Plan Review Details - Permit 15040016
Plan Review Stops For Permit 15040016
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2015-07-27 Cont ID  
Sent By jwitmer Date 2015-07-27 Time 12:30 Rev Time 0.00
Received By jwitmer Date 2015-07-27 Time 11:50 Sent To  
Notes
2015-07-27 12:23:56BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15040016
 ADD: 701 N. ROSEMARY AVE.
 CONT: ADVANCED CONSTRUCTION
 TEL: (561)262-6037
 E-MAIL:
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 5TH REVIEW
 DATE: MON. JULY 27/2015
 ACTION: DENIED
  
  
 1) BUILDING PROVISO: PLANS RED LINED FOR ACCESSIBILITY.
 SHEET AD103 TO MEET W. P. B. CITY STANDARD OF DOUBLE
 STRIPING SEE W.P. B. MUNI CODE SECTION 94-485.
  
 2) PROVISO: A REVISION MAYBE NECESSARY TO SHOW
 ADDITIONAL DETAILS. SHEET AS201 SHOW DETAIL 2 OOF
 FRAMING FOR THE SIDEWALL & NEW ROOF. THIS DETAIL FAILS
 TO PROVIDE THE CONNECTION TO THE EXISTING ROOF FRAMING,
 DOES THE EXISTING LAST FRAMING MEMBER GET DOUBLED? DOES
 THIS FRAMING MEMBER REQUIRE ADDITIONAL STAPPING FOR THE
 ADDITIONAL UPLIFT OF A LARGER TRIBUTARY AREA AND BEING
 PART OF THE MWFRS?
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2015-07-13 Cont ID  
Sent By jwitmer Date 2015-07-13 Time 11:56 Rev Time 0.00
Received By jwitmer Date 2015-07-13 Time   Sent To  
Notes
2015-07-13 11:53:59BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15040016
 ADD: 701 N. ROSEMARY AVE.
 CONT: ADVANCED CONSTRUCTION
 TEL: (561)262-6037
 E-MAIL:
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 4TH REVIEW
 DATE: MON. JULY 13/2015
 ACTION: DENIED
  
 NOTICE !!!!!! THE 2ND SET OF PLANS WERE SUBMITTED,
 MISSING SHEET AD101, DATED 3/25/15.
  
 1) COMPLIED.
  
  
 2) BUILDING PROVISO: PLANS RED LINED FOR ACCESSIBILITY.
 SHEET AD103 TO MEET W. P. B. CITY STANDARD OF DOUBLE
 STRIPING SEE W.P. B. MUNI CODE SECTION 94-485.
  
 3) COMPLIED. ACCESSIBLE ACCESS AISLE AND WLKWAY TO
 ACCESSIBLE ENTRY.
  
 4) COMPLIED> PLANS DO NOT INDICATE COMPLIANCE WITH 2010
 FL ACCESS. CODE 904.4 SALES AND SERVICE COUNTERS.
 SALES COUNTERS AND SERVICE COUNTERS SHALL COMPLY WITH
 904.4.1 OR 904.4.2. THE ACCESSIBLE PORTION OF THE
 COUNTER TOP SHALL EXTEND THE SAME DEPTH AS THE SALES OR
 SERVICE COUNTER TOP.
  
 5) COMPLIED.WIND DESIGN CRITERIA
  
 6A) 3RD REQUEST. SHEET AD201 HAS A CHANGE IN WINDOW
 STYLE, THE LAST SUBMITTAL THE FRONT ELEVAION INDICATED
 THE USE OF PGT SERIES PW 3020 PICTURE WINDOWS,
 SUBMITTED NOA 12-0516.05. THIS SUBMITTAL SHEET AD201
 THE FRONT ELEVATION NOW SHOWS STOREFRONT WINDOW SYSTEM.
 THE SUBMITTED NOA US ALUMINUM NOA # 14-0331.02 HAS NOT
 BEEN REVIEWED BY THE DESIGNER OF RECORD.
  
 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 6B)COMPLIED.
  
 7) NOT APPLICABLE NO NEW ROOF SYSTEM.
  
 8) PROVISO: A REVISION MAYBE NECESSARY TO SHOW
 ADDITIONAL DETAILS. SHEET AS201 SHOW DETAIL 2 OOF
 FRAMING FOR THE SIDEWALL & NEW ROOF. THIS DETAIL FAILS
 TO PROVIDE THE CONNECTION TO THE EXISTING ROOF FRAMING,
 DOES THE EXISTING LAST FRAMING MEMBER GET DOUBLED? DOES
 THIS FRAMING MEMBER REQUIRE ADDITIONAL STAPPING FOR THE
 ADDITIONAL UPLIFT OF A LARGER TRIBUTARY AREA AND BEING
 PART OF THE MWFRS?
  
 9) IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2015-07-01 Cont ID  
Sent By jwitmer Date 2015-07-01 Time 09:07 Rev Time 0.00
Received By jwitmer Date 2015-07-01 Time 07:30 Sent To  
Notes
2015-07-01 09:07:32BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15040016
 ADD: 701 N. ROSEMARY AVE.
 CONT: ADVANCED CONSTRUCTION
 TEL: (561)262-6037
 E-MAIL:
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: WED. JULY 01/2015
 ACTION: DENIED
  
 NOTICE !!!!!! ONLY (1) SET OF PLANS WERE RESUBMITTED
 !!!!!!!
  
