Plan Review Details - Permit 15031312
Plan Review Stops For Permit 15031312
Review Stop AIPP ART IN PUBLIC PLACES
Rev No 1 Status P Date 2017-11-16 Cont ID  
Sent By shill Date 2017-11-16 Time 18:35 Rev Time 0.00
Received By shill Date 2017-11-16 Time 18:35 Sent To  
Notes
2017-11-16 18:35:58OK PER SYBILLE C WELTER
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2016-02-12 Cont ID  
Sent By shill Date 2016-02-12 Time 08:43 Rev Time 0.00
Received By shill Date 2016-02-11 Time 09:49 Sent To  
Notes
2016-02-17 18:24:512010 FLORIDA BUILDING CODE W/ 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION, 2010 EDITION 2012 FBC SUPPLEMENTS
 ADOPTED APRIL 25/2013.
  
 ***PROVISOS***
 ***ISSUED AT CONTRACTOR'S RISK***
  
 1. DELEGATED ENGINEERING: HORIZONTAL TRELLIS FOUND ON
 THE SOUTH & WEST SIDES OF THE BUILDING (SEE SECTION 6,
 8 & 9 PAGE A7.5.4). PLEASE SHOW WIND DESIGN AND
 ANCHORING DETAILS. FBC-B 1609.6.4.4.1 COMPONENTS &
 CLADDING. FL 61G-15-30.006 (3) THE DELEGATED ENGINEER
 SHALL FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO
 THE ENGINEER OF RECORD FOR REVIEW.
  
 2. THE LETTER FROM JOE CUSCHIERI P. E. ACOUSTICS AND
 VIBRATION CONSULTANT HAS SUBMITTED A RATIONAL ANALYSIS
 AS TO HOW THEY ARE ACHIEVING THE IIC AND STC RATINGS.
 ALL FLOORS (FLOOR SLABS ARE 8 INCH POST TENSION SLABS)
 THE 3RD -16TH STORY. PLEASE PROVIDE COMPLIANCE WITH
 BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION
  
 DEFERRED SUBMITTALS. 107.3.4.2. SUBMIT STC, IIC, AND
 FLAME SPREAD TEST REPORTS (REVIEWED BY DOR) PRIOR TO
 INSTALLATION OF FLOORING UNDERLAYMENT.
 (A) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
 (B) FBC-B 2010 1207.2 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
 (C) FLAME SPREAD- FBC-B 2010 603.1.2 EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200
 (TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723).
  
 3. PROVISO: NOTE THERE IS NO KNOWING WHICH WAY A R2
 OCCUPANCY CAN TURN INTO EITHER AN APARTMENT BUILDINGS
 ARE AN R-2 AS WELL AS CONDOMINIUMS. IT ISN?T UNTIL C.O.
 THAT THE DOCUMENTS GO TO THE STATE FOR THE DECLARATION
 OF CONDOMINIUM. THIS NEXT CODE ISSUE WILL BE A PROVISO,
 THE PLANS BEING REVIEWED AS THIS IS TO BE A CONDOMINIUM
 AND UNDER FAIR HOUSING.
 PROVISO: NOTE THIS POOL DECK AND POOL ARE COVERED UNDER
 THE FAIR HOUSING ACT, TO DATE THE GUIDELINES ONLY
 REQUIRES ACCESS MUST BE PROVIDED TO THE POOL DECK AREA,
 NOT AN ACCESSIBLE ROUTE (RAMP OR LIFT) DOWN INTO THE
 WATER INTO THE POOL. ON THE OTHER HAND IF THE
 ASSOCIATION ELECTS TO ALLOW THE COMMUNITY ROOM, POOL,
 AND OR POOL DECK TO BE RENTED OUT FOR PARTIES THAT THE
 PUBLIC COULD USE, THEN THIS AREA WOULD BE REQUIRED TO
 MEET FLORIDA ACCESSIBILITY SECTION 1009 OF THE
 ACCESSIBILITY CODE POOL LIFTS.
  
 4. THE PLANS INDICATE THE USE OF PRE-ENGINEERED A/C
 STANDS. WHEN FIGURING THE REQUIRED CLEARANCES IN HEIGHT
 REQUIRED BY TABLE FBC-B 1509.7, THE CLEARANCE IS FROM
 THE FINISHED ROOF HEIGHT, ABOVE THE LIGHTWEIGHT
 CONCRETE ROOF.
  
 5. PRODUCT APPROVALS: DEFERRED SUBMITTAL. ARCHITECT
 WILL REVIEW/ APPROVE/ STAMP EACH PRODUCT APPROVAL W/
 SHOP DRAWING STAMP BEFORE SUBMISSION TO CITY BUILDING
 DEPARTMENT.
  
 6. A7.5.3, PROVISO: NOTE: THE POOL TRELLIS STRUCTURE
 (PERGOLA) THIS DETAIL INDICATES IT IS GOING TO BE
 DESIGNED BY A SPECIALTY ENGINEER. BEFORE SUBMITTAL TO
 THE BUILDING DEPARTMENT, THE PLANS WILL NEED TO BE
 REVIEWED BY THE ENGINEER OF RECORD. FL 61G-15-30.006
 (3) THE DELEGATED ENGINEER SHALL FORWARD THE DELEGATED
 ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR
 REVIEW.
  
 7. PAGE 136 A7.5.4. PROVISO: DETAIL # 5 RIGID ALUMINUM
 CANOPY WITH FABRIC WRAPPED WILL REQUIRE WIND DESIGN
 CRITERIA SEE OPTIONS FOUND UNDER FBC-B 3105.4 . ALSO:
 FL 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL
 FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO THE
 ENGINEER OF RECORD FOR REVIEW.
  
 8. FBC-B 403.4.6 SMOKE REMOVAL. SMOKE CONTROL SHALL BE
 PROVIDED IN ACCORDANCE WITH SECTION 909.
  
 9. PROVISO: FBC-B 403.5.3.1 STAIRWAY COMMUNICATION
 SYSTEM. A TELEPHONE OR OTHER TWO-WAY COMMUNICATIONS
 SYSTEM CONNECTED TO AN APPROVED CONSTANTLY ATTENDED
 STATION SHALL BE PROVIDED AT NOT LESS THAN EVERY FIFTH
 FLOOR IN EACH STAIRWAY WHERE THE DOORS TO THE STAIRWAY
 ARE LOCKED.
  
 10. FBC-B 403.5.4 SMOKEPROOF EXIT ENCLOSURES. EVERY
 REQUIRED EXIT STAIRWAY SERVING FLOORS MORE THAN 75 FEET
 (22 860 MM) ABOVE THE LOWEST LEVEL OF FIRE DEPARTMENT
 VEHICLE ACCESS SHALL COMPLY WITH SECTIONS 909.20 AND
 1022.9.
  
 11. THE POOL AND SPA PLANS HAVE NOT BEEN REVIEWED. A
 SEPARATE PERMIT WITH SEPARATE APPLICATIONS, PLANS, FEES
 AND REVIEWS REQUIRED.
  
 12. SEE FIRE DEPARTMENT PROVISO/REDLINES ON SHEETS
 LS7.0 AND LS8.0.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-12-12 Cont ID  
Sent By jwitmer Date 2015-12-12 Time 09:30 Rev Time 0.00
Received By jwitmer Date 2015-12-12 Time 06:33 Sent To  
Notes
2015-12-12 09:31:31BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15031312
 ADD: 333 FERN ST.
 CONT: KAST CONSTRUCTION
 CONTACT :
 TEL: (561)689-2910
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 3RD REVIEW
 DATE: SEPT. DEC.12 /2015
 ACTION: BUILDING PROVISO
  
 1) PROVISO: ; THE CITY OF WEST PALM BEACH ART IN PUBLIC
 PLACES ORDINANCE.
 2-6 COMPLIED.
 7A-7I) COMPLIED.
  
 7J) PROVISO/ DELEGATE ENGINEER. ) HORIZONTAL TRELLIS
 FOUND ON THE SOUTH & WEST SIDES OF THE BUILDING SEE
 SECTION 6,8 & 9 PAGE A7.5.4. PLEASE SHOW WIND DESIGN
 AND ANCHORING DETAILS. FBC-B 1609.6.4.4.1 COMPONENTS &
 CLADDING. FL 61G-15-30.006 (3) THE DELEGATED ENGINEER
 SHALL FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO
 THE ENGINEER OF RECORD FOR REVIEW.
  
