROM THE INSIDE. EMERGENCY
 ESCAPE AND RESCUE OPENINGS WITH A FINISHED SILL HEIGHT
 BELOW THE ADJACENT GROUND ELEVATION SHALL BE PROVIDED
 WITH A WINDOW WELL IN ACCORDANCE WITH SECTION R310.2.
 EMERGENCY ESCAPE AND RESCUE OPENINGS SHALL OPEN
 DIRECTLY INTO A PUBLIC WAY, OR TO A YARD OR COURT THAT
 OPENS TO A PUBLIC WAY.
 FBC-R310.1.1 MINIMUM OPENING AREA. ALL EMERGENCY ESCAPE
 AND RESCUE OPENINGS SHALL HAVE A MINIMUM NET CLEAR
 OPENING OF 5.7 SQUARE FEET (0.530 M2).
 EXCEPTION: GRADE FLOOR OPENINGS SHALL HAVE A MINIMUM
 NET CLEAR OPENING OF 5 SQUARE FEET (0.465 M2).
  
 FBC-R310.1.2 MINIMUM OPENING HEIGHT.
 THE MINIMUM NET CLEAR OPENING HEIGHT SHALL BE 24 INCHES
 (610 MM).
  
 FBC-R310.1.3 MINIMUM OPENING WIDTH.
 THE MINIMUM NET CLEAR OPENING WIDTH SHALL BE 20 INCHES
 (508 MM).
  
  
 4) THE FOOTING REINFORCING BARS AND SLAB OF THE NEW
 ADDITION SHOULD BE DOWELED INTO THE EXISTING FOOTINGS
 AND SLAB TO PREVENT UNEVEN SETTLEMENT. FBC 107.2.1
  
 5) THE NOTE ON THE EXTERIOR WALL SECTION ON SHEET 4
 CALLS FOR 3/4" STUCCO OVER PAPER-BACKED METAL LATH ON A
 CONCRETE BLOCK EXTERIOR WALL. THIS NOTE APPEARS TO BE
 IN ERROR. CLARIFY. FBC 107.2.1
  
 6) THE EXTERIOR WALL SECTION ON SHEET 4 SPECIFIES 6"
 THICK BATT INSULATION WITH AN R30 INSULATION VALUE.
 THERE IS NO 6" BATT INSULATION WITH AN R-30 VALUE. FBC
 107.2.1
  
 7) SHOW COMPLIANCE WITH 2010 FBC ENERGY CONSERVATION
 SECT. 101.4.3 & 103.2 BY SUBMITTING THE PROPER
 CONSTRUCTION DOCUMENTS. SEE RESIDENTIAL BUILDING FORM
 405.
  
 8) SPECIFY THE R-VALUE FOR THE EXTERIOR WALL INSULATION
 THAT WILL BE USED ON THE PLANS. FBC 107.2.1
  
 9) FBC-R314.3 SMOKE ALARMS SHALL BE INSTALLED IN THE
 FOLLOWING LOCATIONS:
 1. IN EACH SLEEPING ROOM.
 2. OUTSIDE EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE
 VICINITY OF THE BEDROOMS.
  
 10) THE STRUCTURAL OVERHANG DETAIL AT THE GABLE END
 RAKED BEAM DOES NOT SHOW COMPLIANCE WITH WINDLOAD
 UPLIFT REQUIREMENTS. SPECIFY THE LENGTH OF THE
 OVERHANG. FBC-R 301.1
  
 11) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. PROVIDE TWO COMPLETE PRODUCT
 APPROVALS WITH FL OR NOA NUMBERS INCLUDING INSTALLATION
 INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES FOR THE
 ASPHALT SHINGLE AND WINDOWS.
  
 12) FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. THE
 VALUATION OF $50,000.00 APPEARS TO BE LOW. SUBMIT A
 COPY OF THE SIGNED CONTRACT.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-09-04 Cont ID  
Sent By albarran Date 2015-09-04 Time 10:33 Rev Time 0.00
Received By skennedy Date 2015-09-04 Time 10:33 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-06-01 Cont ID  
Sent By albarran Date 2015-06-01 Time 16:07 Rev Time 0.00
Received By albarran Date 2015-06-01 Time 14:03 Sent To  
Notes
2015-06-01 16:08:21PERMIT APPROVED AS FOLLOWS:
 IMPORTANT NOTICE:
 1. YOU SHALL COMPLY W/FBC-R 314 & 315 SMOKE DETECTOR
 REQUIREMENTS.
 2. SMOKE ALARMS SHALL NOT BE INSTALLED WITHIN 36? FROM
 THE TIP OF A CEILING FAN OR ANY FORCED AIR VENT.
 3. SMOKE ALARMS SHALL NOT BE INSTALLED WITHIN 36? OF A
 BATHROOM DOOR CONTAINING A SHOWER OR TUB.
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-09-23 Cont ID  
Sent By rmcdouga Date 2015-09-23 Time 17:16 Rev Time 0.00
Received By rmcdouga Date 2015-09-04 Time 10:44 Sent To  
Notes
2015-09-04 10:44:46TO RMCDOUGA

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-09-04 Cont ID  
Sent By skennedy Date 2015-09-04 Time 10:33 Rev Time 0.00
Received By skennedy Date 2015-07-17 Time 12:48 Sent To  
Notes
2015-07-24 13:23:15R25

