Plan Review Details - Permit 15040159
Plan Review Stops For Permit 15040159
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2015-04-15 Cont ID  
Sent By tklarge Date 2015-04-15 Time 09:01 Rev Time 0.00
Received By tklarge Date 2015-04-15 Time 09:01 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2015-04-08 Cont ID  
Sent By tklarge Date 2015-04-08 Time 06:44 Rev Time 0.00
Received By tklarge Date 2015-04-08 Time 06:22 Sent To  
Notes
2015-04-08 06:44:181) THE SUBMITTED RINNAI SPECS ARE FOR AN OUTDOOR ONLY
 MODEL AND THE PLANS SHOW THE UNIT INSIDE THE GARAGE.
 SUBMIT COMPLETE MANUF. SPECS FOR AN INDOOR UNIT. WPB
 AMEND. TO 2010 FBC SEC. 107.2.1.
 2) SUBMIT MANUF. SPECIFICATION SHEETS FOR THE RANGE AND
 THE DRYER. ALL APPLIANCES SHALL BE LISTED AND LABELED.
 FGC 301.3.
 3)SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE
 TANKLESS WATER HEATER, DRYER AND RANGE.. COMPLY WITH
 THE 2010 FGC SEC.304.1.
 4) PER TABLE 402.4 (13), THE MAXIMUM ALLOWED BTU LOAD
 FOR 3/4" CSST (EHD 25) IS 97,000 BTU'S AND THE SYSTEM
 LOAD IS 100,000.
 5) SHOW THE SEPARATION WALL BETWEEN THE STRUCTURE AND
 THE GARAGE. AS DRAWN AND LABELED, THE APPLIANCES APPEAR
 TO BE LOCATED IN THE GARAGE..
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-04-15 Cont ID  
Sent By tklarge Date 2015-04-15 Time 09:02 Rev Time 0.00
Received By tklarge Date 2015-04-15 Time 09:02 Sent To  
Notes
***NONE***