 7K-7P) COMPLIED.
  
 8-10) COMPLIED.
  
 11A-B) COMPLIED
  
 11C), COMPLIED/ PROVISO. THE LETTER FROM JOE CUSCHIERI
 P. E. ACOUSTICS AND VIBRATION CONSULTANT HAS SUBMITTED
 A RATIONAL ANALYSIS AS TO HOW THEY ARE ACHIEVING THE
 IIC AND STC RATINGS.
 ALL FLOORS (FLOOR SLABS ARE 8 INCH POST TENSION SLABS)
 , THE 3RD -16TH STORY. PLEASE PROVIDE COMPLIANCE WITH
 BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION
  
 PROVISO: DEFERRED SUBMITTALS. 107.3.4.2.
 11C)(1A) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 11C)(1B) FBC-B 2010 1207.2 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 11C)(1C) FLAME SPREAD- FBC-B 2010 603.1.2 EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 11D) COMPLIED.
  
 12A-D) COMPLIED.
  
 12E) PROVISO: NOTE THERE IS NO KNOWING WHICH WAY A R2
 OCCUPANCY CAN TURN INTO EITHER AN APARTMENT BUILDINGS
 ARE AN R-2 AS WELL AS CONDOMINIUMS. IT ISN?T UNTIL C.O.
 THAT THE DOCUMENTS GO TO THE STATE FOR THE DECLARATION
 OF CONDOMINIUM. THIS NEXT CODE ISSUE WILL BE A PROVISO,
 THE PLANS BEING REVIEWED AS THIS IS TO BE A CONDOMINIUM
 AND UNDER FAIR HOUSING.
 PROVISO: NOTE THIS POOL DECK AND POOL ARE COVERED UNDER
 THE FAIR HOUSING ACT, TO DATE THE GUIDELINES ONLY
 REQUIRES ACCESS MUST BE PROVIDED TO THE POOL DECK AREA,
 NOT AN ACCESSIBLE ROUTE (RAMP OR LIFT) DOWN INTO THE
 WATER INTO THE POOL. ON THE OTHER HAND IF THE
 ASSOCIATION ELECTS TO ALLOW THE COMMUNITY ROOM, POOL,
 AND OR POOL DECK TO BE RENTED OUT FOR PARTIES THAT THE
 PUBLIC COULD USE, THEN THIS AREA WOULD BE REQUIRED TO
 MEET FLORIDA ACCESSIBILITY SECTION 1009 OF THE
 ACCESSIBILITY CODE POOL LIFTS.
  
 12F-G) COMPLIED.
  
 .
 13) COMPLIED.
  
 14A-D) COMPLIED.
  
 14E) PROVISO: THE PLANS INDICATE THE USE OF
 PRE-ENGINEERED A/C STANDS. WHEN FIGURING THE REQUIRED
 CLEARANCES IN HEIGHT REQUIRED BY TABLE FBC-B 1509.7,
 THE CLEARANCE IS FROM THE FINISHED ROOF HEIGHT, ABOVE
 THE LIGHTWEIGHT CONCRETE ROOF.
  
 15) COMPLIED,
  
 16) PROVISO:) PRODUCT APPROVALS: DEFERRED SUBMITTAL.
 ARCHITECT WILL REVIEW/ APPROVE/ STAMP EACH PRODUCT
 APPROVAL W/ SHOP DRAWING STAMP BEFORE SUBMISSION TO
 CITY BUILDING DEPARTMENT..
  
 17-18) COMPLIED.
  
 19)A7.5.3
 19A) PROVISO: NOTE: THE POOL TRELLIS STRUCTURE
 (PERGOLA) THIS DETAIL INDICATES IT IS GOING TO BE
 DESIGNED BY A SPECIALTY ENGINEER. BEFORE SUBMITTAL TO
 THE BUILDING DEPARTMENT, THE PLANS WILL NEED TO BE
 REVIEWED BY THE ENGINEER OF RECORD. FL 61G-15-30.006
 (3) THE DELEGATED ENGINEER SHALL FORWARD THE DELEGATED
 ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR
 REVIEW.
  
 19B) COMPLIED.
  
 20) PAGE 136 A7.5.4. 20A) PROVISO: DETAIL # 5 RIGID
 ALUMINUM CANOPY WITH FABRIC WRAPPED WILL REQUIRE WIND
 DESIGN CRITERIA SEE OPTIONS FOUND UNDER FBC-B 3105.4 .
 ALSO: FL 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL
 FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO THE
 ENGINEER OF RECORD FOR REVIEW.
  
 21-23) COMPLIED.
  
 24 A-C) COMPLIED.
  
 24D) COMPLIED. FBC-B 403.4.6 SMOKE REMOVAL. SMOKE
 CONTROL SHALL BE PROVIDED IN ACCORDANCE WITH SECTION
 909. SEE MECHANICAL REVIEWERS COMMENTS.
  
 24E-G) COMPLIED.
  
 24H) PROVISO: FBC-B 403.5.3.1 STAIRWAY COMMUNICATION
 SYSTEM. A TELEPHONE OR OTHER TWO-WAY COMMUNICATIONS
 SYSTEM CONNECTED TO AN APPROVED CONSTANTLY ATTENDED
 STATION SHALL BE PROVIDED AT NOT LESS THAN EVERY FIFTH
 FLOOR IN EACH STAIRWAY WHERE THE DOORS TO THE STAIRWAY
 ARE LOCKED.
  
 24I) COMPLIED. FBC-B 403.5.4 SMOKEPROOF EXIT
 ENCLOSURES. EVERY REQUIRED EXIT STAIRWAY SERVING FLOORS
 MORE THAN 75 FEET (22 860 MM) ABOVE THE LOWEST LEVEL OF
 FIRE DEPARTMENT VEHICLE ACCESS SHALL COMPLY WITH
 SECTIONS 909.20 AND 1022.9. SEE MECHANICAL REVIEWER
 COMMENT 9A.
  
 24J) COMPLIED
  
 24K) COMPLIED.
  
 25) COMPLIED. IMPACT FEES PAID.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-09-28 Cont ID  
Sent By jwitmer Date 2015-09-28 Time 15:40 Rev Time 0.00
Received By jwitmer Date 2015-09-27 Time 09:02 Sent To  
Notes
2015-09-28 15:40:26BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15031312
 ADD: 333 FERN ST.
 CONT: KAST CONSTRUCTION
 CONTACT :
 TEL: (561)689-2910
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2ND REVIEW
 DATE: MON. SEPT. 28 /2015
 ACTION: DENIED
  
