Plan Review Details - Permit 15040264
Plan Review Stops For Permit 15040264
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-04-22 Cont ID  
Sent By jgomez Date 2015-04-22 Time 09:36 Rev Time 0.00
Received By jgomez Date 2015-04-22 Time 07:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-04-21 Cont ID  
Sent By jgomez Date 2015-04-21 Time 09:29 Rev Time 0.00
Received By jgomez Date 2015-04-21 Time 09:29 Sent To  
Notes
2015-04-21 09:36:49RESIDENTIAL (R3) RE-ROOF SECOND BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
  
 FLAT ROOF NOA 11-0119.09 SUBMITTED:
  
 1- SELECTED ASSEMBLY FROM PAGE 32 OF 41 CAN NOT BE
 USED. IT IT'S LIMITED BY GENERAL LIMITATION #9. SEE
 PAGE 33 OF 41. GENERAL LIMITATION #9 DOESN'T ALLOW
 RATIONAL ANALYSIS OR EXTRAPOLATION. (RAS 117
 CALCULATIONS). SEE GENERAL LIMITATION #9 ON LAST PAGE
 OF NOA. NEED TO SELECT AN ASSEMBLY THAT IS LIMITED BY
 GENERAL LIMITATION #7, WHICH ALLOWS RATIONAL ANALYSIS
 OR EXTRAPOLATION TO MEET THE DESIGN PRESSURES OF SEC.
 R301.1 OF 2010 FBC-RESIDENTIAL.
  
 2- PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS
 REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA
 SUBMITTED. SEC. R301.1 OF 2010 FBC-RESIDENTIAL. NOTE:
 PRESCRIPTIVE NAIL ENHANCING SUBMITTED IS NOT ALLOWED
 BECAUSE RAS 150 IS NOT ADOPTED BY THE CITY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-04-16 Cont ID  
Sent By jgomez Date 2015-04-16 Time 09:26 Rev Time 0.00
Received By jgomez Date 2015-04-16 Time 08:58 Sent To  
Notes
2015-04-16 09:34:55RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR THE FLAT ROOF TO BE INSTALLED.
  
 2- CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY FROM THE
 SELECTED PRODUCT APPROVAL IS GOING TO BE USED TO VERIFY
 COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301 OF
 2010 FBC-RESIDENTIAL.
  
 3- IF THE FLAT ROOF SELECTED ASSEMBLY DOESN'T MEET THE
 DESIGN PRESSURES REQUIRED BY SEC. R301, THEN SIGNED AND
 SEALED RAS 117 CALCULATIONS ARE REQUIRED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2015-04-14 Cont ID  
Sent By fmittner Date 2015-04-14 Time 15:12 Rev Time 0.00
Received By fmittner Date 2015-04-14 Time 15:12 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-04-22 Cont ID  
Sent By jgomez Date 2015-04-22 Time 07:44 Rev Time 0.00
Received By jgomez Date 2015-04-22 Time 07:43 Sent To  
Notes
2015-04-22 07:44:45RECEIVED E-MAIL FROM WILLIAM RIGGS. PRODUCT APPROVAL
 FL16709. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-04-21 Cont ID  
Sent By jgomez Date 2015-04-21 Time 09:29 Rev Time 0.00
Received By jgomez Date 2015-04-21 Time 11:09 Sent To  
Notes
2015-04-21 11:13:39RECEIVED E-MAIL FROM WILL RIGGS. NOA 11-0119.09.