Plan Review Details - Permit 15040181
Plan Review Stops For Permit 15040181
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-06-22 Cont ID  
Sent By skennedy Date 2015-06-22 Time 11:24 Rev Time 0.00
Received By skennedy Date 2015-06-22 Time 11:24 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-04-24 Cont ID  
Sent By jwitmer Date 2015-04-24 Time 13:41 Rev Time  
Received By jwitmer Date 2015-04-24 Time 11:55 Sent To  
Notes
2015-04-24 12:17:30BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15040181
 ADD: 2480 PRESIDENTIAL WAY SUITE # 1504
 CONT: POTTSWORKS CONSTRUCTION
 TEL: (561) 584-2563
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 IMPORTANT NOTICE: EFFECTIVE JUNE 01, 2015
 ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED
 ELECTRONICALLY
 UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS
 SUBMISSION OPTIONS ARE AS FOLLOWS:
 1 UPLOAD VIA THE PROJECT DOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL
 SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED
 NAMING CONVENTION FOR EACH DOCUMENT
 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER
 DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE
 REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT
 TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS
 ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES
 AVAILABLE.
  
 1ST REVIEW
 DATE: FRI. APRIL 24/ 2015
 ACTION: DENIED
  
 1) SUBMITTED AS PART OF THE PERMIT PACKAGE IS NAC FLOOR
 SOUND CONTROL AND WITHIN THE SALES BROCHURE CIRCLED ARE
 THE PRODUCT SAM 3 90 MEMBRANE AND SUPER SAM 125
 MEMBRANE. PLEASE PROVIDE THE THICKNESS OF THE CONCRETE
 SLABS FOR THIS BUILDING.
  
 2) FLOOR INSULATION FOR SOUND WILL NEED TO MEET THE
 FOLLOWING CRITERIA, PROVIDE TEST REPORTS:
 BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION
  
 2A) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 2B) FBC-B 2010 1207.2 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 3) FLAME SPREAD- FBC-B 2010 603.1.2 EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 703.4 NONCOMBUSTIBILITY TESTS.
 THE TESTS INDICATED IN SECTIONS 703.4.1 AND 703.4.2
 SHALL SERVE AS CRITERIA FOR ACCEPTANCE OF BUILDING
 MATERIALS AS SET FORTH IN SECTIONS 602.2, 602.3 AND
 602.4 IN TYPE I, II, III AND IV CONSTRUCTION. THE TERM
 ?NONCOMBUSTIBLE? DOES NOT APPLY TO THE FLAME SPREAD
 CHARACTERISTICS OF INTERIOR FINISH OR TRIM MATERIALS. A
 MATERIAL SHALL NOT BE CLASSIFIED AS A NONCOMBUSTIBLE
 BUILDING CONSTRUCTION MATERIAL IF IT IS SUBJECT TO AN
 INCREASE IN COMBUSTIBILITY OR FLAME SPREAD BEYOND THE
 LIMITATIONS HEREIN ESTABLISHED THROUGH THE EFFECTS OF
 AGE, MOISTURE OR OTHER ATMOSPHERIC CONDITIONS.
  
 703.4.1 ELEMENTARY MATERIALS.
 MATERIALS REQUIRED TO BE NONCOMBUSTIBLE SHALL BE TESTED
 IN ACCORDANCE WITH ASTM E 136.
  
 703.4.2 COMPOSITE MATERIALS.
 MATERIALS HAVING A STRUCTURAL BASE OF NONCOMBUSTIBLE
 MATERIAL AS DETERMINED IN ACCORDANCE WITH SECTION
 703.4.1 WITH A SURFACING NOT MORE THAN 0.125 INCH (3.18
 MM) THICK THAT HAS A FLAME SPREAD INDEX NOT GREATER
 THAN 50 WHEN TESTED IN ACCORDANCE WITH ASTM E 84 OR UL
 723 SHALL BE ACCEPTABLE AS
 NONCOMBUSTIBLE MATERIALS.
  
