Plan Review Details - Permit 15040207
Plan Review Stops For Permit 15040207
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2015-05-29 Cont ID  
Sent By jgomez Date 2015-05-29 Time 16:43 Rev Time 0.00
Received By jgomez Date 2015-05-29 Time 16:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2015-04-27 Cont ID  
Sent By jgomez Date 2015-04-27 Time 15:03 Rev Time 0.00
Received By jgomez Date 2015-04-27 Time 15:03 Sent To  
Notes
2015-04-27 15:03:27 
  
 4/27/15 MET WITH HERB FRANK. SUBMITTAL PACKAGE DIDN'T
 HAVE THE DESIGNER OF RECORD APPROVAL. JG.
  
  
 4/23/15 REVIEWED ENGINEER'S RAS 117 CALCULATIONS.
 WAITING FOR ORIGINAL CALCULATIONS AND COMPLETE
 RESUBMITAL PACKAGE APPROVED BY THE DESIGNER OF RECORD
 TO FINISH PROCESSING THE PERMIT.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2015-04-27 Cont ID  
Sent By jgomez Date 2015-04-23 Time 19:20 Rev Time 0.00
Received By jgomez Date 2015-04-23 Time 15:21 Sent To  
Notes
2015-04-23 19:25:234/23/15 REVIEWED ENGINEER'S RAS 117 CALCULATIONS.
 WAITING FOR ORIGINAL CALCULATIONS AND COMPLETE
 RESUBMITAL PACKAGE APPROVED BY THE DESIGNER OF RECORD
 TO FINISH PROCESSING THE PERMIT.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2015-04-20 Cont ID  
Sent By jgomez Date 2015-04-20 Time 12:56 Rev Time 0.00
Received By jgomez Date 2015-04-20 Time 12:36 Sent To  
Notes
2015-04-20 12:59:11RESIDENTIAL (R3) ROOFING, FOURTH BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- NOA 10-0608.02 SUBMITTED IS FOR INSULATED ASSEMBLIES
 ONLY ALSO. SPECIFY WHICH APPROVED ASSEMBLY IS GOING TO
 BE USED. TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES
 OF SEC. R301.2.1.4 OF 2010 FBC-RESIDENTIAL.
 NOTE: SELECTED APPROVED ASSEMBLY THAT IS LIMITED BY
 GENERAL LIMITATION #9 CAN NOT BE USED IF THE DESIGN
 PRESSURES DON'T MEET THE REQUIRED DESIGN PRESSURES. SEE
 GENERAL LIMITATION # 9 ON LAST PAGE OF NOA SUBMITTED.
  
 2- PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS FOR
 NAIL ENHANCING AT PERIMETER AND CORNER AREAS AS
 REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA
 SUBMITTED. NED THE RAS 117 CALCULATIONS TO MEET THE
 DESIGN PRESSURES REQUIRED BY SEC. 301.2.1.4 OF 2010
 FBC-RESIDENTIAL.
  
 3- DESIGNER OF RECORD NEED TO REVIEW AND APPROVE IN
 WRITING (NOT SIGNING AND SEALING) THE SEALOFLEX PRODUCT
 APPROVAL AS REQUIRED BY SEC. 107.3.4.1 OF CITY
 AMENDMENTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2015-04-20 Cont ID  
Sent By jgomez Date 2015-04-20 Time 10:46 Rev Time 0.00
Received By jgomez Date 2015-04-20 Time 10:31 Sent To  
Notes
2015-04-20 10:37:56RESIDENTIAL (R3) ROOFING, THIRD BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- NOA SUBMITTED IS FOR INSULATED ASSEMBLIES ONLY.
 SPECIFY WHICH APPROVED ASSEMBLY IS GOING TO BE USED. TO
 VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC.
 R301.2.1.4 OF 2010 FBC-RESIDENTIAL.
 NOTE: SELECTED APPROVED ASSEMBLY THAT IS LIMITED BY
 GENERAL LIMITATION #9 CAN NOT BE USED IF THE DESIGN
 PRESSURES DON'T MEET THE REQUIRED DESIGN PRESSURES. SEE
 GENERAL LIMITATION # 9 ON LAST PAGE OF NOA SUBMITTED.
  
 2- PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS FOR
 NAIL ENHANCING AT PERIMETER AND CORNER AREAS AS
 REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA
 12-0418.02 SUBMITTED. NED THE RAS 117 CALCULATIONS TO
 MEET THE DESIGN PRESSURES REQUIRED BY SEC. 301.2.1.4 OF
 2010 FBC-RESIDENTIAL.
  
