Plan Review Details - Permit 15040220
Plan Review Stops For Permit 15040220
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-06-19 Cont ID  
Sent By rmcdouga Date 2015-06-19 Time 10:40 Rev Time 0.00
Received By rmcdouga Date 2015-06-19 Time 06:57 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-05-20 Cont ID  
Sent By rmcdouga Date 2015-05-20 Time 13:49 Rev Time 0.00
Received By rmcdouga Date 2015-05-19 Time 18:21 Sent To  
Notes
2015-05-20 11:23:06PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE COMPONENT AND CLADDING PRESSURES ON S.01 ARE FOR
 A TWO STORY STRUCTURE WITH A 23'-0" MEAN ROOF HEIGHT.
 THIS PROJECT IS FOR A ONE STORY STRUCTURE WITH A 14'-5"
 MEAN ROOF HEIGHT PER THE ELEVATION DRAWINGS. FBC-R
 301.2.1
  
 2) THE MEAN ROOF HEIGHT IS 15'-4" ON THE NORTH
 ELEVATION ON SHEET A.05 AND IT IS 14'-5" ON THE OTHER
 ELEVATIONS. CLARIFY. FBC 107.2.1
  
 3) PROVIDE STRUCTURAL DETAILS FOR THE 5' MASONRY WALL
 AND GATES AT THE REAR OF THE STRUCTURE. FBC-R 301.2.1
  
 4) SPECIFY THE COMPONENT AND CLADDING DESIGN PRESSURES
 FOR THE 10 : 12 SLOPED AND 1/2" : 12 FLAT ROOF AREAS ON
 THE PLANS. FBC-R 301.2.1
  
 5) IDENTIFY THE TYPE OF WINDOW ( SINGLE HUNG, FIXED,
 HORIZONTAL SLIDING, ETC. ) FOR EACH OPENING ON THE
 PLANS. FBC 107.2.1
  
 6) SPECIFY THE SIZES OF THE DOOR SIDELITES AND OF EACH
 WINDOW WHEN MULTIPLES ARE INSTALLED IN ONE OPENING AS
 IN THE FAMILY ROOM. FBC 107.2.1
  
 7) FBC-R 403.1.4, AS WELL AS, THE SOIL REPORT REQUIRES
 THE BOTTOM OF FOOTINGS TO BE A MINIMUM OF 12" BELOW
 FINAL GRADE. DETAIL 1 ON S.03 FOR THE 18" DEEP FOOTING
 WILL NEED TO BE REVISED SO THAT THE 6" ABOVE GRADE IS
 TO THE FINISHED FLOOR RATHER THAN THE 1-1/2" BLOCK
 RECESS.
  
 8) SUBMIT THE MANUFACTURER'S SPECIFICATIONS FOR THE
 OUTDOOR GRILL AND HOOD WHICH INDICATES THAT IT IS
 LISTED FOR USE ON A COVERED PORCH WITH ONLY ONE SIDE
 OPEN TO THE EXTERIOR. FBC-R G2406.1
  
 9) SUBMIT THE CURRENT EVALUATION REPORT FOR THE SPRAY
 FOAM INSULATION THAT WILL BE USED. FBC-R 316
  
 10) SOME OF THE WINDOWS APPEAR TO BE SINGLE HUNG
 WINDOWS AND THERE WAS NOT A PRODUCT APPROVAL SUBMITTED
 FOR THEM. A PRODUCT APPROVAL WAS SUBMITTED FOR
 HORIZONTAL SLIDING WINDOWS (NOA NO.11-1031.04), BUT
 THERE DOES NOT APPEAR TO BE ANY OF THESE. PLEASE
 CLARIFY. DCA RULE 9N-3
  
 11) SPECIFY THE METHOD OF ATTACHMENT FROM THOSE LISTED
 IN NOA NO. 13-0723.05 THAT WILL BE USED TO INSTALL THE
 CONCRETE ROOF TILE AND PROVIDE ADEQUATE RESISTANCE TO
 THE OVERTURN MOMENT. FBC-R 301.2.1 ( NOTE: IF AN
 ADHESIVE WILL BE USED, SUBMIT IT'S PRODUCT APPROVALS.)
  