 4) THE MASTER BATH SHOWER INDICATES THE 3'-0" HIGH WALL
 THAT BACKS UP TO THE TUB WILL BE RETILED, PLEASE REVIEW
 THE LIMITATIONS TO THE USE OF GREEN BOARD, (MOISTURE
 RESISTANT)> 2509.3 LIMITATIONS.
 WATER-RESISTANT GYPSUM BACKING BOARD SHALL NOT BE USED
 IN THE FOLLOWING LOCATIONS:
  
 1. OVER A VAPOR RETARDER IN SHOWER OR BATHTUB
 COMPARTMENTS.
  
 2. WHERE THERE WILL BE DIRECT EXPOSURE TO WATER OR IN
 AREAS SUBJECT TO CONTINUOUS HIGH HUMIDITY.
  
 3. ON CEILINGS WHERE FRAME SPACING EXCEEDS 12 INCHES
 (305 MM) O.C. FOR 1/2-INCH-THICK (12.7 MM)
 WATER-RESISTANT GYPSUM BACKING BOARD AND MORE THAN 16
 INCHES (406 MM) O.C. FOR 5/8-INCH-THICK (15.9 MM)
 WATER-RESISTANT GYPSUM BACKING BOARD.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-06-22 Cont ID  
Sent By skennedy Date 2015-06-22 Time 11:10 Rev Time 0.00
Received By skennedy Date 2015-06-22 Time 11:10 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-05-11 Cont ID  
Sent By dhayes Date 2015-05-11 Time 07:26 Rev Time 0.00
Received By dhayes Date 2015-05-11 Time 07:26 Sent To  
Notes
2015-05-11 07:59:225/11/2015
 PROJECT: M/M BIKOFSKY
 PERMIT#: 15040181
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW
 COMMENTS:
  
 1) R314.3.1 ALTERATIONS, REPAIRS AND ADDITIONS.
 WHEN ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, THE DWELLING UNIT SHALL BE EQUIPPED WITH
 SMOKE ALARMS AS REQUIRED FOR NEW DWELLINGS.
 INDICATE THE REQUIRED SMOKE DETECTORS. IF THE REQUIRED
 SMOKE DETECTORS ARE EXISTING, INDICATE THAT THEY ARE
 EXISTING TO REMAIN IN LOCATIONS AS REQUIRED BY THE
 FBC-R 314, AND 315 FOR CARBON MONOXIDE DETECTORS IF
  
 2) FBC-E 502.3.8 RECESSED LIGHTING.
 RECESSED LUMINAIRES INSTALLED IN THE BUILDING THERMAL
 ENVELOPE SHALL BE SEALED TO LIMIT AIR LEAKAGE BETWEEN
 CONDITIONED AND UNCONDITIONED SPACES.
  
 3) 210.52 (D) BATHROOMS. IN DWELLING UNITS,
 AT LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED IN
 BATHROOMS WITHIN (3 FT) OF THE OUTSIDE EDGE OF EACH
 BASIN.
 3A) NEC 210.8 GROUND-FAULT CIRCUIT-INTERRUPTER
 PROTECTION FOR PERSONNEL.
 (A) ALL 125-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE
 RECEPTACLES INSTALLED IN THE LOCATIONS SPECIFIED IN (1)
 THROUGH (8) SHALL HAVE GROUND-FAULT CIRCUIT-INTERRUPTER
 PROTECTION FOR PERSONNEL. (1) BATHROOMS
 3B) NEC 210.11(C)
 PROVIDE A 20 AMPERE BRANCH CIRCUIT FOR THE BATHROOMS.
 INDICATE THE REQUIRED 20AMP CIRCUIT AND GFI RECEPTACLES
 AS INDICATED IN THE NEC 210.52(D), NEC 210.52.8(A)(1)
 AND NEC 210.11(C).
  
 4) NEC 210.12
 ALL NEW GENERAL PURPOSE OUTLETS MUST BE AFCI PROTECTED.
  
 5) NEC 406.11
 ALL NEW GENERAL PURPOSE RECEPTACLES MUST BE TAMPER
 RESISTANT.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-06-22 Cont ID  
Sent By skennedy Date 2015-06-22 Time 11:24 Rev Time 0.00
Received By skennedy Date 2015-06-04 Time 12:46 Sent To  
Notes
2015-06-04 13:24:33RE-SUBMITTAL SENT TO B1 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-05-11 Cont ID  
Sent By dhayes Date 2015-05-11 Time 07:59 Rev Time  
Received By dhayes Date 2015-04-06 Time   Sent To  
Notes
2015-04-06 16:39:37SENT TO B20.

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-06-22 Cont ID  
Sent By skennedy Date 2015-06-22 Time 11:08 Rev Time 0.00
Received By skennedy Date 2015-06-22 Time 11:08 Sent To  
Notes
2015-06-04 13:28:26NEW DRAWINGS SUBMITTED. JG.

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-05-10 Cont ID  
Sent By tklarge Date 2015-05-10 Time 04:31 Rev Time 0.00
Received By tklarge Date 2015-05-10 Time 04:04 Sent To  
Notes
***NONE***