 1) PROVISO: ; THE CITY OF WEST PALM BEACH ART IN PUBLIC
 PLACES ORDINANCE.
 2-6 COMPLIED.
 7A-7I) COMPLIED.
 7J) PROVISO/ DELEGATE ENGINEER. ) HORIZONTAL TRELLIS
 FOUND ON THE SOUTH & WEST SIDES OF THE BUILDING SEE
 SECTION 6,8 & 9 PAGE A7.5.4. PLEASE SHOW WIND DESIGN
 AND ANCHORING DETAILS. FBC-B 1609.6.4.4.1 COMPONENTS &
 CLADDING. FL 61G-15-30.006 (3) THE DELEGATED ENGINEER
 SHALL FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO
 THE ENGINEER OF RECORD FOR REVIEW.
 7K-7M) COMPLIED.
 7N) 2ND REQUEST. RESPONSE INDICATES NOTE # 37 SHEET
 024-LS-1.0. NO SUCH NOTE. NOR ON SHEET 023-LS-01.
 PLEASE PROVIDE COMPLIANCE WITH THE 2010 FBC-B: [F]
 914.2 EQUIPMENT ROOM IDENTIFICATION. FIRE PROTECTION
 EQUIPMENT SHALL BE IDENTIFIED IN AN APPROVED MANNER.
 ROOMS CONTAINING CONTROLS FOR AIR-CONDITIONING SYSTEMS,
 SPRINKLER RISERS AND VALVES OR OTHER FIRE DETECTION,
 SUPPRESSION OR CONTROL ELEMENTS SHALL BE IDENTIFIED FOR
 THE USE OF THE FIRE DEPARTMENT. APPROVED SIGNS REQUIRED
 TO IDENTIFY FIRE PROTECTION EQUIPMENT AND EQUIPMENT
 LOCATION SHALL BE CONSTRUCTED OF DURABLE MATERIALS,
 PERMANENTLY INSTALLED AND READILY VISIBLE
 70-7P) COMPLIED.
 8A-B) COMPLIED.
 9A) DISCREPANCY IN PLANS, SEMI-COMPLIED. THE RESPONSE
 INDICATED THE DIMENSIONS WERE ADDED TO SHEETS
 077-A6.1.1 AND 078-A6.1.2 BUT THEY WERE NEVER CHANGED
 ON SHEETS 038-A2.3.1 OR 039- A2.3.2.
 DOORS 307.02 & 307.03 BOTH DOORS ARE CONSIDERED COMMON
 AREA DOORS SINCE THEY ARE NOT ENTRY DOORS TO THE UNIT.
 THE 2 DOORS DO NOT HAVE THE 18 INCHES REQUIRED ON THE
 LATCH SIDE OF THE DOOR, PER FAIR HOUSING REQUIREMENT 3.
 USABLE DOORS. GUIDELINE SECTION 100.205(C)(2) WOULD
 APPLY TO DOORS THAT ARE A PART OF AN ACCESSIBLE ROUTE
 IN THE PUBLIC AND COMMON USE AREAS OF MULTIFAMILY
 DWELLINGS AND TO DOORS INTO AND WITHIN INDIVIDUAL
 DWELLING UNITS.
 (1) ON ACCESSIBLE ROUTES IN PUBLIC AND COMMON USE AREAS
 AND FOR PRIMARY ENTRY DOORS TO COVERED UNITS, DOORS
 THAT COMPLY WITH ANSI 4.13 WOULD MEET THIS REQUIREMENT.
 9B) COMPLIED.
 10A-B) COMPLIED.
 10C) NEW COMMENT. PLEASE SEE MARK UP ON SHEET
 039-A2-3-2. THE COMMON CORRIDOR HAS PINCH POINTS IN THE
 CORRIDOR NEXT TO THE COLUMN LINE WHERE 36 INCH MINIMUM
 IS REQUIRED FOR THE CORRIDOR WIDTH BOTH BY FAIR HOUSING
 AND THE 2010 FBC-B 1018.2 EXC. # 2.
 11A) DISCREPANCY IN PLANS, SEMI-COMPLIED. THE RESPONSE
 INDICATED THE DIMENSIONS WERE ADDED TO SHEETS
 077-A6.1.1 AND 078-A6.1.2 BUT THEY WERE NEVER CHANGED
 ON SHEETS 045-A2.5.2.
 DOORS 307.02 & 307.03 BOTH DOORS ARE CONSIDERED COMMON
 AREA DOORS SINCE THEY ARE NOT ENTRY DOORS TO THE UNIT.
 THE 2 DOORS DO NOT HAVE THE 18 INCHES REQUIRED ON THE
 LATCH SIDE OF THE DOOR, PER FAIR HOUSING REQUIREMENT 3.
 USABLE DOORS. GUIDELINE SECTION 100.205(C)(2) WOULD
 APPLY TO DOORS THAT ARE A PART OF AN ACCESSIBLE ROUTE
 IN THE PUBLIC AND COMMON USE AREAS OF MULTIFAMILY
 DWELLINGS AND TO DOORS INTO AND WITHIN INDIVIDUAL
 DWELLING UNITS.
 11B) COMPLIED.
 11C), 11C)(1A), 11C(1B) 11C)(1C) THE LETTER FROM JOE
 CUSCHIERI P. E. ACOUSTICS AND VIBRATION CONSULTANT WILL
 NEED TO PROVIDE RATIONAL ANYLSIS AS TO HOW THEY ARE
 ACHIEVING THE IIC AND STC RATINGS STATED WITHIN THE
 LETTER. WE SEE MANY PRODUCTS THAT WERE TESTED IN
 LAVATORIES ON A 6 INCH CONCRETE SLAB AND BARELY GET A
 IIC RATING OF 51 WITH SOUND INSULATION. AT THE VARY END
 OF THE LETTER THE STATEMENT FOR HARD FINISHES SUCH AS
 WOOD OR MARBLE OR TILE MITIGATION FOR STRUCTURE BORNE
 SOUND SUCH AS THE USE OF KINETIC SR FLOOR BOARD OR
 EQUIVALENT SHOULD BE CONSIDERED TO MEET THE FBC
 REQUIREMENT.
 COMMENT FROM THE 1ST REVIEW. 11C) THIS COMMENT WILL BE
 A COMMON COMMENT FOR ALL FLOORS (FLOOR SLABS ARE 8 INCH
 POST TENSION SLABS) , THE 3RD -16TH STORY. PLEASE
 PROVIDE COMPLIANCE WITH BLDG TYPE: TYPE I/ TYPE II
 FLOOR INSULATION
  
 11C)(1A) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 11C)(1B) FBC-B 2010 1207.2 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 11C)(1C) FLAME SPREAD- FBC-B 2010 603.1.2 EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 11D) NEW COMMENT. PLEASE SEE MARK UP ON SHEET
 045-A2.5.2. THE COMMON CORRIDOR HAS PINCH POINTS IN THE
 CORRIDOR NEXT TO THE COLUMN LINE WHERE 36 INCH MINIMUM
 IS REQUIRED FOR THE CORRIDOR WIDTH BOTH BY FAIR HOUSING
 AND THE 2010 FBC-B 1018.2 EXC. # 2.
  
 12A) COMPLIED.
  
 12B) POOL DECK AND THE MEANS OF EGRESS. PLEASE VERIFY
 THE EGRESS DOORS THAT LEAD FROM THE POOL DECK TO THE
 INTERIOR OF THE BUILDING HAVE CARD READERS ON BOTH
 DOORS. PLEASE VERIFY THE CARD READERS ARE FOR ENTRY
 ONTO THE POOL DECK. THAT IF YOU ARE ON THE POOL DECK
 THE DOORS WILL AUTOMATICALLY UNLOCK. THIS CONFIGURATION
 WILL ALSO LIMIT CHILDREN GAINING ACCESS TO THE POOL
 DECK AND BE IN COMPLIANCE WITH 2010 FBC-B 424.1.3.1.9.
  
 12C) COMPLIED.
  
 12D) 2ND REQUEST. PLEASE SEE THE SHEET 119-A6.16.1 THE
 TOTAL CORRIDOR WIDTH IS 4 FT. 7 ? INCHES WIDE. DOOR
 706F DOES NOT COMPLY WITH THE FAIR HOUSING GUIDE LINES
 REQUIREMENT 2. ACCESSIBLE AND USABLE PUBLIC AND COMMON
 USE AREAS. ANSI A117.1 TABLE 404.2.4.1 MANEUVERING
 CLEARANCES FOR MANUAL SWING DOORS.
  
 12E) NOTE THERE IS NO KNOWING WHICH WAY A R2 OCCUPANCY
 CAN TURN INTO. APARTMENT BUILDINGS ARE A R-2 AS WELL AS
 CONDOMINIUMS. IT ISN?T UNTIL C.O. THAT THE DOCUMENTS GO
 TO THE STATE FOR THE DECLARATION OF CONDOMINIUM. THIS
 NEXT CODE ISSUE WILL BE A PROVISO, THE PLANS BEING
 REVIEWED AS THIS IS TO BE A CONDOMINIUM AND UNDER FAIR
 HOUSING.
 PROVISO: NOTE THIS POOL DECK AND POOL ARE COVERED UNDER
 THE FAIR HOUSING ACT, TO DATE THE GUIDELINES ONLY
 REQUIRES ACCESS MUST BE PROVIDED TO THE POOL DECK AREA,
 NOT AN ACCESSIBLE ROUTE (RAMP OR LIFT) DOWN INTO THE
 WATER INTO THE POOL. ON THE OTHER HAND IF THE
 ASSOCIATION ELECTS TO ALLOW THE COMMUNITY ROOM, POOL,
 AND OR POOL DECK TO BE RENTED OUT FOR PARTIES THAT THE
 PUBLIC COULD USE, THEN THIS AREA WOULD BE REQUIRED TO
 MEET FLORIDA ACCESSIBILITY SECTION 1009 OF THE
 ACCESSIBILITY CODE POOL LIFTS.
  