 1) COMPLIED.
  
  
 2) BUILDING PROVISO: PLANS RED LINED FOR ACCESSIBILITY.
 SHEET AD103 TO MEET W. P. B. CITY STANDARD OF DOUBLE
 STRIPING SEE W.P. B. MUNI CODE SECTION 94-485.
  
 3) COMPLIED. ACCESSIBLE ACCESS AISLE AND WLKWAY TO
 ACCESSIBLE ENTRY.
  
 4) COMPLIED> PLANS DO NOT INDICATE COMPLIANCE WITH 2010
 FL ACCESS. CODE 904.4 SALES AND SERVICE COUNTERS.
 SALES COUNTERS AND SERVICE COUNTERS SHALL COMPLY WITH
 904.4.1 OR 904.4.2. THE ACCESSIBLE PORTION OF THE
 COUNTER TOP SHALL EXTEND THE SAME DEPTH AS THE SALES OR
 SERVICE COUNTER TOP.
  
 5) COMPLIED.WIND DESIGN CRITERIA
  
 6A) 3RD REQUEST. SHEET AD201 HAS A CHANGE IN WINDOW
 STYLE, THE LAST SUBMITTAL THE FRONT ELEVAION INDICATED
 THE USE OF PGT SERIES PW 3020 PICTURE WINDOWS,
 SUBMITTED NOA 12-0516.05. THIS SUBMITTAL SHEET AD201
 THE FRONT ELEVATION NOW SHOWS STOREFRONT WINDOW SYSTEM.
 THE SUBMITTED NOA US ALUMINUM NOA # 14-0331.02 HAS NOT
 BEEN REVIEWED BY THE DESIGNER OF RECORD.
  
 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 6B)COMPLIED.
  
 7) NOT APPLICABLE NO NEW ROOF SYSTEM.
  
 8) PROVISO: A REVISION MAYBE NECESSARY TO SHOW
 ADDITIONAL DETAILS. SHEET AS201 SHOW DETAIL 2 OOF
 FRAMING FOR THE SIDEWALL & NEW ROOF. THIS DETAIL FAILS
 TO PROVIDE THE CONNECTION TO THE EXISTING ROOF FRAMING,
 DOES THE EXISTING LAST FRAMING MEMBER GET DOUBLED? DOES
 THIS FRAMING MEMBER REQUIRE ADDITIONAL STAPPING FOR THE
 ADDITIONAL UPLIFT OF A LARGER TRIBUTARY AREA AND BEING
 PART OF THE MWFRS?
  
 9) IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-04-20 Cont ID  
Sent By J WITMER Date 2015-04-20 Time 08:46 Rev Time 0.00
Received By jwitmer Date 2015-04-20 Time   Sent To  
Notes
2015-04-20 08:45:58BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15040016
 ADD: 701 N. ROSEMARY AVE.
 CONT: ADVANCED CONSTRUCTION
 TEL: (561)262-6037
 E-MAIL:
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 IMPORTANT NOTICE: EFFECTIVE MARCH 30, 2015
 ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED
 ELECTRONICALLY
 UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS
 SUBMISSION OPTIONS ARE AS FOLLOWS:
 1 UPLOAD VIA THE PROJECT DOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL
 SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED
 NAMING CONVENTION FOR EACH DOCUMENT
 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER
 DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE
 REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT
 TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS
 ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES
 AVAILABLE.
  
 2ND REVIEW
 DATE: MON. APRIL 20/2015
 ACTION: DENIED
  
 1) 2ND REQUEST. SHEET AD103 & AD201 NEEDS TO SHOW AN
 ACCESSIBLE ENTRANCE TO THE BUILDING FROM THE
 ACCESSIBILE PARKING SPACE AND ACCESS AISLE. ICE MACHINE
 BLOCKS THE SIDEWALK AND SEE THE REQUIRED WIDTH OF
 SIDEWALK AND TURNING FOR ENTRY AT DOOR. SHEET AD103
 SHOWS PLANTERS IN FRONT OF THE CONCENIENCE STORE WHERE
 AS SD201 SHOWS A ICE MACHINE BLOCKING THE ROUTE ON THE
 SIDEWALK TO THE STORE ENTRANCE DOOR. NEITHER SHEET
 AD103 OR AD201 INDICATE IF THE EXISTING CURB IS FLUSH
 AT THE ENTRY DOOR, THERE IS A STATEMENT THAT THE NEW
 PAVEMENT AT THE ADDITION IS TO BE FLUSH WITH THE
 EXISTING SIDEWALK BUT NO STATEMENT OF WHAT HAPPENS AT
 THE EXISTING FRONT ENTRY FOR CODE COMPLIANCE WITH
 ACCESSIBILITY.
  
 2010 FL ACCESSIBILITY CODE 206.2.1 SITE ARRIVAL POINTS.
 AT LEAST ONE ACCESSIBLE ROUTE SHALL BE PROVIDED WITHIN
 THE SITE FROM ACCESSIBLE PARKING SPACES AND ACCESSIBLE
 PASSENGER LOADING ZONES; PUBLIC STREETS AND SIDEWALKS;
 AND PUBLIC TRANSPORTATION STOPS TO THE ACCESSIBLE
 BUILDING OR FACILITY ENTRANCE THEY SERVE.
  
