Plan Review Details - Permit 15040080
Plan Review Stops For Permit 15040080
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-04-11 Cont ID  
Sent By dhayes Date 2015-04-11 Time 13:48 Rev Time 0.00
Received By dhayes Date 2015-04-11 Time 13:28 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-04-07 Cont ID  
Sent By dhayes Date 2015-04-07 Time 08:08 Rev Time 0.00
Received By dhayes Date 2015-04-07 Time 08:07 Sent To  
Notes
2015-04-07 08:13:05SEE FIRE DEPT COMMENTS. IN ADDITION TO THE FIRE DEPT
 COMMENTS PROVIDE WIRE TYPES AND SIZES FOR WIRING
 METHODS PROPOSED.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2015-04-10 Cont ID  
Sent By pleduc Date 2015-04-10 Time   Rev Time 0.00
Received By pleduc Date 2015-04-09 Time 10:29 Sent To E
Notes
2015-04-10 10:08:45THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THERE IS INSUFFICIENT INFORMATION SUBMITTED TO
 DETERMINE IF THE PROPOSED RESTRICTED EGRESS AND LOCKING
 OF EXITS AT THIS FACILITY IS MEETING THE CODE INTENT.
  
 WORK HAS BEEN COMPLETED AND ON GOING RELATED TO THIS
 SUBMITTAL WITHOUT A PERMIT THAT IS COMPROMISING THE
 INTEGRITY OF THE EXIT DOORS AND EXIT STAIRWELLS.
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-04-03 Cont ID  
Sent By pleduc Date 2015-04-03 Time   Rev Time 0.00
Received By pleduc Date 2015-04-03 Time 14:54 Sent To E
Notes
2015-04-03 15:08:42THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1)THERE ARE NUMEROUS NUMBERS AND LETTERS WITH VARIOUS
 FIGURES THAT ARE NOT IDENTIFEID. PROVIDE A LEGEND THAT
 IDENTIFIES EACH DEVICE AND/OR LOCATION.
  
 2) PROVIDE MANUFACTURES PRODUCT/EQUIPMENT SPEC SHEET
 FOR EACH DEVICE.
  
 3) PROVIDE A LETTER OF INTENT AND OR DESIGN AS TO WHAT
 IS BEING PROPOSED; INCLUDE WHAT AND HOW THIS SYTEM WILL
 FUNCTION IF APPROVED.
  
 4) PROVIDE A SEQUENCE OF OPERATION.
  
 5) PROVIDE THE FLORIDA FIRE PREVENTION CODE AND/OR
 NATIONAL FIRE PREVENTION ASSOCIATION CODE REFERENCE
 THAT THIS INSTALLATION IS PROPOSING TO COMPLY WITH.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-04-11 Cont ID  
Sent By dhayes Date 2015-04-11 Time 13:48 Rev Time 0.00
Received By dhayes Date 2015-04-07 Time 09:48 Sent To  
Notes
2015-04-08 09:49:21RE-SUBMITTAL SENT TO FIRE FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-04-07 Cont ID  
Sent By dhayes Date 2015-04-07 Time 08:13 Rev Time  
Received By dhayes Date   Time   Sent To  
Notes
2015-04-02 12:29:12ROUTED TO FIRE