 12F) 2ND REQUEST. ) THIS NOTE WILL BE A COMMON NOTE FOR
 FLOORS 7-20TH FLOORS. THE DOOR SCHEDULE FOUND ON PAGE
 126 A.7.1.1 (DOOR SCHEDULE) IN THE REMARKS COLUMN THERE
 ARE VARIOUS DOORS IN THE CORRIDOR(STORAGE & ELECTRICAL)
 THAT STATE THAT A FIRE DAMPER IS TO BE INSTALLED IN THE
 LOUVERED DOOR. PLEASE SHOW COMPLIANCE WITH:
  
 2010 FBC-B 715.4.6 LABELED PROTECTIVE ASSEMBLIES. FIRE
 DOOR ASSEMBLIES SHALL BE LABELED BY AN APPROVED AGENCY.
 THE LABELS SHALL COMPLY WITH NFPA 80, AND SHALL BE
 PERMANENTLY AFFIXED TO THE DOOR OR FRAME INSTALLED
 WITHIN THE LOUVERED DOOR.
  
 716.5.2 FIRE BARRIERS. DUCTS AND AIR TRANSFER OPENINGS
 OF FIRE BARRIERS SHALL BE PROTECTED WITH APPROVED FIRE
 DAMPERS INSTALLED IN ACCORDANCE WITH THEIR LISTING.
  
 12G) COMPLIED.
 13A) COMPLIED. SLIDING GLASS DOORS.
 13B) 2ND REQUEST. ) FOR ALL SLIDING GLASS DOORS THE
 HARDWARE WILL ALSO NEED TO MEET THE ANSI 117.1 STANDARD
 404.2.7. RESPONSE INDICATES SEE SPECS, REQUIREMENT
 INCLUDED IN SPEC. IF SPEC BOOKS ARE SUBMITTED WE STAMP
 THEM VOID. WE ARE LOOKING FOR CODE COMPLIANCE ON THE
 PLANS. WE DO NOT REVIEW SPEC BOOKS>
  
 14A-D) COMPLIED.
  
 14E) PROVISO: THE PLANS INDICATE THE USE OF
 PRE-ENGINEERED A/C STANDS. WHEN FIGURING THE REQUIRED
 CLEARANCES IN HEIGHT REQUIRED BY TABLE FBC-B 1509.7,
 THE CLEARANCE IS FROM THE FINISHED ROOF HEIGHT, ABOVE
 THE LIGHTWEIGHT CONCRETE ROOF.
  
 15) COMPLIED,
  
 16A-C) PRODUCT APPROVALS: DEFERRED SUBMITTAL. ARCHITECT
 WILL APPROVE/ STAMP EACH PRODUCT APPROVAL AND SUBMIT.
  
 17-18) COMPLIED.
  
 19)A7.5.3
 19A) PROVISO: ) NOTE: THE POOL TRELLIS STRUCTURE
 (PERGOLA) THIS DETAIL INDICATES IT IS GOING TO BE
 DESIGNED BY A SPECIALTY ENGINEER. BEFORE SUBMITTAL TO
 THE BUILDING DEPARTMENT, THE PLANS WILL NEED TO BE
 REVIEWED BY THE ENGINEER OF RECORD. FL 61G-15-30.006
 (3) THE DELEGATED ENGINEER SHALL FORWARD THE DELEGATED
 ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR
 REVIEW.
  
 19B) COMPLIED.
  
  
  
 20) PAGE 136 A7.5.4. 20A) PROVISO: DETAIL # 5 RIGID
 ALUMINUM CANOPY WITH FABRIC WRAPPED WILL REQUIRE WIND
 DESIGN CRITERIA SEE OPTIONS FOUND UNDER FBC-B 3105.4 .
 ALSO: FL 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL
 FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO THE
 ENGINEER OF RECORD FOR REVIEW.
  
 21-23) COMPLIED.
  
 24 A-C) COMPLIED.
  
 24D) 2ND REQUEST ) FBC-B 403.4.6 SMOKE REMOVAL. SMOKE
 CONTROL SHALL BE PROVIDED IN ACCORDANCE WITH SECTION
 909. SEE MECHANICAL REVIEWERS COMMENTS.
  
 24E-G) COMPLIED.
  
 24H) PROVISO: FBC-B 403.5.3.1 STAIRWAY COMMUNICATION
 SYSTEM. A TELEPHONE OR OTHER TWO-WAY COMMUNICATIONS
 SYSTEM CONNECTED TO AN APPROVED CONSTANTLY ATTENDED
 STATION SHALL BE PROVIDED AT NOT LESS THAN EVERY FIFTH
 FLOOR IN EACH STAIRWAY WHERE THE DOORS TO THE STAIRWAY
 ARE LOCKED.
  
 24I) 2ND REQUEST. ) FBC-B 403.5.4 SMOKEPROOF EXIT
 ENCLOSURES. EVERY REQUIRED EXIT STAIRWAY SERVING FLOORS
 MORE THAN 75 FEET (22 860 MM) ABOVE THE LOWEST LEVEL OF
 FIRE DEPARTMENT VEHICLE ACCESS SHALL COMPLY WITH
 SECTIONS 909.20 AND 1022.9. SEE MECHANICAL REVIEWER
 COMMENT 9A.
  
 24J) 2ND REQUEST, RESPONSE: ACKNOWLEDGED. FBC-B 1022.8
 FLOOR IDENTIFICATION SIGNS. / 1022.8.1 SIGNAGE
 REQUIREMENTS.
  
 24K) COMPLIED.
  
 25) COMPLIED. IMPACT FEES PAID.
  
 26) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-05-18 Cont ID  
Sent By jwitmer Date 2015-05-18 Time 07:33 Rev Time  
Received By jwitmer Date 2015-05-06 Time 07:01 Sent To  
Notes
2015-05-17 14:08:14BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15031312
 ADD: 333 FERN ST.
 CONT: KAST CONSTRUCTION
 CONTACT :
 TEL: (561)689-2910
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 1ST REVIEW
 DATE: MAY 18 /2015
 ACTION: DENIED
  
 1) NOTICE ONLY; THE CITY OF WEST PALM BEACH ART IN
 PUBLIC PLACES ORDINANCE REQUIREMENT THAT APPLIES TO ANY
 REMODEL OR NEW CONSTRUCTION PROJECT FOR WHICH THE
 PERMIT APPLICATION WAS SUBMITTED AFTER 7/1/14, AND THE
 TOTAL PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR
 GREATER THAN $500,000. PER CITY OF WEST PALM BEACH
 ORDINANCE NO. 4504-14, AND CITY OF WEST PALM BEACH CODE
 OF ORDINANCES, ARTICLE V, ART IN PUBLIC PLACES, SECTION
 78-123(A) AND SECTION 78-126(A), THE ART ASSESSMENT IS
 1% OF THE TOTAL PROJECT CONSTRUCTION COST.
  
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE
 V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND
 NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO
 THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS.
  
 2) THE PERMIT APPLIED VALUE IS STATED AS $28,665,000.00
 DOLLARS. THE CALCULATED VALUE IS $44,101,328.00 DOLLARS
 IN VALUE. USING THE FLOOR AREA SUMMARY FOUND ON 022
 SP1.1. PLEASE PROVIDE THE SQUARE FOOTAGE PER FLOOR.
 PLEASE BREAK OUT MIXED USE OCCUPANCIES PER FLOOR. FOR
 THE PARKING GARAGE PLEASE PROVIDE AREA BY LEVEL.
  
 W P B ADMINISTRATIVE CODE 108.2 SCHEDULE OF PERMIT
 FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS,
 MECHANICAL AND PLUMBING SYSTEMS OR ALTERATIONS
 REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID
 AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE
 ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY.
  
