Plan Review Details - Permit 15040162
Plan Review Stops For Permit 15040162
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2015-04-15 Cont ID  
Sent By tklarge Date 2015-04-15 Time 06:50 Rev Time 0.00
Received By tklarge Date 2015-04-15 Time 06:31 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2015-04-08 Cont ID  
Sent By tklarge Date 2015-04-08 Time 09:18 Rev Time 0.00
Received By tklarge Date 2015-04-08 Time 09:04 Sent To  
Notes
2015-04-08 09:18:531) THE SUBMITTED PLANS SHOW THE TANKLESS WATER HEATER
 LOCATED ON THE INTERIOR OF THE STRUCTUR BUT THE
 SUBMITTED MANUF. SPECIFICATIONS ARE FOR AN OUTDOOR
 MODEL. SUBMIT THE CORRECT SPECIFICATIONS FOR AN INDOOR
 UNIT. WPB AMEND. TO 2010 FBC SEC.107.2.1.
 2) SHOW THE CAPPED OFF LINE FOR THE UNDERGROUND LINE ON
 THE RISER DIAGRAM. WPB AMEND. TO 2010 FBC SEC.107.2.1,
 107.3.5.3.
 3) SIZE THE STEEL LINE TO THE DRYER AND THE TANKLESS
 WATER HEATER ON THE RISER.WPB AMEND. TO 2010 FBC
 SEC.107.2.1.
 4) INDICATE ON THE PLAN IF THE DRYER IS LOCATED IN A
 CLOSET. IF SO, PROVIDE THE CUBIC FEET OF THE CLOSET.
 COMPLY WITH THE 2010 FGC SEC.614.5.IF LOUVERED DOORS
 ARE ON THE CLOSET, COMPLY WITH THE FGC SEC.304.10 FOR
 THE CALCULATION OF THE NET FREE AREA.
 5) SUBMIT A VENT DETAIL FOR THE TANKLESS WATER HEATER.
 COMPLY WITH 2010 FGC SEC.502,503.2.3, 503.8 (3).
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-04-15 Cont ID  
Sent By tklarge Date 2015-04-15 Time 06:50 Rev Time 0.00
Received By tklarge Date 2015-04-15 Time 06:31 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved