Plan Review Stops For Permit 15040207 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
7 |
Status |
P |
Date |
2015-05-29 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2015-05-29 |
Time |
16:43 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2015-05-29 |
Time |
16:32 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
6 |
Status |
F |
Date |
2015-04-27 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2015-04-27 |
Time |
15:03 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2015-04-27 |
Time |
15:03 |
Sent To |
|
|
Notes |
2015-04-27 15:03:27 | | | | | 4/27/15 MET WITH HERB FRANK. SUBMITTAL PACKAGE DIDN'T | | HAVE THE DESIGNER OF RECORD APPROVAL. JG. | | | | | | 4/23/15 REVIEWED ENGINEER'S RAS 117 CALCULATIONS. | | WAITING FOR ORIGINAL CALCULATIONS AND COMPLETE | | RESUBMITAL PACKAGE APPROVED BY THE DESIGNER OF RECORD | | TO FINISH PROCESSING THE PERMIT. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | (561)805-6712 | | [email protected] |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
5 |
Status |
F |
Date |
2015-04-27 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2015-04-23 |
Time |
19:20 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2015-04-23 |
Time |
15:21 |
Sent To |
|
|
Notes |
2015-04-23 19:25:23 | 4/23/15 REVIEWED ENGINEER'S RAS 117 CALCULATIONS. | | WAITING FOR ORIGINAL CALCULATIONS AND COMPLETE | | RESUBMITAL PACKAGE APPROVED BY THE DESIGNER OF RECORD | | TO FINISH PROCESSING THE PERMIT. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | (561)805-6712 | | [email protected] |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
F |
Date |
2015-04-20 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2015-04-20 |
Time |
12:56 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2015-04-20 |
Time |
12:36 |
Sent To |
|
|
Notes |
2015-04-20 12:59:11 | RESIDENTIAL (R3) ROOFING, FOURTH BUILDING REVIEW | | COMMENTS. | | CODE: 2010 FBC. | | | | 1- NOA 10-0608.02 SUBMITTED IS FOR INSULATED ASSEMBLIES | | ONLY ALSO. SPECIFY WHICH APPROVED ASSEMBLY IS GOING TO | | BE USED. TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES | | OF SEC. R301.2.1.4 OF 2010 FBC-RESIDENTIAL. | | NOTE: SELECTED APPROVED ASSEMBLY THAT IS LIMITED BY | | GENERAL LIMITATION #9 CAN NOT BE USED IF THE DESIGN | | PRESSURES DON'T MEET THE REQUIRED DESIGN PRESSURES. SEE | | GENERAL LIMITATION # 9 ON LAST PAGE OF NOA SUBMITTED. | | | | 2- PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS FOR | | NAIL ENHANCING AT PERIMETER AND CORNER AREAS AS | | REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA | | SUBMITTED. NED THE RAS 117 CALCULATIONS TO MEET THE | | DESIGN PRESSURES REQUIRED BY SEC. 301.2.1.4 OF 2010 | | FBC-RESIDENTIAL. | | | | 3- DESIGNER OF RECORD NEED TO REVIEW AND APPROVE IN | | WRITING (NOT SIGNING AND SEALING) THE SEALOFLEX PRODUCT | | APPROVAL AS REQUIRED BY SEC. 107.3.4.1 OF CITY | | AMENDMENTS. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | (561)805-6712 | | [email protected] |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2015-04-20 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2015-04-20 |
Time |
10:46 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2015-04-20 |
Time |
10:31 |
Sent To |
|
|
Notes |
2015-04-20 10:37:56 | RESIDENTIAL (R3) ROOFING, THIRD BUILDING REVIEW | | COMMENTS. | | CODE: 2010 FBC. | | | | 1- NOA SUBMITTED IS FOR INSULATED ASSEMBLIES ONLY. | | SPECIFY WHICH APPROVED ASSEMBLY IS GOING TO BE USED. TO | | VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. | | R301.2.1.4 OF 2010 FBC-RESIDENTIAL. | | NOTE: SELECTED APPROVED ASSEMBLY THAT IS LIMITED BY | | GENERAL LIMITATION #9 CAN NOT BE USED IF THE DESIGN | | PRESSURES DON'T MEET THE REQUIRED DESIGN PRESSURES. SEE | | GENERAL LIMITATION # 9 ON LAST PAGE OF NOA SUBMITTED. | | | | 2- PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS FOR | | NAIL ENHANCING AT PERIMETER AND CORNER AREAS AS | | REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA | | 12-0418.02 SUBMITTED. NED THE RAS 117 CALCULATIONS TO | | MEET THE DESIGN PRESSURES REQUIRED BY SEC. 301.2.1.4 OF | | 2010 FBC-RESIDENTIAL. | | | | 3- DESIGNER OF RECORD NEED TO REVIEW AND APPROVE IN | | WRITING (NOT SIGNING AND SEALING) THE SEALOFLEX PRODUCT | | APPROVAL AS REQUIRED BY SEC. 107.3.4.1 OF CITY | | AMENDMENTS. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | (561)805-6712 | | [email protected] |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2015-04-13 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2015-04-13 |
