Plan Review Details - Permit 15040056
Plan Review Stops For Permit 15040056
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2015-04-23 Cont ID  
Sent By jwitmer Date 2015-04-23 Time 17:56 Rev Time 0.00
Received By jwitmer Date 2015-04-23 Time 17:20 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-05-26 Cont ID  
Sent By pleduc Date 2015-05-27 Time 17:11 Rev Time 0.00
Received By albarran Date 2015-05-26 Time 12:53 Sent To FIRE
Notes
2015-05-26 13:14:41ALL PREVIOUS COMMENTS HAVE BEEN ADDRESSED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-05-07 Cont ID  
Sent By albarran Date 2015-05-07 Time 15:39 Rev Time 0.00
Received By albarran Date 2015-05-07 Time 14:30 Sent To I
Notes
2015-05-07 16:08:08THE FOLLOWING ITEMS NEED ATTEN/CORRECTION FOR A
 SUCCESSFUL REVIEW:
 PG. E1.1
 1. EVEN IF AS EXISTING, THE LIFE SAFETY ILLUMINATION
 SHALL BE SHOWN ON THE PLANS TO VERIFY COMPLIANCE
 2, OFFICE RM 409 IS MISSING AN EXIT SIGN ABOVE THE DOOR
 AS WELL AS EMERGENCY LIGHTING INSIDE THE ROOM. AS PER
 NEC700.16, THERE CANT BE A ROOM LEFT IN TOTAL DARKNESS
 IN THE EVEN OF A POWER FAILURE.
 PG. E1.2
 1. ACCORDING TO THE NOTES, THE AREA ABOVE THE CEILING
 IS ALL A PLENUM, MAKE CERTAIN THAT THE NEW TRANSFORMER
 INDICATED ABOVE THE CEILING IT THE IT ROOM IS LISTED
 FOR A PLENUM.
 PG. E2.1
 1. VENDING MACHINES AND/OR THEIR CIRCUIT SHALL COMPLY
 WITH NEC422..51
 2. NEW PANEL "LC" AS WELL AS ALL EXISTING, SHALL BEAR
 THE REQUIRED FLASH PROTECTION DECAL AS INDICATED IN
 NEC110.16
 3. THE RISER DIAGRAM IS NOT COMPLETE. THE RISER DIAGRAM
 SHALL INCLUDE IN ADDITION TO ALL THE EXISTING LOADS,
 THE STANDBY GENERATOR AS WELL.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-05-27 Cont ID  
Sent By pleduc Date 2015-05-27 Time   Rev Time 0.00
Received By pleduc Date 2015-05-27 Time 17:09 Sent To PC
Notes
2015-05-27 17:12:40THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 1) THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF
 THE 5TH EDITION OF FLORIDA FIRE PREVENTION CODE
 INCLUDING THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND
 ALL OTHER APPLICABLE CODES OR STANDARDS.
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2010 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2010 EDITION.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2009 EDITION.
 FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 10, 2010 EDITION.
 ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION.
  
 2) THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF
 THE FIRE ALARM AND SPRINKLER SYSTEM FOR CODE COVERAGE
 AND COMPLIANCE.
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-04-09 Cont ID  
Sent By pleduc Date 2015-04-09 Time   Rev Time 0.00
Received By pleduc Date 2015-04-09 Time 13:47 Sent To  
Notes
2015-04-09 14:00:37THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 1) THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF
 THE 5TH EDITION OF FLORIDA FIRE PREVENTION CODE
 INCLUDING THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND
 ALL OTHER APPLICABLE CODES OR STANDARDS.
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2010 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2010 EDITION.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2009 EDITION.
 FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 10, 2010 EDITION.
 ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION.
  
 2) THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF
 THE FIRE ALARM AND SPRINKLER SYSTEM FOR CODE COVERAGE
 AND COMPLIANCE.
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-05-27 Cont ID  
Sent By albarran Date 2015-05-27 Time   Rev Time 0.00
Received By pleduc Date 2015-05-20 Time   Sent To E
Notes
2015-05-21 16:17:17M. ALBARRAN'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-05-07 Cont ID  
Sent By skennedy Date 2015-05-07 Time 16:12 Rev Time 0.00
Received By skennedy Date 2015-04-02 Time 12:22 Sent To  
Notes
2015-04-03 12:23:01C01
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2015-04-23 Cont ID  
Sent By jwitmer Date 2015-04-23 Time 17:56 Rev Time 0.00
Received By jwitmer Date 2015-04-23 Time 17:40 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2015-04-12 Cont ID  
Sent By tklarge Date 2015-04-12 Time 07:41 Rev Time 0.00
Received By tklarge Date 2015-04-12 Time 07:20 Sent To  
Notes
***NONE***