 SEE ACCESS. CODE FIGURE 404.2.4.1 (HOR I) DEPENDING ON
 IF THERE IS A DOOR CLOSER.
  
 2) SEMI-COMPLIED. SHEET AD103 WILL NEED TO SHOW THE W.
 P. B. CITY STANDARD OF DOUBLE STRIPING SEE W.P. B. MUNI
 CODE SECTION 94-485. THE PLANS SHOW THE DOUBLE
 STRIPPING AS REQUIRED BY THE CITY STANDARDS BUT THE
 PLANS STILL CO NOT SHOW THE REQUIRED DIMENSIONS UNDER
 THE MUNI-CODE AND ACCESSIBILITY CODE. 2010
 FBC-ACCESSIBILITY CODE 502.2 & 502.3.1.
  
 3) 2ND REQUEST. SHEET AD201 INDICATES WHERE THE NEW
 ADDITION IS TO THE EXISTING BUILDING TO FLUSH UO THE
 NEW PAVEMENT TO THE EXISTING SIDE WALK. THIS SHEET NOR
 AD103 SHOW THE PROPOSED GRADES NOR THE TRANSITION OF
 GRADE ELEVATION AT THE EXISTING SIDEWALK VERSES THE
 PAVEMENT. 2010 FL ACCESS. CODE 502.4. 502.4 FLOOR OR
 GROUND SURFACES.
 PARKING SPACES AND ACCESS AISLES SERVING THEM SHALL
 COMPLY WITH 302. ACCESS AISLES SHALL BE AT THE SAME
 LEVEL AS THE PARKING SPACES THEY SERVE. CHANGES IN
 LEVEL ARE NOT PERMITTED.
 EXCEPTION: SLOPES NOT STEEPER THAN 1:48 SHALL BE
 PERMITTED.
  
 4) COMPLIED> PLANS DO NOT INDICATE COMPLIANCE WITH 2010
 FL ACCESS. CODE 904.4 SALES AND SERVICE COUNTERS.
 SALES COUNTERS AND SERVICE COUNTERS SHALL COMPLY WITH
 904.4.1 OR 904.4.2. THE ACCESSIBLE PORTION OF THE
 COUNTER TOP SHALL EXTEND THE SAME DEPTH AS THE SALES OR
 SERVICE COUNTER TOP.
  
 5) 2ND REQUEST. THE PLANS INDICATE NEW WINDOWS AND
 DOORS, THERE IS NO WIND DESIGN CRITERIA:
 WIND DESIGN CRITERIA
 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 5.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 5.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 5.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 5.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 5.5) SEMI-COMPLIED. PRESSURES CAN NOT BE CALCULATED
 UNTIL THE ABOVE INFORMATION IS PROVIDED.
 COMPONENTS & CLADDING PRESSURES POSITIVE & NEGATIVE
 TABLE 1609.2(2) .
  
 6A) 2ND REQUEST . 2010 FBC 107.3.4.1 PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE
 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 6B)2ND REQUEST. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS.SECURITY GRILL. DOORS ARE NOT
 IDENTIFIED. CIRCLE WIDTH, LENGHT, GLAZING TYPE,
 FASTENERS AND ASSOCIATED PRESSURES. NOTE SHEET AD201
 THE EAST ELEVATION SHOWS A WOOD DOOR WITH STEEL DOOR
 FRAME, THE SUBMITTED REPORT FL 14940 JELD-WEN IS A 24
 GAUGE STEEL DOOR AND STEEL DOOR FRAME DISCREPANCY IN
 PRODUCTS, NOT REVIEWED BY THE DESIGNER OF RECORD.
 (B) WINDOWS. CIRCLE WIDTH, LENGHT, GLAZING TYPE,
 FASTENERS AND ASSOCIATED PRESSURES.
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS, CIRCLE WIDTH, LENGHT, GLAZING
 TYPE, FASTENERS AND ASSOCIATED PRESSURES.
 (D) ROOFING PRODUCTS AND ASSEMBLIES NO PRODUCT
 APPROVALS WERE SUBMITTED ON THE 2ND REVIEW. NOTE NO
 WORK IS BEING COMPLETED UNDER THIS PERMIT, THE ADDITION
 WILL ADD ROOF AREA WHICH WILL NEED TO BE SIZED THE THE
 EXISTING ROOF.
  
 6C) COMPLIED .SHEET AD201 INDICATES THE WINDOWS TO BE
 SLIDERS WHERE AS THE PRODUCT APPROVAL SUBMITTED WAS FOR
 ALUMINUM STOREFRONT SYSTEM.
  
 6D) 2ND REQUEST. SHEET AD201 ALSO INDICATES A NEW
 MOTORIZED SECURITY SHUTTER.
  
 7) 2ND REQUEST. SHEET AD201 SHOWS A ROOF CURB AND WHAT
 APPEARS TO BE INSULATED ROOF WITH PITCH TO A ROOF
 SCUPPER, NOTE THERE IS NO CALCULATION FOR RAIN/ ROOF
 AREA NOR STHE MINIMUM SIZE OF SCUPPER.
 7A) 2ND REQUEST. FBC-B P] 1503.4 ROOF DRAINAGE.
 UNLESS ROOFS ARE SLOPED TO DRAIN OVER ROOF EDGES,
 DESIGN AND INSTALLATION OF ROOF DRAINAGE SYSTEMS SHALL
 COMPLY WITH SECTION 1503 AND THE FLORIDA BUILDING CODE,
 PLUMBING, CHAPTER 11.
  