 12) SPECIFY THE APPROVED ASSEMBLY AND MAXIMUM DESIGN
 PRESSURE FROM NOA NO. 11-0119.09 ( FIRESTONE MODIFIED
 BITUMEN ROOF SYSTEM) THAT WILL BE INSTALLED. SUBMIT
 SIGNED AND SEALED RAS 117 CALCULATIONS FOR ENHANCED
 FASTENING. FBC-R 301.2.1
  
 13) IN ORDER TO REDUCE PLAN REVIEW TIMES AND PROVIDE
 CLARIFICATION, PLEASE SUBMIT A RESPONSE LETTER
 INDICATING HOW EACH OF THE REVIEW COMMENTS HAS BEEN
 ADDRESSED.
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-05-19 Cont ID  
Sent By rlecky Date 2015-05-19 Time 12:09 Rev Time 0.00
Received By rlecky Date 2015-05-19 Time 10:09 Sent To  
Notes
2015-05-19 12:32:13PROVISO:
  
 HALL AND FOYER RECEPTACLES ARE REQUIRED. NEC 210.52(H)
  
 AN ELECTRICAL GROUNDING SYSTEM IS REQUIRED. NEC 250.24
  
 ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR ALL BRANCH
 CIRCUITS SUPPLYING OUTLETS. NEC 210.12
  
 PROVIDE A 20 AMPERE BRANCH CIRCUIT FOR THE BATHROOMS.
 NEC 210.11 (C) (3)
  
 PROVIDE A 20 AMPERE BRANCH CIRCUIT FOR THE DINING AREA
 OUTLETS. NEC 210.52(B) (1)
  
 A BONDING STRIP IS REQUIRED AT THE ELECTRIC SERVICE
 GROUND. NEC 250.94
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2015-05-09 Cont ID  
Sent By tklarge Date 2015-05-09 Time 06:23 Rev Time 0.00
Received By tklarge Date 2015-05-09 Time 06:23 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-06-19 Cont ID  
Sent By rmcdouga Date 2015-06-19 Time 10:40 Rev Time 0.00
Received By rmcdouga Date 2015-06-04 Time 11:18 Sent To  
Notes
2015-06-05 11:19:07RE-SUBMITTAL SENT TO ROBERT MCDOUGAL FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-05-20 Cont ID  
Sent By rmcdouga Date 2015-05-20 Time 13:49 Rev Time 0.00
Received By rmcdouga Date 2015-04-07 Time 17:32 Sent To  
Notes
2015-04-07 17:32:33SENT TO R29 SHELF FOR REVIEW. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2015-06-19 Cont ID  
Sent By rmcdouga Date 2015-06-19 Time 06:58 Rev Time 0.00
Received By rmcdouga Date 2015-06-19 Time 06:57 Sent To  
Notes
2015-06-19 06:59:18MU2015-7978 FEE PAID WAS $21.91

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-05-20 Cont ID  
Sent By rmcdouga Date 2015-05-20 Time 07:06 Rev Time 0.00
Received By rmcdouga Date 2015-05-20 Time 07:06 Sent To  
Notes
2015-05-20 07:08:03SUBMIT A COPY OF THE PAID IMPACT FEE RECEIPT.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2015-05-19 Cont ID  
Sent By ccole Date 2015-05-19 Time 14:42 Rev Time 0.00
Received By ccole Date 2015-04-07 Time 14:41 Sent To  
Notes
2015-05-19 14:44:18MECHANICAL PROVISO:
  
 1) OUTSIDE AIR SUPPLY FOR AHU-1 SHALL CONNECT TO THE
 RETURN AIR PLENUM, NOT THE SUPPLY PLENUM AS SHOWN ON
 THE PLAN.
  
 CHRISTOPHER COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-05-09 Cont ID  
Sent By tklarge Date 2015-05-09 Time 06:23 Rev Time 0.00
Received By tklarge Date 2015-05-09 Time 05:49 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2015-05-20 Cont ID  
Sent By rmcdouga Date 2015-05-20 Time 10:59 Rev Time 0.00
Received By rmcdouga Date 2015-05-20 Time 07:08 Sent To  
Notes
2015-05-20 10:59:06BORAL TILESEAL NOA NO. 13-1113.05
 BORAL SAXONY 900 CONCRETE ROOF TILE NOA NO. 13-0723.05
 3M AH-160 ROOF TILE ADHESIVE NOA NO. 12-0228.18
 GAF MODIFIED ROOFING NOA NO. 14-0611.01

Review Stop Z ZONING
Rev No 1 Status P Date 2015-04-14 Cont ID  
Sent By sgraham Date 2015-04-14 Time 09:50 Rev Time 0.00
Received By sgraham Date 2015-04-14 Time 09:50 Sent To  
Notes
2015-04-14 10:05:194/14/15 SEPARATE PERMIT AND PLANS FOR LANDSCAPING
 REQUIRED.