Plan Review Details - Permit 15040273
Plan Review Stops For Permit 15040273
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-04-26 Cont ID  
Sent By jwitmer Date 2015-04-26 Time 06:22 Rev Time 0.00
Received By jwitmer Date 2015-04-25 Time 14:10 Sent To  
Notes
2015-04-25 14:30:08BUILDING PLAN REVIEW
 W. P. B. REVISION: 15040273
 W. P. B. PERMIT: 12050519
 ADD: 4748 FRED GLADSTONE DR.
 CONT: THE WEITZ CO.
 TEL: (
 E-MAIL:
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SUNDAY APRIL 26/ 2015
 ACTION: DENIED
  
 1) SHEETS 000-G1.02 & 018-E-A101 IN STAIRWELL # 1 BOTH
 INDICATE A NOTE PROVIDE 2 HOUR SHAFT AND A 2 HOUR
 ACCESS PANEL. PLEASE PROVIDE WHAT THIS (2) HOUR FIRE
 RATED ACCESS PANEL WILL BE USED FOR? PLEASE SEE THE
 ONLY ITEMS THAT ARE ALOUD IN THE EXIT STAIRWELL,
 ASSUMING THIS IS AN REQUIRED EXIT? 2010 FBC-B 1022.4
 PENETRATIONS. PENETRATIONS INTO AND OPENINGS THROUGH AN
 EXIT ENCLOSURE ARE PROHIBITED EXCEPT FOR REQUIRED EXIT
 DOORS, EQUIPMENT AND DUCTWORK NECESSARY FOR INDEPENDENT
 VENTILATION OR PRESSURIZATION, SPRINKLER PIPING,
 STANDPIPES, ELECTRICAL RACEWAY FOR FIRE DEPARTMENT
 COMMUNICATION SYSTEMS AND ELECTRICAL RACEWAY SERVING
 THE EXIT ENCLOSURE AND TERMINATING AT A STEEL BOX NOT
 EXCEEDING 16 SQUARE INCHES (0.010 M2). SUCH
 PENETRATIONS SHALL BE PROTECTED IN ACCORDANCE WITH
 SECTION 713. THERE SHALL BE NO PENETRATIONS OR
 COMMUNICATION OPENINGS, WHETHER PROTECTED OR NOT,
 BETWEEN ADJACENT EXIT ENCLOSURES.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-05-11 Cont ID  
Sent By albarran Date 2015-05-11 Time 13:39 Rev Time 0.00
Received By albarran Date 2015-05-11 Time 12:21 Sent To  
Notes
2015-05-11 13:41:09BEEN FILE AND FOUND THAT IT HAD BEEN PREVIOUSLY
 REVIEWED AND APPROVED BY ME, BUT NO ENTRY OF THE SAME
 HAD BEEN MADE INTO COMMUNITY PLUS

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-04-29 Cont ID  
Sent By wjolin Date 2015-04-29 Time 15:57 Rev Time 0.00
Received By wjolin Date 2015-04-29 Time 15:39 Sent To  
Notes
2015-04-29 15:56:574847 FRED GLADSTONE DRIVE
 TRACKING ##15040273
 MASTER #12050519
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET E-M201: PER NFPA 101 SECTION 7.1.3.2.1,
 PENETRATIONS INTO, AND OPENINGS THROUGH, AN EXIT
 ENCLOSURE ASSEMBLY SHALL BE LIMITED TO DOOR ASSEMBLIES
 FROM NORMALLY OCCUPIED SPACES AND CORRIDORS, REQUIRED
 EXIT DOOR OPENINGS, ELECTRICAL CONDUIT SERVING THE EXIT
 ENCLOSURE, DUCTWORK AND EQUIPMENT NECESSARY FOR
 INDEPENDENT STAIR PRESSURIZATION, WATER OR STEAM PIPING
 NECESSARY FOR THE HEATING OR COOLING OF THE EXIT
 ENCLOSURE, SPRINKLER PIPING, STANDPIPES, AND
 PENETRATIONS FOR FIRE ALARM CIRCUITS, WHERE THE
 CIRCUITS ARE INSTALLED IN METAL CONDUIT AND THE
 PENETRATIONS ARE PROTECTED.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-05-12 Cont ID  
Sent By cpuell Date 2015-05-12 Time 12:10 Rev Time 0.00
Received By cpuell Date 2015-04-09 Time 10:10 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By tklarge Date 2015-05-06 Time 06:22 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2015-04-20 Cont ID  
Sent By eschneid Date 2015-04-20 Time 12:14 Rev Time 1.00
Received By eschneid Date 2015-04-20 Time 12:14 Sent To  
Notes
2015-04-20 12:15:44THE LANDSCAPING AND THE FENCE/GATE REQUIRE SEPARATE
 PERMITS WITH PLANS AND ARE NOT APPROVED AS PART OF THIS
 PERMIT REVISION.