Time |
17:35 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2015-04-13 |
Time |
17:35 |
Sent To |
|
|
Notes |
2015-04-13 17:36:05 | RESIDENTIAL (R3) ROOFING, BUILDING REVIEW COMMENTS. | | CODE: 2010 FBC. | | | | 1- I REVIEWED THE PROPOSED ASSEMBLY W-10 FROM FLORIDA | | PRODUCT APPROVAL FL2920-R8. THIS ASSEMBLY IS GOOD FOR | | -85PSF. ACCORDING TO NOTE # 5 ON PAGE 1 OF 6 OF | | FL2920-R8 THIS ASSEMBLY CAN NOT BE USED BECAUSE IT | | DOESN'T MEET THE DESIGN PRESSURES REQUIRED FOR THIS | | HOUSE AND RATIONAL ANALYSIS IS NOT ALLOWED. THIS HOUSE | | IS LOCATED IN EXPOSURE D. THE DESIGN PRESSURES FOR THE | | PERIMETER AND CORNER AREAS ARE HIGHER THAN -85PSF. | | | | 2- DESIGNER OF RECORD NEED TO REVIEW AND APPROVE IN | | WRITING (NOT SIGNING AND SEALING) THE SEALOFLEX PRODUCT | | APPROVAL AS REQUIRED BY SEC. 107.3.4.1 OF CITY | | AMENDMENTS. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | (561)805-6712 | | [email protected] |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2015-04-09 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2015-04-09 |
Time |
08:06 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2015-04-09 |
Time |
07:47 |
Sent To |
|
|
Notes |
2015-04-09 08:07:13 | RESIDENTIAL (R3) ROOFING, BUILDING REVIEW COMMENTS. | | CODE: 2010 FBC. | | | | 1- SPECIFY WHICH APPROVED ASSEMBLY IS GOING TO BE USED. | | TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. | | R301.2.1.4 OF 2010 FBC-RESIDENTIAL. | | NOTE: SELECTED APPROVED ASSEMBLY THAT IS LIMITED BY | | GENERAL LIMITATION #9 CAN NOT BE USED IF THE DESIGN | | PRESSURES DON'T MEET THE REQUIRED DESIGN PRESSURES. SEE | | GENERAL LIMITATION # 9 ON LAST PAGE OF NOA SUBMITTED. | | | | 2- PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS FOR | | NAIL ENHANCING AT PERIMETER AND CORNER AREAS AS | | REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA | | 12-0418.02 SUBMITTED. NED THE RAS 117 CALCULATIONS TO | | MEET THE DESIGN PRESSURES REQUIRED BY SEC. 301.2.1.4 OF | | 2010 FBC-RESIDENTIAL. | | NOTE: SELECTED APPROVED ASSEMBLY THAT IS LIMITED BY | | GENERAL LIMITATION #9 CAN NOT BE USED IF THE DESIGN | | PRESSURES DON'T MEET THE REQUIRED DESIGN PRESSURES. SEE | | GENERAL LIMITATION # 9 ON LAST PAGE OF NOA SUBMITTED. | | | | 3- DESIGNER OF RECORD NEED TO REVIEW AND APPROVE IN | | WRITING (NOT SIGNING AND SEALING) THE SEALOFLEX PRODUCT | | APPROVAL AS REQUIRED BY SEC. 107.3.4.1 OF CITY | | AMENDMENTS. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | (561)805-6712 | | [email protected] |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2015-05-29 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2015-05-29 |
Time |
16:32 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2015-05-29 |
Time |
16:32 |
Sent To |
|
|
Notes |
2015-05-29 16:39:01 | SUBMITTAL OF PRODUCT APPROVAL REVIEWED BY THE ENGINEER | | OF RECORD. JG. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2015-04-27 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2015-04-27 |
Time |
15:01 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2015-04-27 |
Time |
15:01 |
Sent To |
|
|
Notes |
2015-04-27 15:02:48 | 4/27/15 MET WITH HERB FRANK. SUBMITTAL PACKAGE DIDN'T | | HAVE THE DESIGNER OF RECORD APPROVAL. JG. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2015-04-23 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2015-04-23 |
Time |
19:20 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2015-04-23 |
Time |
15:20 |
Sent To |
|
|
Notes |
2015-04-23 15:21:43 | ENGINEER E-MAILED RAS 117 CALCULATIONS. JG. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2015-04-20 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2015-04-20 |
Time |
12:56 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2015-04-20 |
Time |
12:36 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2015-04-20 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2015-04-20 |
Time |
10:31 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2015-04-20 |
Time |
10:30 |
Sent To |
|
|
Notes |
2015-04-20 10:31:24 | HERB FRANK E-MAILED NOA 12-0418.02 |
|
|