Plan Review Details - Permit 15040080
Plan Review Stops For Permit 15040080 |
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2015-04-11 |
|
|
Cont ID |
|
Sent By |
dhayes |
Date |
2015-04-11 |
Time |
13:48 |
Rev Time |
0.00 |
Received By |
dhayes |
Date |
2015-04-11 |
Time |
13:28 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2015-04-07 |
|
|
Cont ID |
|
Sent By |
dhayes |
Date |
2015-04-07 |
Time |
08:08 |
Rev Time |
0.00 |
Received By |
dhayes |
Date |
2015-04-07 |
Time |
08:07 |
Sent To |
|
|
Notes |
2015-04-07 08:13:05 | SEE FIRE DEPT COMMENTS. IN ADDITION TO THE FIRE DEPT | | COMMENTS PROVIDE WIRE TYPES AND SIZES FOR WIRING | | METHODS PROPOSED. | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | 561-805-6717 OR [email protected] |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
F |
Date |
2015-04-10 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2015-04-10 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2015-04-09 |
Time |
10:29 |
Sent To |
E |
|
Notes |
2015-04-10 10:08:45 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | THERE IS INSUFFICIENT INFORMATION SUBMITTED TO | | DETERMINE IF THE PROPOSED RESTRICTED EGRESS AND LOCKING | | OF EXITS AT THIS FACILITY IS MEETING THE CODE INTENT. | | | | WORK HAS BEEN COMPLETED AND ON GOING RELATED TO THIS | | SUBMITTAL WITHOUT A PERMIT THAT IS COMPROMISING THE | | INTEGRITY OF THE EXIT DOORS AND EXIT STAIRWELLS. | | | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2015-04-03 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2015-04-03 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2015-04-03 |
Time |
14:54 |
Sent To |
E |
|
Notes |
2015-04-03 15:08:42 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | 1)THERE ARE NUMEROUS NUMBERS AND LETTERS WITH VARIOUS | | FIGURES THAT ARE NOT IDENTIFEID. PROVIDE A LEGEND THAT | | IDENTIFIES EACH DEVICE AND/OR LOCATION. | | | | 2) PROVIDE MANUFACTURES PRODUCT/EQUIPMENT SPEC SHEET | | FOR EACH DEVICE. | | | | 3) PROVIDE A LETTER OF INTENT AND OR DESIGN AS TO WHAT | | IS BEING PROPOSED; INCLUDE WHAT AND HOW THIS SYTEM WILL | | FUNCTION IF APPROVED. | | | | 4) PROVIDE A SEQUENCE OF OPERATION. | | | | 5) PROVIDE THE FLORIDA FIRE PREVENTION CODE AND/OR | | NATIONAL FIRE PREVENTION ASSOCIATION CODE REFERENCE | | THAT THIS INSTALLATION IS PROPOSING TO COMPLY WITH. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2015-04-11 |
|
|
Cont ID |
|
Sent By |
dhayes |
Date |
2015-04-11 |
Time |
13:48 |
Rev Time |
0.00 |
Received By |
dhayes |
Date |
2015-04-07 |
Time |
09:48 |
Sent To |
|
|
Notes |
2015-04-08 09:49:21 | RE-SUBMITTAL SENT TO FIRE FOR REVIEW. JG. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2015-04-07 |
|
|
Cont ID |
|
Sent By |
dhayes |
Date |
2015-04-07 |
Time |
08:13 |
Rev Time |
|
Received By |
dhayes |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2015-04-02 12:29:12 | ROUTED TO FIRE |
|
|
|