 3- DESIGNER OF RECORD NEED TO REVIEW AND APPROVE IN
 WRITING (NOT SIGNING AND SEALING) THE SEALOFLEX PRODUCT
 APPROVAL AS REQUIRED BY SEC. 107.3.4.1 OF CITY
 AMENDMENTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-04-13 Cont ID  
Sent By jgomez Date 2015-04-13 Time 17:35 Rev Time 0.00
Received By jgomez Date 2015-04-13 Time 17:35 Sent To  
Notes
2015-04-13 17:36:05RESIDENTIAL (R3) ROOFING, BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- I REVIEWED THE PROPOSED ASSEMBLY W-10 FROM FLORIDA
 PRODUCT APPROVAL FL2920-R8. THIS ASSEMBLY IS GOOD FOR
 -85PSF. ACCORDING TO NOTE # 5 ON PAGE 1 OF 6 OF
 FL2920-R8 THIS ASSEMBLY CAN NOT BE USED BECAUSE IT
 DOESN'T MEET THE DESIGN PRESSURES REQUIRED FOR THIS
 HOUSE AND RATIONAL ANALYSIS IS NOT ALLOWED. THIS HOUSE
 IS LOCATED IN EXPOSURE D. THE DESIGN PRESSURES FOR THE
 PERIMETER AND CORNER AREAS ARE HIGHER THAN -85PSF.
  
 2- DESIGNER OF RECORD NEED TO REVIEW AND APPROVE IN
 WRITING (NOT SIGNING AND SEALING) THE SEALOFLEX PRODUCT
 APPROVAL AS REQUIRED BY SEC. 107.3.4.1 OF CITY
 AMENDMENTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-04-09 Cont ID  
Sent By jgomez Date 2015-04-09 Time 08:06 Rev Time 0.00
Received By jgomez Date 2015-04-09 Time 07:47 Sent To  
Notes
2015-04-09 08:07:13RESIDENTIAL (R3) ROOFING, BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- SPECIFY WHICH APPROVED ASSEMBLY IS GOING TO BE USED.
 TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC.
 R301.2.1.4 OF 2010 FBC-RESIDENTIAL.
 NOTE: SELECTED APPROVED ASSEMBLY THAT IS LIMITED BY
 GENERAL LIMITATION #9 CAN NOT BE USED IF THE DESIGN
 PRESSURES DON'T MEET THE REQUIRED DESIGN PRESSURES. SEE
 GENERAL LIMITATION # 9 ON LAST PAGE OF NOA SUBMITTED.
  
 2- PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS FOR
 NAIL ENHANCING AT PERIMETER AND CORNER AREAS AS
 REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA
 12-0418.02 SUBMITTED. NED THE RAS 117 CALCULATIONS TO
 MEET THE DESIGN PRESSURES REQUIRED BY SEC. 301.2.1.4 OF
 2010 FBC-RESIDENTIAL.
 NOTE: SELECTED APPROVED ASSEMBLY THAT IS LIMITED BY
 GENERAL LIMITATION #9 CAN NOT BE USED IF THE DESIGN
 PRESSURES DON'T MEET THE REQUIRED DESIGN PRESSURES. SEE
 GENERAL LIMITATION # 9 ON LAST PAGE OF NOA SUBMITTED.
  
 3- DESIGNER OF RECORD NEED TO REVIEW AND APPROVE IN
 WRITING (NOT SIGNING AND SEALING) THE SEALOFLEX PRODUCT
 APPROVAL AS REQUIRED BY SEC. 107.3.4.1 OF CITY
 AMENDMENTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2015-05-29 Cont ID  
Sent By jgomez Date 2015-05-29 Time 16:32 Rev Time 0.00
Received By jgomez Date 2015-05-29 Time 16:32 Sent To  
Notes
2015-05-29 16:39:01SUBMITTAL OF PRODUCT APPROVAL REVIEWED BY THE ENGINEER
 OF RECORD. JG.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2015-04-27 Cont ID  
Sent By jgomez Date 2015-04-27 Time 15:01 Rev Time 0.00
Received By jgomez Date 2015-04-27 Time 15:01 Sent To  
Notes
2015-04-27 15:02:484/27/15 MET WITH HERB FRANK. SUBMITTAL PACKAGE DIDN'T
 HAVE THE DESIGNER OF RECORD APPROVAL. JG.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-04-23 Cont ID  
Sent By jgomez Date 2015-04-23 Time 19:20 Rev Time 0.00
Received By jgomez Date 2015-04-23 Time 15:20 Sent To  
Notes
2015-04-23 15:21:43ENGINEER E-MAILED RAS 117 CALCULATIONS. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-04-20 Cont ID  
Sent By jgomez Date 2015-04-20 Time 12:56 Rev Time 0.00
Received By jgomez Date 2015-04-20 Time 12:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-04-20 Cont ID  
Sent By jgomez Date 2015-04-20 Time 10:31 Rev Time 0.00
Received By jgomez Date 2015-04-20 Time 10:30 Sent To  
Notes
2015-04-20 10:31:24HERB FRANK E-MAILED NOA 12-0418.02