 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 3) PLEASE PROVIDE A SURVEY WITH THE PROPOSED OVERLAY OF
 THE BUILDING TO VERIFY THE ACTUAL DISTANCE FROM
 PROPERTY LINES. 2010 FBC-B TABLE 602.
 4) THE CURRENT SURVEY SUBMITTED INDICATES THIS PROPOSED
 STRUCTURE WILL BE LOCATED ON LOTS 11-15 OF BLOCK 10. A
 REPLAT WILL BE REQUIRED TO ELIMINATE THE BUILDING GOING
 PAST PROPERTY LINES. TABLE 602.
  
 5) NO ENERGY REPORT AND CALCULATIONS WERE SUBMITTED.
 PLEASE PROVIDE CODE COMPLIANCE WITH THE 2010 FBC-ENERGY
 103.2.1 CODE DEMONSTRATION FORMS, TABLE 103.2.1.
  
 6) THIS BUILDING QUALIFIES AS A THRESHOLD BUILDING.
 ?THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN
 THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT.
 IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 6A) THRESHOLD INSPECTION PLAN FL S. S. 553.71(7). 2010
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 109.3.6.1 THE ENFORCING
 AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 6B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUESTS FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS
 ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH
 INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND
 REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE
 PLACE. CONTACT KEN CONRAD MANAGER OF THE SPECIAL
 INSPECTOR PROGRAM AT (561)805-6666 FOR FURTHER
 INFORMATION BEFORE THE PERMIT MAY BE ISSUED.
 FORMS WERE SENT TO: : [email protected] AT
 05/09/2015 02:09 PM.
  
 6C) THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B.
 AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH
 ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT
 OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 6D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
 CONTACT KEN CONRAD
 TEL: 561-805-6666
 E-MAIL: [email protected]
  
 6E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION. THIS MAY BE
 SUBMITTED TO KEN CONRAD BY E-MAIL. KEN CONRAD:
 [email protected]
  
 6F) FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, THE
 PERMIT LIBRARIAN WILL E-MAIL YOU, THE APPROVED AND
 BATCH STAMPED PLANS SO YOU MAY PRINT YOUR PLANS, TWO
 SETS OF PLANS WILL NEED TO BE PRINTED IN COLOR, (1) FOR
 THE THRESHOLD INSPECTOR, THE OTHER FOR THE MEP
 INSPECTORS.
  
  
 6G) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR
 IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS.
  
 6H) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES
 FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER
 HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE
 MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR
 WALLS AND CEILINGS.
  
 7) PAGE 024 LS-1.0, 032 A2.1.1 & 033 A2.1.2.
  
 7A) THESE PLANS INDICATE 5 STAIRWELLS WITH STAIRS 4 & 5
 HAVING THE EXIT DISCHARGE DIRECTLY AT THE EXTERIOR OF
 THE BUILDING. STAIR 1 EXITS THE VERTICAL ENCLOSURE
 TRAVEL THROUGH THE ELEVATOR LOBBY, MAIN LOBBY AND
 GALLERY BEFORE THE EXIT DISCHARGE IS ARRIVED AT. IN THE
 ELEVATOR LOBBY THERE ARE (2) COLUMNS AND SOME WALL TYPE
 THAT WOULD BLOCK THE VIEW OF THE MAIN ENTRANCE, MORE
 INFORMATION IS REQUIRED HOW THIS WILL QUALIFY UNDER THE
 EXCEPTIONS FOUND IN SECTION FBC-B 1027.1 IT APPEARS
 EXCEPTION 1 WOULD BE TAKEN?
  
 7B) THE OTHER STAIRWELL # 3 IT APPEARS IS ALSO TAKING
 THE SAME EXCEPTION FOUND IN 2010 FBC-B 1027.1 EXCEPTION
 # 1. THE 2007 FBC CODE COMMENTARY DOES IN PRINCIPLE
 AGREE, THERE IS LANGUAGE DOES LEAVE ROOM FOR QUESTION.
 THIS DOES NOT MEAN THE EXTERIOR EXIT DOOR MUST BE
 DIRECTLY IN FRONT OF THE DOOR AT THE BOTTOM OF THE
 STAIRWAY, BUT THE INTENT IS THAT IT SHOULD BE WITHIN
 THE GENERAL RANGE OF VISION. IT SHOULD NOT BE REQUIRED
 THAT A PERSON MUST TURN COMPLETELY AROUND OR GO AROUND
 A CORNER TO BE ABLE TO SEE THE WAY OUT.
  
 7C) STAIRWELL # 2 ROOM 139 IS SHOWN WITH A 2 HR.
 ENCLOSURE DOOR 139 1 ? HOUR OPENING PROTECTIVE. THE
 EXTENSION OF THE EXIT IS LABELED AS AN EXIT ACCESS
 CORRIDOR # 115. PLEASE NOTE THIS IS AN EXIT PASSAGE WAY
 AND NEEDS TO COMPLY WITH SECTION FBC-B 1023.6
 PENETRATIONS. THE MECHANICAL AND ELECTRICAL PLANS
 INDICATE AN INTAKE AIR LOUVER AN FAN WITH 2160 CFM TO
 PRESSURIZE THE EXIT PASSAGEWAY. NOTE NO ELECTRICAL RACE
 WAYS, CONDUITS, ETC. FROM THE FPL VAULT OR FROM THE
 SWITCHGEAR/ ELECTRICAL ROOM RUN THROUGH THIS EXIT
 PASSAGEWAY.
  
 7D) PLEASE NOTE THE EXIT PASSAGEWAY 115 THE TOP AND
 BOTTOM SLOPED AREAS MEET THE DEFINITION OF GRADE WITH A
 SLOPE OF 1:20 THE MIDDLE SECTION FROM LANDING MARKED AS
 12.75 FT. TO LANDING 12.08 FT. IS A DIFFERENCE OF 8
 INCHES X 20= 160 INCHES (13.3 FT. RAMP FBC-B 1010.2
 SLOPE) OF RUN REQUIRED NOT TO BE CONSIDERED A RAMP.
 THIS SECTION WILL NEED TO COMPLY WITH 2010 FBC-B 1010.8
 HANDRAILS.
  
 7E) THE PLANS INDICATE A SERIES OF LOUVERS AND WALL
 OPENINGS, THE OPENINGS DO NOT SHOW ANY PROTECTION NOR
 DOES THE LOUVERS WITH THE EXCEPTION OF LOUVER 17 SEE
 SHEET A7.4. THE FBC-B TABLE 705.8 BASES THE AMOUNT OF
 OPENINGS BASED ON THE SEPARATION DISTANCE. WHEN FACING
 PUBLIC RIGHT OF WAYS STREETS OR ALLIES AN ASSUMED
 PROPERTY LINE IS TAKEN FROM THE CENTER OF THE STREET OR
 ALLEY WAY OR IN THIS CASE 7?-0? FROM THE
 PROPERTY LINE, ALSO SEE FOOTNOTE (A) THE VALUES
 INDICATED ARE THE PERCENTAGE OF THE AREA OF THE
 EXTERIOR WALL, PER STORY.
  
 7F) TRASH TERMINATION ROOM # 117 HAS (2) DOORS A SWING
 DOOR LISTED AS 117 WHILE THE OVERHEAD DOOR DOES NOT
 HAVE A IDENTIFICATION TAG, NOR DOOR RATING AS REQUIRED
 BY 2010 FBC-B 70813.4.
  
 7G) THE DOOR 101 SEPARATING THE S2 STORAGE OCCUPANCY
 FROM THE BUSINESS OCCUPANCY IS MISSING THE DOOR RATING
 ON THE DOOR SCHEDULE, PAGE 126 A.7.1.1. 2010 FBC-B
 TABLE 715.4.
  