 7B) 2ND REQUEST. 1503.4.2 SCUPPERS. WHERE REQUIRED FOR
 ROOF DRAINAGE, A SCUPPER SHALL BE PLACED LEVEL WITH THE
 ROOF SURFACE IN A WALL OR PARAPET. THE SCUPPER SHALL BE
 LOCATED AS DETERMINED BY THE SLOPE AND THE CONTRIBUTING
 AREA OF THE ROOF. THE EXTERIOR FACING OR LINING OF A
 SCUPPER, IF METAL, SHALL BE THE SAME AS FLASHING
 MATERIAL REQUIRED BY SECTIONS 1503 THROUGH 1510 FOR THE
 PARTICULAR TYPE OF COVERING SPECIFIED FOR THE BUILDING.
 FOR OTHER TYPE MATERIALS, FOLLOW MANUFACTURER?S
 SPECIFICATIONS.
  
 7C) 2ND REQUEST. 1503.4.1 SECONDARY DRAINAGE REQUIRED.
 SECONDARY (EMERGENCY) ROOF DRAINS OR SCUPPERS SHALL BE
 PROVIDED WHERE THE ROOF PERIMETER CONSTRUCTION EXTENDS
 ABOVE THE ROOF IN SUCH A MANNER THAT WATER WILL BE
 ENTRAPPED IF THE PRIMARY DRAINS ALLOW BUILDUP FOR ANY
 REASON.
  
 7D) 2ND REQUEST. 1503.4.2.1 OVERFLOW SCUPPERS.
 WHEN OTHER MEANS OF DRAINAGE OF OVERFLOW WATER IS NOT
 PROVIDED, OVERFLOW SCUPPERS SHALL BE PLACED IN WALLS OR
 PARAPETS NOT LESS THAN 2 INCHES (51 MM) NOR MORE THAN 4
 INCHES (102 MM) ABOVE THE FINISHED ROOF COVERING AND
 SHALL BE LOCATED AS CLOSE AS PRACTICAL TO REQUIRED
 VERTICAL LEADERS OR DOWNSPOUTS OR WALL AND PARAPET
 SCUPPERS. AN OVERFLOW SCUPPER SHALL BE SIZED IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODE, PLUMBING.
  
 7E) 2ND REQUEST.1503.7 PROTECTION AGAINST DECAY AND
 TERMITES.
 CONDENSATE LINES AND ROOF DOWNSPOUTS SHALL DISCHARGE AT
 LEAST 1 FOOT (305 MM) AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EXTENSIONS, OR
 SPLASH BLOCKS. GUTTERS WITH DOWNSPOUTS ARE REQUIRED ON
 ALL BUILDINGS WITH EAVES OF LESS THAN 6 INCHES (152 MM)
 HORIZONTAL PROJECTION EXCEPT FOR GABLE END RAKES OR ON
 A ROOF ABOVE ANOTHER ROOF.
  
 8)SHEET AS201 SHOW DETAIL 2 OOF FRAMING FOR THE
 SIDEWALL & NEW ROOF. THIS DETAIL FAILS TO PROVIDE THE
 CONNECTION TO THE EXISTING ROOF FRAMING, DOES THE
 EXISTING LAST FRAMING MEMBER GET DOUBLED? DOES THIS
 FRAMING MEMBER REQUIRE ADDITIONAL STAPPING FOR THE
 ADDITIONAL UPLIFT OF A LARGER TRIBUTARY AREA AND BEING
 PART OF THE MWFRS?
  
 9) IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  
 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-04-06 Cont ID  
Sent By jwitmer Date 2015-04-06 Time 08:05 Rev Time  
Received By jwitmer Date 2015-04-06 Time 06:45 Sent To  
Notes
2015-04-06 08:05:09BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15040016
 ADD: 701 N. ROSEMARY AVE.
 CONT: ADVANCED CONSTRUCTION
 TEL: (561)262-6037
 E-MAIL:
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 IMPORTANT NOTICE: EFFECTIVE MARCH 30, 2015
 ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED
 ELECTRONICALLY
 UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS
 SUBMISSION OPTIONS ARE AS FOLLOWS:
 1 UPLOAD VIA THE PROJECT DOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL
 SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED
 NAMING CONVENTION FOR EACH DOCUMENT
 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER
 DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE
 REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT
 TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS
 ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES
 AVAILABLE.
  
 1ST REVIEW
 DATE: MON. APRIL 06/2015
 ACTION: DENIED
  
 1) SHEET AD103 NEEDS TO SHOW AN ACCESSIBLE ENTRANCE TO
 THE BUILDING FROM THE ACCESSIBILE PARKING SPACE AND
 ACCESS AISLE. ICE MACHINE BLOCKS THE SIDEWALK AND
 SEE THE REQUIRED WIDTH OF SIDEWALK AND TURNING FOR
 ENTRY AT DOOR.
  
 2010 FL ACCESSIBILITY CODE 206.2.1 SITE ARRIVAL POINTS.
 AT LEAST ONE ACCESSIBLE ROUTE SHALL BE PROVIDED WITHIN
 THE SITE FROM ACCESSIBLE PARKING SPACES AND ACCESSIBLE
 PASSENGER LOADING ZONES; PUBLIC STREETS AND SIDEWALKS;
 AND PUBLIC TRANSPORTATION STOPS TO THE ACCESSIBLE
 BUILDING OR FACILITY ENTRANCE THEY SERVE.
  
