Plan Review Details - Permit 15040249
Plan Review Stops For Permit 15040249
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2015-04-10 Cont ID  
Sent By tklarge Date 2015-04-10 Time 05:13 Rev Time 0.00
Received By tklarge Date 2015-04-10 Time 05:07 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-04-09 Cont ID  
Sent By tklarge Date 2015-04-10 Time 05:13 Rev Time 0.00
Received By dhayes Date 2015-04-09 Time 14:02 Sent To P
Notes
2015-04-09 14:29:54APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN APPROVED
 PROVISIONALLY. FAILURE TO CORRECT THE LISTED
 DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED
 INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION
 FEE(S).
  
 1) WHEN ALTERATIONS, REPAIRS, OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS. FBC-RESIDENTIAL
 314 AND 315.
 2) ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER
 RESISTANT AND AFCI PROTECTED. NEC 210.12, 406.11
 3) ALL 125V SINGLE PHASE, 15 AND 20AMP RECEPTACLES
 INSTALLED IN THE KITCHEN SHALL HAVE GROUND FAULT
 CIRCUIT INTERRUPTER PROTECTION FOR PERSONNEL. NEC
 210.8(6)

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-04-10 Cont ID  
Sent By dhayes Date 2015-04-10 Time 05:13 Rev Time 0.00
Received By tklarge Date 2015-04-08 Time 14:02 Sent To E
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-04-10 Cont ID  
Sent By tklarge Date 2015-04-10 Time 05:07 Rev Time 0.00
Received By tklarge Date 2015-04-10 Time 05:06 Sent To  
Notes
***NONE***