 7H) THIS NOTE IS COMMON FOR ALL FLOORS. IN REVIEWING
 THE VARIOUS DOORS IN EXIT ENCLOSURES FOR THERE FIRE
 RATINGS IN THE DOOR SCHEDULE LISTED ON PAGE 126 A7.1.1
 THERE IS A NOTE # 1 FOR HARDWARE SETS REFER TO
 SPECIFICATIONS. PLEASE NOTE SPECIFICATIONS ARE
 SOMETHING WE NORMALLY DO NOT REVIEW SINCE THEY CAN BE
 SEVERAL HUNDRED PAGES IN LENGTH. PLEASE PROVIDE A
 HARDWARE SCHEDULE THAT RELATES TO THE DOOR SCHEDULE SO
 CODE COMPLIANCE CAN BE REVIEWED. NORMALLY
 SPECIFICATIONS ARE STAMPED VOID NOT REVIEWED.
 7I) PLEASE PROVIDE THE 1ST FLOOR SQ. FOOTAGE VERSES THE
 OWNERS STORAGE LOCKER AREA TO SEE IF THIS AREA
 QUALIFIES AS AN MIXED USE OCCUPANCY REQUIRING
 SEPARATION. 2010 FBC-B 508.2.1.
 7J) HORIZONTAL TRELLIS FOUND ON THE SOUTH & WEST SIDES
 OF THE BUILDING SEE SECTION 6,8 & 9 PAGE A7.5.4. PLEASE
 SHOW WIND DESIGN AND ANCHORING DETAILS. FBC-B
 1609.6.4.4.1 COMPONENTS & CLADDING. FL 61G-15-30.006
 (3) THE DELEGATED ENGINEER SHALL FORWARD THE DELEGATED
 ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR
 REVIEW.
  
 7K) NOTE!!! THE FPL VAULT TO BE BUILT TO THE AGREEMENT
 BETWEEN FPL AND PROPERTY OWNER.
 7L) PLEASE PROVIDE COMPLIANCE WITH THE 2010 FBC-B: F]
 914.1.1 EXTERIOR ACCESS TO SHAFTWAYS. OUTSIDE OPENINGS
 ACCESSIBLE TO THE FIRE DEPARTMENT AND THAT OPEN
 DIRECTLY ON A HOISTWAY OR SHAFTWAY COMMUNICATING
 BETWEEN TWO OR MORE FLOORS IN A BUILDING SHALL BE
 PLAINLY MARKED WITH THE WORD ?SHAFTWAY? IN RED LETTERS
 AT LEAST 6 INCHES (152 MM) HIGH ON A WHITE BACKGROUND.
 SUCH WARNING SIGNS SHALL BE PLACED SO AS TO BE READILY
 DISCERNIBLE FROM THE OUTSIDE OF THE BUILDING.
 7M) PLEASE PROVIDE COMPLIANCE WITH THE 2010 FBC-B: F
 914.1.2 INTERIOR ACCESS TO SHAFTWAYS. DOOR OR WINDOW
 OPENINGS TO A HOISTWAY OR SHAFTWAY FROM THE INTERIOR OF
 THE BUILDING SHALL BE PLAINLY MARKED WITH THE WORD
 ?SHAFTWAY? IN RED LETTERS AT LEAST 6 INCHES (152 MM)
 HIGH ON A WHITE BACKGROUND. SUCH WARNING SIGNS SHALL BE
 PLACED SO AS TO BE READILY DISCERNIBLE.
 7N) PLEASE PROVIDE COMPLIANCE WITH THE 2010 FBC-B: [F]
 914.2 EQUIPMENT ROOM IDENTIFICATION. FIRE PROTECTION
 EQUIPMENT SHALL BE IDENTIFIED IN AN APPROVED MANNER.
 ROOMS CONTAINING CONTROLS FOR AIR-CONDITIONING SYSTEMS,
 SPRINKLER RISERS AND VALVES OR OTHER FIRE DETECTION,
 SUPPRESSION OR CONTROL ELEMENTS SHALL BE IDENTIFIED FOR
 THE USE OF THE FIRE DEPARTMENT. APPROVED SIGNS REQUIRED
 TO IDENTIFY FIRE PROTECTION EQUIPMENT AND EQUIPMENT
 LOCATION SHALL BE CONSTRUCTED OF DURABLE MATERIALS,
 PERMANENTLY INSTALLED AND READILY VISIBLE.
 7O) PLEASE PROVIDE COMPLIANCE WITH THE 2010 FBC-B: [F]
 915.1 GENERAL. [F] 915.1 GENERAL.
 EMERGENCY RESPONDER RADIO COVERAGE SHALL BE PROVIDED IN
 ALL NEW BUILDINGS IN ACCORDANCE THE FLORIDA FIRE
 PREVENTION CODE.
  
 7P) PLEASE PROVIDE COMPLIANCE WITH THE 2010 FBC-B 916.1
 CARBON MONOXIDE PROTECTION. EVERY SEPARATE BUILDING OR
 AN ADDITION TO AN EXISTING BUILDING FOR WHICH A PERMIT
 FOR NEW CONSTRUCTION IS ISSUED AND HAVING A
 FOSSIL-FUEL-BURNING HEATER OR APPLIANCE, A FIREPLACE,
 AN ATTACHED GARAGE, OR OTHER FEATURE, FIXTURE, OR
 ELEMENT THAT EMITS CARBON MONOXIDE AS A BYPRODUCT OF
 COMBUSTION SHALL HAVE AN OPERATIONAL CARBON MONOXIDE
 ALARM INSTALLED WITHIN 10 FEET OF EACH ROOM USED FOR
 SLEEPING PURPOSES IN THE NEW BUILDING OR ADDITION, OR
 AT SUCH OTHER LOCATIONS AS REQUIRED BY THIS CODE.
  
 8) 2ND FLOOR, PAGE 025 LS-2-0, 035 A2-2-1,& A-2-2-2.
 8A) THE HANDICAPPED SPACE # 58 DOES NOT HAVE A 5?-0?
 CLEAR ACCESS AISLE NEXT TO IT, THERE IS A COLUMN IN THE
 WAY AT GRID LINE C.6 AND 1.5. NOTE THE COLUMN IS 3FT 3
 INCHES FROM THE ACCESSIBLE PARKING SPACE, EVEN THOUGH
 THE AISLE IS WIDER IF THE COLUMN IS AT A POINT WHERE
 THE DOOR CANNOT BE OPENED NOR A VANS ACCESSIBLE
 PLATFORM CANNOT BE LOWERED.
 8B) THERE IS (2) AREAS NOT CLEAR AS TO WHERE THE
 CEILING IS LOCATED OR IF THE BLOCK WALL GOES ALL THE
 WAY TO THE 3RD FLOOR. SEE FPL TRANSFORMER VAULT AND
 SWITCHGEAR/ ELECTRIC ROOM. 107.2.1.3 ADDITIONAL
 INFORMATION REQUIRED.
 9) PAGE 026 LS-3.0, PAGE 038 A2.3.1 & PAGE 039 A2.3.2:
 9A) DOORS 307.02 & 307.03 BOTH DOORS ARE CONSIDERED
 COMMON AREA DOORS SINCE THEY ARE NOT ENTRY DOORS TO THE
 UNIT. THE 2 DOORS DO NOT HAVE THE 18 INCHES REQUIRED ON
 THE LATCH SIDE OF THE DOOR, PER FAIR HOUSING
 REQUIREMENT 3. USABLE DOORS. GUIDELINE SECTION
 100.205(C)(2) WOULD APPLY TO DOORS THAT ARE A PART OF
 AN ACCESSIBLE ROUTE IN THE PUBLIC AND COMMON USE AREAS
 OF MULTIFAMILY DWELLINGS AND TO DOORS INTO AND WITHIN
 INDIVIDUAL DWELLING UNITS.
 (1) ON ACCESSIBLE ROUTES IN PUBLIC AND COMMON USE AREAS
 AND FOR PRIMARY ENTRY DOORS TO COVERED UNITS, DOORS
 THAT COMPLY WITH ANSI 4.13 WOULD MEET THIS REQUIREMENT.
 9B)NOTE THIS WILL BE A COMMON STATEMENT FOR ALL UNITS
 FOUND ON:
 PAGE 078 A6.1.2 UNIT 301 & 302
 PAGE 080 A6.2.2 UNIT 303 & 304
 PAGE 083 A6.3.2 UNIT 305 & 306
 PLEASE NOTE THE TENANT SEPARATION WALLS FOR THIS FLOOR
 INDICATE A 1 HOUR FIRE RATING BUT THE DOOR SCHEDULE FOR
 THE TYPICAL DWELLING UNIT DOORS SHOWS THE ENTRY DOOR AS
 WELL AS THE A/C CLOSET DOOR THAT IS WITHIN THE TENANT
 SEPARATION WALL BOTH SHOW 20 MIN. DOORS. FBC-B TABLE
 715.4 DOES ALLOW FOR 20 MIN. DOORS INTO CORRIDORS FOR A
 GENERAL RULE. SECTION 709.3 FIRE RESISTANCE RATINGS AS
 WELL IN EXCEPTION # 1 ALLOWS FOR CORRIDOR WALLS TO BE ?
 HR. RATED. EXCEPTION # 2 FOR DWELLING UNITS DOES NOT
 GIVE THE REDUCTION FOR TYPE I BUILDINGS, THE REDUCTION
 CAN ONLY TAKE PLACE IN TYPE IIB, IIIB AND VB.
 10) PAGE 027 LS 4.0, PAGE 041 A2.4.1 & PAGE 042 A2.4.2:
 NOTE: COMMENTS FOR THE 4TH FLOOR WILL ALSO STAND FOR
 THE 6TH FLOOR.
  
