Plan Review Details - Permit 15040251
Plan Review Stops For Permit 15040251
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2015-07-21 Cont ID  
Sent By dhayes Date 2015-07-21 Time 15:07 Rev Time 0.00
Received By dhayes Date 2015-07-21 Time 15:07 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-07-08 Cont ID  
Sent By dhayes Date 2015-07-08 Time 08:56 Rev Time 0.00
Received By dhayes Date 2015-07-01 Time 19:07 Sent To  
Notes
2015-07-08 11:27:25CONTRACTOR HAS NOT ADDRESSED ORIGINAL REVIEW DEFICIENCY
 COMMENTS. PLEASE READ AND COMPLY WITH ALL THE
 FOLLOWING:
  
 NOTICE: CHAPTER 553.80(2)(B) FLORIDA STATUTES STATES
 THAT A LOCAL GOVERNMENT SHALL IMPOSE A FEE OF FOUR
 TIMES THE FEE FOR PLAN REVIEW, IF PLANS ARE REJECTED
 (3) OR MORE TIMES FOR REPEATED FAILURE TO CORRECT A
 CODE VIOLATION.
  
 1) INDICATE REQUIRED EXIT SIGNS ON THE FLOOR PLAN.
 ACCESS TO EXITS SHALL BE MARKED BY APPROVED, READILY
 VISIBLE SIGNS IN ALL CASES WHERE THE EXIT OR WAY TO
 REACH THE EXIT IS NOT READILY APPARENT TO THE
 OCCUPANTS. NFPA 101 SECTION 7.10.1.5.1
 2) INDICATE REQUIRED EMERGENCY ILLUMINATION. EMERGENCY
 LIGHTING SYSTEMS SHALL BE DESIGNED AND INSTALLED SO
 THAT THE FAILURE OF ANY INDIVIDUAL LIGHTING ELEMENT,
 SUCH AS THE BURNING OUT OF A LAMP CANNOT LEAVE IN TOTAL
 DARKNESS ANY SPACE THAT REQUIRES EMERGENCY
 ILLUMINATION. NEC 700.16
 3) INDICATE CIRCUIT NUMBERS ON THE FLOOR PLAN. THE
 BRANCH CIRCUIT FEEDING THE EMERGENCY LIGHTING SHALL BE
 THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL
 SWITCHES. NEC 700.12
 4) PROVIDE A PANEL SCHEDULE. EVERY CIRCUIT AND CIRCUIT
 MODIFICATION SHALL BE LEGIBLY IDENTIFIED AS TO ITS
 CLEAR, EVIDENT, AND SPECIFIC PURPOSE OR USE. NEC 408.4
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
  
  
2015-07-01 19:37:43I TRIED CONTACTING MR. RAWLS FOR FURTHER EXPLANATION OF
 HIS DESIGN BUT VM WAS FULL. I DEFERRED THIS BACK TO
 DHAYES.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-04-09 Cont ID  
Sent By dhayes Date 2015-04-09 Time 14:45 Rev Time 0.00
Received By dhayes Date 2015-04-09 Time 14:45 Sent To  
Notes
2015-04-09 15:42:511) INDICATE REQUIRED EXIT SIGNS ON THE FLOOR PLAN.
 ACCESS TO EXITS SHALL BE MARKED BY APPROVED, READILY
 VISIBLE SIGNS IN ALL CASES WHERE THE EXIT OR WAY TO
 REACH THE EXIT IS NOT READILY APPARENT TO THE
 OCCUPANTS. NFPA 101 SECTION 7.10.1.5.1
 2) INDICATE REQUIRED EMERGENCY ILLUMINATION. EMERGENCY
 LIGHTING SYSTEMS SHALL BE DESIGNED AND INSTALLED SO
 THAT THE FAILURE OF ANY INDIVIDUAL LIGHTING ELEMENT,
 SUCH AS THE BURNING OUT OF A LAMP CANNOT LEAVE IN TOTAL
 DARKNESS ANY SPACE THAT REQUIRES EMERGENCY
 ILLUMINATION. NEC 700.16
 3) INDICATE CIRCUIT NUMBERS ON THE FLOOR PLAN. THE
 BRANCH CIRCUIT FEEDING THE EMERGENCY LIGHTING SHALL BE
 THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL
 SWITCHES. NEC 700.12
 4) PROVIDE A PANEL SCHEDULE. EVERY CIRCUIT AND CIRCUIT
 MODIFICATION SHALL BE LEGIBLY IDENTIFIED AS TO ITS
 CLEAR, EVIDENT, AND SPECIFIC PURPOSE OR USE. NEC 408.4
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-07-08 Cont ID  
Sent By dhayes Date 2015-07-08 Time 11:27 Rev Time 0.00
Received By dhayes Date 2015-06-29 Time 17:01 Sent To  
Notes
2015-06-29 17:02:24ROUTED TO DAH/CC

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-04-09 Cont ID  
Sent By dhayes Date 2015-04-09 Time 15:42 Rev Time 0.00
Received By dhayes Date 2015-04-08 Time 14:45 Sent To  
Notes
***NONE***