 SEE ACCESS. CODE FIGURE 404.2.4.1 (HOR I) DEPENDING ON
 IF THERE IS A DOOR CLOSER.
  
 2) SHEET AD103 WILL NEED TO SHOW THE W. P. B. CITY
 STANDARD OF DOUBLE STRIPING SEE W.P. B. MUNI CODE
 SECTION 94-485.
  
 3) SHEET AD201 INDICATES WHERE THE NEW ADDITION IS TO
 THE EXISTING BUILDING TO FLUSH UO THE NEW PAVEMENT TO
 THE EXISTING SIDE WALK. THIS SHEET NOR AD103 SHOW THE
 PROPOSED GRADES NOR THE TRANSITION OF GRADE ELEVATION
 AT THE EXISTING SIDEWALK VERSES THE PAVEMENT. 2010 FL
 ACCESS. CODE 502.4. 502.4 FLOOR OR GROUND SURFACES.
 PARKING SPACES AND ACCESS AISLES SERVING THEM SHALL
 COMPLY WITH 302. ACCESS AISLES SHALL BE AT THE SAME
 LEVEL AS THE PARKING SPACES THEY SERVE. CHANGES IN
 LEVEL ARE NOT PERMITTED.
 EXCEPTION: SLOPES NOT STEEPER THAN 1:48 SHALL BE
 PERMITTED.
  
 4) PLANS DO NOT INDICATE COMPLIANCE WITH 2010 FL
 ACCESS. CODE 904.4 SALES AND SERVICE COUNTERS.
 SALES COUNTERS AND SERVICE COUNTERS SHALL COMPLY WITH
 904.4.1 OR 904.4.2. THE ACCESSIBLE PORTION OF THE
 COUNTER TOP SHALL EXTEND THE SAME DEPTH AS THE SALES OR
 SERVICE COUNTER TOP.
  
 5) THE PLANS INDICATE NEW WINDOWS AND DOORS, THERE IS
 NO WIND DESIGN CRITERIA:
 WIND DESIGN CRITERIA
 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 5.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 5.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 5.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 5.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 5.5) COMPONENTS & CLADDING PRESSURES POSITIVE &
 NEGATIVE TABLE 1609.2(2) .
  
 6A) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 6B) FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS. DOORS ARE NOT IDENTIFIED.
 CIRCLE WIDTH, LENGHT, GLAZING TYPE, FASTENERS AND
 ASSOCIATED PRESSURES.
 (B) WINDOWS. CIRCLE WIDTH, LENGHT, GLAZING TYPE,
 FASTENERS AND ASSOCIATED PRESSURES.
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS, CIRCLE WIDTH, LENGHT, GLAZING
 TYPE, FASTENERS AND ASSOCIATED PRESSURES.
 (D) ROOFING PRODUCTS AND ASSEMBLIES NO PRODUCT
 APPROVALS WERE SUBMITTED.
  
 6C) SHEET AD201 INDICATES THE WINDOWS TO BE SLIDERS
 WHERE AS THE PRODUCT APPROVAL SUBMITTED WAS FOR
 ALUMINUM STOREFRONT SYSTEM.
  
 6D) SHEET AD201 ALSO INDICATES A NEW MOTORIZED SECURITY
 SHUTTER.
  
 7) SHEET AD201 SHOWS A ROOF CURB AND WHAT APPEARS TO BE
 INSULATED ROOF WITH PITCH TO A ROOF SCUPPER, NOTE THERE
 IS NO CALCULATION FOR RAIN/ ROOF AREA NOR STHE MINIMUM
 SIZE OF SCUPPER.
 7A) FBC-B P] 1503.4 ROOF DRAINAGE.
 UNLESS ROOFS ARE SLOPED TO DRAIN OVER ROOF EDGES,
 DESIGN AND INSTALLATION OF ROOF DRAINAGE SYSTEMS SHALL
 COMPLY WITH SECTION 1503 AND THE FLORIDA BUILDING CODE,
 PLUMBING, CHAPTER 11.
  
 7B) 1503.4.2 SCUPPERS. WHERE REQUIRED FOR ROOF
 DRAINAGE, A SCUPPER SHALL BE PLACED LEVEL WITH THE ROOF
 SURFACE IN A WALL OR PARAPET. THE SCUPPER SHALL BE
 LOCATED AS DETERMINED BY THE SLOPE AND THE CONTRIBUTING
 AREA OF THE ROOF. THE EXTERIOR FACING OR LINING OF A
 SCUPPER, IF METAL, SHALL BE THE SAME AS FLASHING
 MATERIAL REQUIRED BY SECTIONS 1503 THROUGH 1510 FOR THE
 PARTICULAR TYPE OF COVERING SPECIFIED FOR THE BUILDING.
 FOR OTHER TYPE MATERIALS, FOLLOW MANUFACTURER?S
 SPECIFICATIONS.
  
 7C) 1503.4.1 SECONDARY DRAINAGE REQUIRED.
 SECONDARY (EMERGENCY) ROOF DRAINS OR SCUPPERS SHALL BE
 PROVIDED WHERE THE ROOF PERIMETER CONSTRUCTION EXTENDS
 ABOVE THE ROOF IN SUCH A MANNER THAT WATER WILL BE
 ENTRAPPED IF THE PRIMARY DRAINS ALLOW BUILDUP FOR ANY
 REASON.
  