 10A) THE COMMON CMU WALL BETWEEN THE PARKING GARAGE AND
 OPEN AIR 3RD STORY DWELLING UNITS (CLEARSTORY) IS A 2
 HOUR FIRE RATED WALL. THE STRUCTURAL SHEETS SHOW
 DETAILS OF THIS WALL PAGE 171 S2.40 SHOWS A DETAIL #7
 FOUND ON S5-10. THIS DETAIL SHOW A REINFORCED CONCRETE
 POURED 8 INCH WALL TO COMPLY WITH FBC-B 1607.7.3
 VEHICLE BARRIER SYSTEMS. THERE ARE (2) POINTS OF
 LOADING TO CONSIDER, PLEASE PROVIDE HOW THE 2ND IS MET:
 THE SECOND LOADING CONDITION SHALL APPLY THE LOAD AT 2
 FEET, 3 INCHES (686 MM) ABOVE THE FLOOR OR RAMP
 SURFACE. THE MORE SEVERE LOAD CONDITION SHALL GOVERN
 THE DESIGN OF THE BARRIER.
 10B) THE 2ND COMMENT DEALS WITH AN ACCESSIBLE PARKING
 SPACE AND ACCESS AISLE NEXT TO STAIR # 3. THE FAIR
 HOUSING REQUIREMENT 2. ACCESSIBLE AND USABLE PUBLIC AND
 COMMON USE AREAS. ANSI 117.1 GENERAL SITE AND BUILDING
 ELEMENTS. SECTION 503.3 ACCESS AISLES. WIDTH 503.3.1 60
 INCHES/ LENGTH 503.3.2 20 FT. LONG MINIMUM.
 11) PAGE 028 LS 5.0, PAGE 044 A2.5.1 & PAGE 045 A2.5.2:
 11A) DOORS 507.02 & 507.03 BOTH DOORS ARE CONSIDERED
 COMMON AREA DOORS SINCE THEY ARE NOT ENTRY DOORS TO THE
 UNIT. THE 2 DOORS DO NOT HAVE THE 18 INCHES REQUIRED ON
 THE LATCH SIDE OF THE DOOR, PER FAIR HOUSING
 REQUIREMENT 3. USABLE DOORS. GUIDELINE SECTION
 100.205(C)(2) WOULD APPLY TO DOORS THAT ARE A PART OF
 AN ACCESSIBLE ROUTE IN THE PUBLIC AND COMMON USE AREAS
 OF MULTIFAMILY DWELLINGS AND TO DOORS INTO AND WITHIN
 INDIVIDUAL DWELLING UNITS.
 (1) ON ACCESSIBLE ROUTES IN PUBLIC AND COMMON USE AREAS
 AND FOR PRIMARY ENTRY DOORS TO COVERED UNITS, DOORS
 THAT COMPLY WITH ANSI 4.13 WOULD MEET THIS REQUIREMENT.
  
 11B)NOTE THIS WILL BE A COMMON STATEMENT FOR ALL UNITS
 FOUND ON:
 PAGE 078 A6.1.2 UNIT 501 & 502
 PAGE 080 A6.2.2 UNIT5303 & 504
 PAGE 083 A6.3.2 UNIT 505 & 506
 PLEASE NOTE THE TENANT SEPARATION WALLS FOR THIS FLOOR
 INDICATE A 1 HOUR FIRE RATING BUT THE DOOR SCHEDULE FOR
 THE TYPICAL DWELLING UNIT DOORS SHOWS THE ENTRY DOOR AS
 WELL AS THE A/C CLOSET DOOR THAT IS WITHIN THE TENANT
 SEPARATION WALL BOTH SHOW 20 MIN. DOORS. FBC-B TABLE
 715.4 DOES ALLOW FOR 20 MIN. DOORS INTO CORRIDORS FOR A
 GENERAL RULE. SECTION 709.3 FIRE RESISTANCE RATINGS AS
 WELL IN EXCEPTION # 1 ALLOWS FOR CORRIDOR WALLS TO BE ?
 HR. RATED. EXCEPTION # 2 FOR DWELLING UNITS DOES NOT
 GIVE THE REDUCTION FOR TYPE I BUILDINGS, THE REDUCTION
 CAN ONLY TAKE PLACE IN TYPE IIB, IIIB AND VB.
  
 11C) THIS COMMENT WILL BE A COMMON COMMENT FOR ALL
 FLOORS,(FLOOR SLABS ARE 8 INCH POST TENSION SLABS) THE
 3RD -16TH STORY. PLEASE PROVIDE COMPLIANCE WITH BLDG
 TYPE: TYPE I/ TYPE II FLOOR INSULATION
  
 11C)(1A) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 11C)(1B) FBC-B 2010 1207.2 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 11C)(1C) FLAME SPREAD- FBC-B 2010 603.1.2 EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 703.4 NONCOMBUSTIBILITY TESTS.
  
 THE TESTS INDICATED IN SECTIONS 703.4.1 AND 703.4.2
 SHALL SERVE AS CRITERIA FOR ACCEPTANCE OF BUILDING
 MATERIALS AS SET FORTH IN SECTIONS 602.2, 602.3 AND
 602.4 IN TYPE I, II, III AND IV CONSTRUCTION. THE TERM
 ?NONCOMBUSTIBLE? DOES NOT APPLY TO THE FLAME SPREAD
 CHARACTERISTICS OF INTERIOR FINISH OR TRIM MATERIALS. A
 MATERIAL SHALL NOT BE CLASSIFIED AS A NONCOMBUSTIBLE
 BUILDING CONSTRUCTION MATERIAL IF IT IS SUBJECT TO AN
 INCREASE IN COMBUSTIBILITY OR FLAME SPREAD BEYOND THE
 LIMITATIONS HEREIN ESTABLISHED THROUGH THE EFFECTS OF
 AGE, MOISTURE OR OTHER ATMOSPHERIC CONDITIONS.
  
 703.4.1 ELEMENTARY MATERIALS.
 MATERIALS REQUIRED TO BE NONCOMBUSTIBLE SHALL BE TESTED
 IN ACCORDANCE WITH ASTM E 136.
  
 703.4.2 COMPOSITE MATERIALS.
 MATERIALS HAVING A STRUCTURAL BASE OF NONCOMBUSTIBLE
 MATERIAL AS DETERMINED IN ACCORDANCE WITH SECTION
 703.4.1 WITH A SURFACING NOT MORE THAN 0.125 INCH (3.18
 MM) THICK THAT HAS A FLAME SPREAD INDEX NOT GREATER
 THAN 50 WHEN TESTED IN ACCORDANCE WITH ASTM E 84 OR UL
 723 SHALL BE ACCEPTABLE AS
 NONCOMBUSTIBLE MATERIALS.
  