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-06-01 Cont ID  
Sent By rmcdouga Date 2015-06-01 Time 19:22 Rev Time 0.00
Received By rmcdouga Date 2015-04-09 Time 14:27 Sent To  
Notes
2015-04-09 14:27:47R01
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 5 Status P Date   Cont ID  
Sent By per SAK Date 2015-10-27 Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status F Date 2015-10-26 Cont ID  
Sent By rmcdouga Date 2015-10-26 Time 13:05 Rev Time 0.00
Received By rmcdouga Date 2015-10-26 Time 12:46 Sent To  
Notes
2015-10-26 13:09:07NEED COPY OF PAID RECEIPT FOR IMPACT FEES.
 MU2015-23061, $1281.90.
2015-10-26 12:46:18MCDOUGAL'S DESK

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2015-09-23 Cont ID  
Sent By rmcdouga Date 2015-09-23 Time 15:40 Rev Time 0.00
Received By rmcdouga Date 2015-09-23 Time 15:40 Sent To  
Notes
2015-09-23 15:41:11BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2015-08-13 Cont ID  
Sent By rmcdouga Date 2015-08-13 Time 17:26 Rev Time 0.00
Received By rmcdouga Date 2015-08-13 Time 17:26 Sent To  
Notes
2015-08-13 17:42:53BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-06-01 Cont ID  
Sent By rmcdouga Date 2015-06-01 Time 16:36 Rev Time 0.00
Received By rmcdouga Date 2015-06-01 Time 16:36 Sent To  
Notes
2015-06-01 16:37:47BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-08-13 Cont ID  
Sent By ccole Date 2015-08-13 Time 07:39 Rev Time 0.00
Received By ccole Date 2015-08-13 Time 07:04 Sent To  
Notes
2015-08-13 07:43:56MECHANICAL APPROVED WITH EXCEPTION.
 8/13/15
  
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S).
 1) REVISE THE AC PLAN TO SHOW THE TOTAL BALANCED 525
 CFM AIR DISTRIBUTION, AND SHOW THE RETURN DUCT SIZES.
 2) PROVIDE A CONDENSER TIE DOWN DETAIL WITH LEGIBLE
 NOTES AND DETAILS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-06-01 Cont ID  
Sent By ccole Date 2015-06-01 Time 11:13 Rev Time 0.00
Received By ccole Date 2015-06-01 Time 11:12 Sent To  
Notes
2015-06-01 11:19:521ST REVIEW: FBC 2010 MECHANICAL
  
 1) PROVIDE MANUAL J AC LOAD CALCULATIONS- SECTION
 403.6.1 FBC-10 ENERGY CONSERVATION.
 2) THE SUBMITTED ENERGY CALCULATION FORM IS OUTDATED.
 THE HOUSE ADDITION WAS NEVER PERMITTED OR INSPECTED
 UNDER EXPIRED #04070391, AND THEREFORE MUST BE APPROVED
 UNDER THE CURRENT CODE IN EFFECT. PLEASE PROVIDE TWO
 COPIES OF EITHER FORM 402-2010 OR FORM 405-2010-
 SECTION 101.4.3 FBC-10 ENERGY.
 3) PROVIDE AN AC EQUIPMENT SCHEDULE ON THE PLAN.
 4) PROVIDE CONDENSER MOUNTING PAD AND CONDENSER
 TIE-DOWN DETAILS IN COMPLIANCE WITH SECTIONS
 M1305.1.4.1 AND M1307.2.1 FBC-10 RESIDENTIAL.
 5) PROVIDE A CONDENSATE DISPOSAL PLAN: SHOW THE TYPE
 AND SIZE OF CONDENSATE PIPING, PIPING RUN, AND DISPOSAL
 LOCATION- SECTION M1411.3 FBC-10 RES. INDICATE A
 SECONDARY OR AUXILIARY MEANS OF DISPOSAL- SECTION
 M1411.3.1.
 6) INDICATE HOW RETURN AIR FROM THE 12X12 GRILL IN THE
 HALLWAY IS RETURNING AIR TO THE AIR HANDLER. IS IT
 BEING DUCTED?
  
 CHRISTOPHER COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-08-21 Cont ID  
Sent By tklarge Date 2015-08-21 Time 01:38 Rev Time 0.00
Received By tklarge Date 2015-08-18 Time 06:15 Sent To  
Notes
2015-09-04 09:30:07SKENNEDY'S DESK
2015-08-21 01:40:52NO INSPECTIONS ON UNDERGROUND SANITARY & WATER ON FILE.
 ALL WORK TO BE EXPOSED FOR INSPECTION. TKL.

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-05-16 Cont ID  
Sent By tklarge Date 2015-05-16 Time 08:17 Rev Time 0.00
Received By tklarge Date 2015-05-16 Time 07:14 Sent To  
Notes
2015-05-16 07:39:42APPROVED W/ PROVISO. THERE IS A NOTE ON SHT. 3 OF 7
 WHICH STATES " UNDERGROUND PLUMBING WAS PLACED UNDER
 PREVIOUS PERMIT # 04070391. THERE WERE NO PLUMBING
 INSPECTIONS DONE UNDER THAT PERMIT NUMBER OR THE
 PLUMBING SUB-PERMIT # 04070395. TKL.

Review Stop Z ZONING
Rev No 2 Status P Date 2015-09-24 Cont ID  
Sent By sgraham Date 2015-09-24 Time 13:38 Rev Time 0.00
Received By sgraham Date 2015-09-24 Time 13:38 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2015-04-16 Cont ID  
Sent By rmcdouga Date 2015-09-24 Time 10:43 Rev Time 0.00
Received By sgraham Date 2015-04-16 Time 12:45 Sent To  
Notes
***NONE***