 7D) 1503.4.2.1 OVERFLOW SCUPPERS.
 WHEN OTHER MEANS OF DRAINAGE OF OVERFLOW WATER IS NOT
 PROVIDED, OVERFLOW SCUPPERS SHALL BE PLACED IN WALLS OR
 PARAPETS NOT LESS THAN 2 INCHES (51 MM) NOR MORE THAN 4
 INCHES (102 MM) ABOVE THE FINISHED ROOF COVERING AND
 SHALL BE LOCATED AS CLOSE AS PRACTICAL TO REQUIRED
 VERTICAL LEADERS OR DOWNSPOUTS OR WALL AND PARAPET
 SCUPPERS. AN OVERFLOW SCUPPER SHALL BE SIZED IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODE, PLUMBING.
  
 7E) 1503.7 PROTECTION AGAINST DECAY AND TERMITES.
 CONDENSATE LINES AND ROOF DOWNSPOUTS SHALL DISCHARGE AT
 LEAST 1 FOOT (305 MM) AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EXTENSIONS, OR
 SPLASH BLOCKS. GUTTERS WITH DOWNSPOUTS ARE REQUIRED ON
 ALL BUILDINGS WITH EAVES OF LESS THAN 6 INCHES (152 MM)
 HORIZONTAL PROJECTION EXCEPT FOR GABLE END RAKES OR ON
 A ROOF ABOVE ANOTHER ROOF.
  
 8)SHEET AS201 SHOW DETAIL 2 OOF FRAMING FOR THE
 SIDEWALL & NEW ROOF. THIS DETAIL FAILS TO PROVIDE THE
 CONNECTION TO THE EXISTING ROOF FRAMING, DOES THE
 EXISTING LAST FRAMING MEMBER GET DOUBLED? DOES THIS
 FRAMING MEMBER REQUIRE ADDITIONAL STAPPING FOR THE
 ADDITIONAL UPLIFT OF A LARGER TRIBUTARY AREA AND BEING
 PART OF THE MWFRS?
  
 9) IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  
 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-04-01 Cont ID  
Sent By dhayes Date 2015-04-01 Time 13:47 Rev Time 0.00
Received By dhayes Date 2015-04-01 Time 13:39 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2015-06-25 Cont ID  
Sent By pleduc Date 2015-06-25 Time   Rev Time 0.00
Received By pleduc Date 2015-06-25 Time 11:01 Sent To  
Notes
2015-06-25 11:12:01THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 IT APPEARS THAT ONLY ONE COMPLETE SET OF PLANS WERE
 PROVIDED; IT WAS STAMPED.
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 1) PROVIDE EXIT SIGNS AT EACH DOOR.
  
 2) PROVIDE AN INTERIOR EMERGENCY LIGHT.
  
 3) PROVIDE KEY LOCKS FOR THE EXIT DOORS THAT INDICATED
 OPEN/LOCKED. INSTALL SIGN THAT STATES DOORS SHALL BE
 UNLOCKED DURING BUSINESS HOURS. THUMB TURN LOCKS ARE
 NOT APPROVED.
  
 4) PROVIDE 1 5LLB ABC CERTIFIED AND TAGGED FIRE
 EXTINGUISHER.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-04-29 Cont ID  
Sent By PLEDUC Date 2015-04-29 Time   Rev Time 0.00
Received By pleduc Date 2015-04-27 Time 16:50 Sent To  
Notes
2015-04-29 11:01:04THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 1) PROVIDE EXIT SIGNS AT EACH DOOR.
  
 2) PROVIDE AN INTERIOR EMERGENCY LIGHT.
  
 3) PROVIDE KEY LOCKS FOR THE EXIT DOORS THAT INDICATED
 OPEN/LOCKED. INSTALL SIGN THAT STATES DOORS SHALL BE
 UNLOCKED DURING BUSINESS HOURS. THUMB TURN LOCKS ARE
 NOT APPROVED.
  
 4) PROVIDE 1 5LLB ABC CERTIFIED AND TAGGED FIRE
 EXTINGUISHER.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-04-13 Cont ID  
Sent By pleduc Date 2015-04-13 Time   Rev Time 0.00
Received By pleduc Date 2015-04-13 Time 13:15 Sent To  
Notes
2015-04-13 13:25:28THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THE PROPOSED OCCUPANCY IS NOT INDICATED.
  
 PROVIDE AN EQUIPMENT AND SHELVING ( IF APPROPRIATE)
 PLAN, AND/OR PROPOSED FLOOR LAYOUT PLAN SHOWING THE
 INTERIOR OF THE OCCUPANCY.
  
 COMPLETE LIFE SAFETY PLANS FOR THE OCCUPANCY SHALL BE
 PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL
 DISTANCES, COMMON PATHS OF TRAVEL, DEAD-END CORRIDORS,
 EXIT SIGNS, EMERGENCY LIGHTING, EXITS LEADING TO A
 PUBLIC WAY, FIRE EXTINGUISHER LOCATIONS, AND ALL FIRE
 SAFETY FEATURES AND EQUIPMENT.
  
