Plan Review Details - Permit 15040196
Plan Review Stops For Permit 15040196
Review Stop E ELECTRICAL
Rev No 4 Status P Date 2015-06-05 Cont ID  
Sent By tlarge Date 2015-06-05 Time 10:24 Rev Time 0.00
Received By dhayes Date 2015-06-05 Time 10:24 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2015-05-12 Cont ID  
Sent By dhayes Date 2015-05-12 Time 13:49 Rev Time 0.00
Received By dhayes Date 2015-05-12 Time 13:49 Sent To  
Notes
2015-05-12 13:57:053RD REVIEW.
  
 1) PROVIDE AN ELECTRICAL PANEL SCHEDULE INDICATEING THE
 OCPD AND WIRE SIZE FOR THE WATER HEATER CIRCUIT. NEC
 408.8
 ) PROVIDE A LOAD CALCULATION INDICATING THE CAPACITY OF
 THE SERVICE AND PANEL(S) TO SUPPORT THE ADDITIONAL LOAD
 OF THE NEW WATER HEATER.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-05-02 Cont ID  
Sent By dhayes Date 2015-05-02 Time 14:23 Rev Time 0.00
Received By dhayes Date 2015-05-02 Time 14:23 Sent To  
Notes
2015-05-02 14:27:322ND REVIEW. DUPLICATE COMMENTS. PREVIOUS COMMENTS HAVE
 NOT YET BEEN ADDRESSED.
  
 1) SUBMIT AN EXISTING FLOOR PLAN SHOWING THE LOCATION
 OF THE EXISTING WATER HEATER. WHAT WILL BE DONE WITH
 THE EXISTING ELECTRIC? WPB AMEND. TO 2010 FBC SEC.
 107.2.1.
 2) PROVIDE AN ELECTRICAL PANEL SCHEDULE INDICATEING THE
 OCPD AND WIRE SIZE FOR THE WATER HEATER CIRCUIT. NEC
 408.8
 3) PROVIDE THE WIRING METHODS AND MATERIALS PROPOSED
 FOR THE RELOCATION OF THE WATER HEATER CIRCUIT.
 4) PROVIDE MANUFACTURER NAMEPLATE INFORMATION ON THE
 WATER HEATER INDICATING THE REQUIRED OPERATING VOLTAGE
 AND WATTAGE AND NUMBER OF THE ELEMENTS AND TYPE OF
 THERMOSTAT USED
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-04-07 Cont ID  
Sent By dhayes Date 2015-04-07 Time 07:12 Rev Time 0.00
Received By dhayes Date 2015-04-07 Time 07:12 Sent To  
Notes
2015-04-07 07:19:101) SUBMIT AN EXISTING FLOOR PLAN SHOWING THE LOCATION
 OF THE EXISTING WATER HEATER. WHAT WILL BE DONE WITH
 THE EXISTING ELECTRIC? WPB AMEND. TO 2010 FBC SEC.
 107.2.1.
 2) PROVIDE AN ELECTRICAL PANEL SCHEDULE INDICATEING THE
 OCPD AND WIRE SIZE FOR THE WATER HEATER CIRCUIT. NEC
 408.8
 3) PROVIDE THE WIRING METHODS AND MATERIALS PROPOSED
 FOR THE RELOCATION OF THE WATER HEATER CIRCUIT.
 4) PROVIDE MANUFACTURER NAMEPLATE INFORMATION ON THE
 WATER HEATER INDICATING THE REQUIRED OPERATING VOLTAGE
 AND WATTAGE AND NUMBER OF THE ELEMENTS AND TYPE OF
 THERMOSTAT USED
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2015-06-06 Cont ID  
Sent By tklarge Date 2015-06-06 Time 06:46 Rev Time 0.00
Received By tklarge Date 2015-06-02 Time 13:10 Sent To  
Notes
2015-06-02 13:10:30TO DAH DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-05-12 Cont ID  
Sent By dhayes Date 2015-05-12 Time 13:50 Rev Time 0.00
Received By dhayes Date 2015-05-11 Time   Sent To  
Notes
2015-05-12 09:38:48SENT TO D. HAYES DESK.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-05-02 Cont ID  
Sent By dhayes Date 2015-05-02 Time 14:23 Rev Time 0.00
Received By dhayes Date 2015-04-30 Time 12:20 Sent To  
Notes
2015-04-30 12:20:24TO TL DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-04-07 Cont ID  
Sent By dhayes Date 2015-04-07 Time 07:19 Rev Time 0.00
Received By dhayes Date 2015-04-06 Time 16:14 Sent To  
Notes
2015-04-06 16:15:14,<5000 PLUMB
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2015-06-06 Cont ID  
Sent By tklarge Date 2015-06-06 Time 06:46 Rev Time 0.00
Received By tklarge Date 2015-06-06 Time 06:42 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-05-01 Cont ID  
Sent By tklarge Date 2015-05-01 Time 05:44 Rev Time 0.00
Received By tklarge Date 2015-05-01 Time 05:10 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-04-07 Cont ID  
Sent By tklarge Date 2015-04-07 Time 06:17 Rev Time 0.00
Received By tklarge Date 2015-04-07 Time 05:32 Sent To  
Notes
2015-04-07 06:15:291) SUBMIT AN EXISTING FLOOR PLAN SHOWING THE LOCATION
 OF THE EXISTING WATER HEATER. WHAT WILL BE DONE WITH
 THE EXISTING PLUMBING AND ELECTRIC? WPB AMEND. TO 2010
 FBC SEC. 107.2.1.
 2) INDICATE THE OCCUPANCY OF THIS SPACE? WHAT TYPE OF
 BUSINESS IS CURRENTLY OCCUPYING THIS SPACE? FBC
 SEC.302.
 3) INDICATE ON THE PLANS WHAT THESE SINKS WILL BE USED
 FOR? WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 4) WHERE IS THE VENT FOR THE EXISTING SINK? WPB AMEND.
 TO 2010 FBC SEC. 107.2.1.
 5) SUBMIT A WATER RISER FOR REVIEW. SHOW ALL PIPE SIZES
 AND VALVES.
 6) A CLEANOUT IS REQUIRED IN THE STACK FOR THE AIR
 ADMITTANCE VALVE. FPC SEC.708.3.4.
 7) SHOW REQUIREMENTS FOR CONTROLLING THERMAL EXPANSION
 IN THE WATER SUPPLY SYSTEM PER THE 2010 FPC
 SEC.607.3.OF THE 2010 FPC.
 8) SHOW THE WATER LINES ON THE PLAN VIEW. WPB AMEND. TO
 2010 FBC SEC. 107.2.1.
 9) ONE OF THE SINKS SHALL COMPLY WITH THE FL.
 ACCESSIBILITY CODE SEC.212.3, 305, 306, 309 & 606. SHOW
 THE REQD. CLEAR FLOOR SPACE, HEIGHTS, DIMENSIONS OF
 SINK,
 10) INDICATE ON THE PLAN IF THE WATER HEATER IS BEING
 INSTALLED ABOVE OR BELOW THE EXISTING COUNTER. IF ABOVE
 THE CONTER ON A SHELF, A PAN AND PAN DRAIN SHALL BE
 INSTALLED IN ACCORDANCE WITH THE 2010 FPC SEC.504.7.
 11) THE RELIEF LINE SHALL DISCHARGE IN ACCORDANCE WITH
 2010 FPC SEC.504.6.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  