 NO EXIT DOOR SHALL BE LOCKED FROM THE EGRESS SIDE. ANY
 AND ALL LOCKING MECHANISMS SHALL BE COMPLAINT WITH
 CHAPTER 7 OF THE FLORIDA FIRE PREVENTION CODE AND
 PRE-APPROVED (PRIOR TO INSTALLATION) BY THE BUREAU OF
 FIRE PREVENTION.
  
 PER SECTION 7.2.1.5.9, THE LOCK/LATCH RELEASING
 MECHANISM ON ALL DOORS SHALL OPEN THE DOOR WITH NOT
 MORE THAN ONE RELEASING OPERATION. THE RELEASING
 MECHANISM SHALL HAVE AN OBVIOUS METHOD OF OPERATION
 THAT IS READILY OPERATED UNDER ALL LIGHTING CONDITIONS.
 THE RELEASING DEVICE SHOULD BE CAPABLE OF BEING
 OPERATED WITH ONE HAND AND SHOULD NOT REQUIRE TIGHT
 GRASPING, TIGHT PINCHING OR TWISTING OF THE WRIST TO
 OPERATE.
  
 A THUMB TURN LOCK IS NOT PERMITTED ON THE MAIN ENTRY
 DOOR(S). IN LIEU OF PANIC HARDWARE, THE MAIN ENTRY IS
 PERMITTED TO BE EQUIPPED WITH A KEYED LOCK WITH
 LOCK/UNLOCK INDICATOR WINDOW AND SIGNAGE STATING THE
 DOOR IS TO REMAIN UNLOCKED DURING BUSINESS HOURS. NO
 OTHER LOCKING OR LATCHING MECHANISMS ARE PERMITTED.
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2015-07-29 Cont ID  
Sent By tklarge Date 2015-07-29 Time 09:59 Rev Time 0.00
Received By tklarge Date 2015-07-27 Time 14:09 Sent To  
Notes
2015-07-28 14:10:53TLARGE DESK

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By cpuell Date 2015-07-20 Time 16:12 Sent To  
Notes
2015-07-20 16:12:49JWITMER DESK

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2015-07-14 Cont ID  
Sent By jwitmer Date 2015-07-14 Time 09:26 Rev Time 0.00
Received By tklarge Date 2015-07-09 Time 11:10 Sent To  
Notes
2015-07-10 11:12:37ON JWITMER DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-07-09 Cont ID  
Sent By tklarge Date 2015-07-09 Time 13:08 Rev Time 0.00
Received By tklarge Date 2015-06-19 Time 17:44 Sent To  
Notes
2015-06-19 17:52:42ROUTED TO C30

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-05-14 Cont ID  
Sent By tklarge Date 2015-05-14 Time 12:08 Rev Time 0.00
Received By tklarge Date 2015-04-17 Time   Sent To  
Notes
2015-04-18 07:57:54GAVE TO S GRAHAM FOR LANDSCAPE REVIEW.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By dhayes Date 2015-04-17 Time   Rev Time 0.00
Received By dhayes Date 2015-04-01 Time 13:39 Sent To E
Notes
2015-04-01 13:38:27B13

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 6 Status P Date 2015-07-30 Cont ID  
Sent By skennedy Date 2015-07-30 Time 09:01 Rev Time 0.00
Received By skennedy Date 2015-07-30 Time 09:01 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 5 Status F Date 2015-07-27 Cont ID  
Sent By jwitmer Date 2015-07-27 Time 12:07 Rev Time 0.00
Received By jwitmer Date 2015-07-27 Time   Sent To  
Notes
2015-07-27 12:07:16IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status F Date 2015-07-13 Cont ID  
Sent By jwitmer Date 2015-07-13 Time 11:56 Rev Time 0.00
Received By jwitmer Date 2015-07-13 Time   Sent To  
Notes
2015-07-13 11:56:51IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2015-07-01 Cont ID  
Sent By jwitmer Date 2015-07-01 Time 09:09 Rev Time 0.00
Received By jwitmer Date 2015-07-01 Time 09:09 Sent To  
Notes
2015-07-01 09:09:31IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2015-04-20 Cont ID  
Sent By jwitmer Date 2015-04-20 Time 08:46 Rev Time 0.00
Received By jwitmer Date 2015-04-20 Time 08:46 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-04-04 Cont ID  
Sent By skennedy Date 2015-04-04 Time 12:50 Rev Time 0.00
Received By skennedy Date 2015-04-04 Time 12:50 Sent To  
Notes
2015-04-04 12:56:03IS REVIEW
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE PLAN AND
 TAKE TO THAT OFFICE FOR REVIEW. PLEASE RETURNED STAMPED
 WITH A COPY OF RECEIPT AS APPLICABLE.
  
 STEVEN KENNEDY
 561 805 6710

Review Stop L LANDSCAPING
Rev No 2 Status P Date 2015-05-14 Cont ID  
Sent By RCARANCI Date 2015-05-14 Time 10:17 Rev Time 0.00
Received By rcaranci Date 2015-05-14 Time 10:16 Sent To  
Notes
2015-05-14 10:19:22NEED SEPARATE PERMIT FOR LANDSCAPING, LANDSCAPE PLAN IS
 IN PERMIT PLANS, JUST NEED PERMIT FORM FILLED OUT AND
 FEES PAID.

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2015-04-09 Cont ID  
Sent By rcaranci Date 2015-04-09 Time 16:19 Rev Time 0.00
Received By rcaranci Date 2015-04-09 Time 16:19 Sent To  
Notes
2015-04-10 16:01:23PROVIDE LANDSCAPE AREAS AT FRONT OF BUILDING,
 COORDINATE WITH ADA ACCESS REQUIREMENTS. RESUBMIT
 CORRECTED PLANS.
 RAY CARANC,I LANDSCAPE PLANNER 561-822-1462
 [email protected]
2015-04-09 16:22:32ADD LANDSCAPING AROUND BUILDING IN AREAS WHERE
 POSSIBLE. TRIED TO CALL CONTRACTOR, NO VOICEMAIL. EMAIL
 IS NOT LEGIBLE.
 RAY CARANCI, LANDSCAPE PLANNER 561-822-1462,
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2015-04-25 Cont ID  
Sent By SKENNEDY Date 2015-04-25 Time 10:32 Rev Time 0.00
Received By hmoser Date 2015-04-25 Time 10:23 Sent To  
Notes
2015-04-25 10:32:32HAVE AIR CONDITIONING CONTRACTOR PROVIDE SEPARATE
 APPLICATION, PLAN AND PERMIT FOR AIR CONDITIONING
 AND REFRIGERATION.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-04-04 Cont ID  
Sent By skennedy Date 2015-04-04 Time 12:51 Rev Time 0.00
Received By skennedy Date 2015-04-04 Time 12:52 Sent To  
Notes
2015-04-04 12:54:421ST REVIEW: FBC 2010
  
 NO MECHANICAL PLAN IS SHOWN. NO REFRIGERATION EQUIPMENT
 IS SHOWN. NO ENERGY SUBMITTAL IS PROVIDED.
  
 MEET MINIMUM PLAN REVIEW CRITERIA OF FBC 107 AND
 PROVIDE THE ABOVE.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop P PLUMBING
Rev No 5 Status P Date 2015-07-29 Cont ID  
Sent By tklarge Date 2015-07-29 Time 09:57 Rev Time 0.00
Received By tklarge Date 2015-07-29 Time 09:57 Sent To  
Notes
2015-07-29 09:58:24PROVISO
 WATER RISER DIAGRAM SHALL BE SUBMITTED FOR REVIEW AND
 APPROVAL PRIOR TO ANY PLUMBING INSPECTION.

Review Stop P PLUMBING
Rev No 4 Status F Date 2015-07-14 Cont ID  
Sent By tklarge Date 2015-07-14 Time 09:25 Rev Time 0.00
Received By tklarge Date 2015-07-14 Time 06:57 Sent To  
Notes
2015-07-14 09:26:031) SUBMIT A WATER AND SANITARY RISER DIAGRAM FOR THE
 RELOCATION OF THE PLUMBING FIXTURES IN BOTH TOILET
 ROOMS. WPB AMEND. TO 2010 FBC SEC. 107.3.5.1.3. 2ND
 REQUEST.
 2) THE SANITARY RISER ON SHT.AP 201 SHOWS A BATHTUB.
 THE RISER IS NOT FOR THIS PROJECT.3RD REQUEST.
 I SUGGEST THE DESIGN PROFESSIONAL CALL ME TO DISCUSS MY
 COMMENTS.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2015-07-09 Cont ID  
Sent By tklarge Date 2015-07-09 Time 13:08 Rev Time 0.00
Received By tklarge Date 2015-07-09 Time 12:58 Sent To  
Notes
2015-07-09 13:07:541) SUBMIT A WATER AND SANITARY RISER DIAGRAM FOR THE
 RELOCATION OF THE PLUMBING FIXTURES IN BOTH TOILET
 ROOMS. WPB AMEND. TO 2010 FBC SEC. 107.3.5.1.3. 2ND
 REQUEST.
 2) THE SANITARY RISER ON SHT.AP 201 SHOWS A BATHTUB.
 THE RISER IS NOT FOR THIS PROJECT. 2ND REQUEST.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2015-05-09 Cont ID  
Sent By SKENNEDY Date 2015-05-09 Time 07:36 Rev Time 0.00
Received By tklarge Date 2015-05-09 Time 07:16 Sent To  
Notes
2015-05-09 07:36:281) THE INSIDE MINIMUM WIDTH OF THE ACCESSIBLE TOILET
 ROOM SHALL BE 85 INCHES IF BUILT PERFECT. 86 INCHES
 ALLOWS FOR TOLERANCES. FAC SECS.604.3.1, 606.2 & 305.
 2) SUBMIT A WATER AND SANITARY RISER DIAGRAM FOR THE
 RELOCATION OF THE PLUMBING FIXTURES IN BOTH TOILET
 ROOMS. WPB AMEND. TO 2010 FBC SEC. 107.3.5.1.3.
 3) THE SANITARY RISER ON SHT.AP 201 SHOWS A BATHTUB.
 THE RISER IS NOT FOR THIS PROJECT.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-04-04 Cont ID  
Sent By skennedy Date 2015-04-04 Time 12:50 Rev Time 0.00
Received By skennedy Date 2015-04-04 Time 12:50 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2015-05-08 Cont ID  
Sent By SGRAHAM Date 2015-05-08 Time 11:56 Rev Time 0.00
Received By sgraham Date 2015-05-08 Time 11:56 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2015-04-16 Cont ID  
Sent By sgraham Date 2015-04-16 Time 12:24 Rev Time 0.00
Received By sgraham Date 2015-04-16 Time 12:24 Sent To  
Notes
***NONE***