 12) PAGE 030 LS 7.0, PAGE 050 A2.7.1 & PAGE 051 A2.7.2:
 12A) COMMON ROOM 701.01 APPROXIMATELY 1286 SQ. FT./ 15=
 85 OCCUPANTS, THIS ROOM WILL REQUIRE 2 EXITS. NOTE ONE
 EXIT IS THROUGH THE ELEVATOR LOBBY (700) TO STAIR 701.
 THE LIFE SAFETY SHEET DOES NOT SHOW EXITING FOR THIS
 ROOM. 708.14.1 ELEVATOR LOBBIES SHALL HAVE AT LEAST ONE
 MEANS OF EGRESS COMPLYING WITH CHAPTER 10 AND OTHER
 PROVISIONS WITHIN THIS CODE. IN REALITY STAIRWELL 701
 CANNOT BE USED FOR THIS FLOOR AS DEPICTED!
 12B) THE POOL DECK AND POOL SURFACE AREA TOTAL OCCUPANT
 LOAD EQUAL A TOTAL OF 121 OCCUPANTS. PLEASE PROVIDE THE
 (2) MEANS OF EGRESS WITHOUT GOING THROUGH THE ELEVATOR
 LOBBY. IN REALITY STAIRWELL 701 CANNOT BE USED FOR THIS
 FLOOR AS DEPICTED!
 12C) EXIT ROUTE # 07 WEST TRAVELS THROUGH THE ELEVATOR
 LOBBY. . 708.14.1 ELEVATOR LOBBIES SHALL HAVE AT LEAST
 ONE MEANS OF EGRESS COMPLYING WITH CHAPTER 10 AND OTHER
 PROVISIONS WITHIN THIS CODE. IN REALITY STAIRWELL 701
 CANNOT BE USED FOR THIS FLOOR AS DEPICTED!
 12D) DOOR 706F DOES NOT COMPLY WITH THE FAIR HOUSING
 GUIDE LINES REQUIREMENT 2. ACCESSIBLE AND USABLE PUBLIC
 AND COMMON USE AREAS. ANSI A117.1 TABLE 404.2.4.1
 MANEUVERING CLEARANCES FOR MANUAL SWING DOORS.
 12E) NOTE THIS POOL DECK AND POOL ARE COVERED UNDER THE
 FAIR HOUSING ACT, TO DATE THE GUIDELINES ONLY REQUIRES
 ACCESS MUST BE PROVIDED TO THE POOL DECK AREA, NOT AN
 ACCESSIBLE ROUTE(RAMP OR LIFT) DOWN INTO THE WATER INTO
 THE POOL. ON THE OTHER HAND IF THE ASSOCIATION ELECTS
 TO ALLOW THE COMMUNITY ROOM, POOL, AND OR POOL DECK TO
 BE RENTED OUT FOR PARTIES THAT THE PUBLIC COULD USE,
 THEN THIS AREA WOULD BE REQUIRED TO MEET FLORIDA
 ACCESSIBILITY SECTION 1009 OF THE ACCESSIBILITY CODE
 POOL LIFTS.
 12F) THIS NOTE WILL BE A COMMON NOTE FOR FLOORS 7-20TH
 FLOORS. THE DOOR SCHEDULE FOUND ON PAGE 126 A.7.1.1
 (DOOR SCHEDULE) IN THE REMARKS COLUMN THERE ARE VARIOUS
 DOORS IN THE CORRIDOR THAT STATE THAT A FIRE DAMPER IS
 TO BE INSTALLED IN THE LOUVERED DOOR. PLEASE SHOW
 COMPLIANCE WITH:
  
 2010 FBC-B 715.4.6 LABELED PROTECTIVE ASSEMBLIES. FIRE
 DOOR ASSEMBLIES SHALL BE LABELED BY AN APPROVED AGENCY.
 THE LABELS SHALL COMPLY WITH NFPA 80, AND SHALL BE
 PERMANENTLY AFFIXED TO THE DOOR OR FRAME INSTALLED
 WITHIN THE LOUVERED DOOR.
  
 716.5.2 FIRE BARRIERS. DUCTS AND AIR TRANSFER OPENINGS
 OF FIRE BARRIERS SHALL BE PROTECTED WITH APPROVED FIRE
 DAMPERS INSTALLED IN ACCORDANCE WITH THEIR LISTING.
  
 12G) PAGE 023 LS-0.1 LIST THE REQUIRED FIRE SEPARATION
 DISTANCE FOR THE REQUIRED HOURLY RATING AND AMOUNT OF
 ALLOWABLE OPENINGS. SHEET A2-7.2 THE EAST PROPERTY LINE
 WALL IS APPROX. 13 FEET AWAY FROM THE OPENINGS, FBC-B
 TABLE 705.8 ALLOWS 45% UNPROTECTED SPRINKLERED, PLEASE
 PROVIDE THE PERCENTAGE OF ALLOWABLE OPENING TAKEN PER
 FLOOR LEVEL.
 13) PAGE 031 LS 8.0, PAGE 053 A2.8.1 & PAGE 054 A2.8.2.
 8TH-20TH FLOORS COMMON TO ALL FLOORS.
 13A) THIS PAGE SHOWS SLIDING GLASS DOOR (SGD 6) IN UNIT
 815 BEDROOM # 02, THE DOOR SCHEDULE (129 A7.3.1)
 INDICATES THIS SLIDING GLASS DOOR IS A 6FT. 4 IN. IS
 THIS A ROUGH OPENING SIZE OR OUTSIDE DOOR JAMB OPENING,
 NOT CLEAR. IN THE FAIR HOUSING GUIDE THE EXTERIOR
 SLIDING GLASS DOORS WILL NEED TO MEET REQUIREMENT # 4
 (2)
 A MINIMUM CLEAR WIDTH OF 32 INCHES IS PROVIDED.
  
 13B) FOR ALL SLIDING GLASS DOORS THE HARDWARE WILL ALSO
 NEED TO MEET THE ANSI 117.1 STANDARD 404.2.7.
  
 14) PAGE 056 A.2.9.1:
  
 14A) ROOF NOTE # 3 :
 THE NO LESS THAN R-10 IN ANY LOCATION LIKE ROOF DRAINS
 STILL HAS TO HAVE A MINIMUM OF R-19 INSULATION. SEE THE
 2010 FBC-ENERGY CODE 506.2.1 UNDER TOTAL BUILDING
 PERFORMANCE METHOD.
 SEE BOAF INFORMAL INTERPRETATION # 5438
  
 DATE: TUE NOV 13 2007
 REPORT #: 5438
 CODE: BUILDING
 SECTION: 404.1.A
 QUESTION:
 IS IT THE INTENT OF THE CODE "....THE INSULATION SHALL
 HAVE A R-VALUE OF AT LEAST R-19, SPACE PERMITTING." TO
 MEAN THE MINIMUM R-VALUE OF ROOF INSULATION TO BE R-19
 AT LOWEST POINTS AT DRAINS? ALL ROOFERS WHO WE HAVE
 SPOKEN TO, INTERPRETED THIS CODE AS MINIMUM AVERAGE
 R-19, NOT MINIMUM R-19 AND HAVE DONE MOST ROOFING JOB
 ACCORDINGLY. THANK YOU
 ANSWER: A MINIMUM LEVEL OF INSULATION REQUIRED IS THAT,
 A MINIMUM, NOT AN AVERAGE. HOWEVER, PROVIDED THE
 MINIMUM R-19 VALUE HAS BEEN MET, A REASONABLE AVERAGING
 PROCEDURE CAN BE USED BY ROOF AREA FOR CALCULATIONS OF
 THE VALUE.
 COMMENTARY: THIS QUESTION ACTUALLY REFERS TO SECTION
 13-404.1 (A) PRESCRIPTIVE REQUIREMENTS SPECIFIC TO
 METHOD A. THIS SECTION MANDATES COMPLIANCE WITH FLA/COM
 METHOD A, HOWEVER GIVES A PRESCRIPTIVE REQUIREMENT OF
 AN R-19 FOR MULTIFAMILY RESIDENTIAL ROOF/CEILING
 ASSEMBLY. AS SPACE PERMITS, MAY RELATE TO THE AREA OF
 THE EAVES WHERE THE R- 19 INSULATION WOULD HAVE TO BE
 COMPRESSED TO FIT IN THE SPACE AVAILABLE. HOWEVER, THE
 PETITIONER ALLUDES TO THE ROOFER INSTALLING THE
 INSULATION. THERE ARE NO SPACE CONSTRAINTS FOR
 INSULATION APPLIED TO A ROOF DECK; IT SHOULD BE R-19
 MINIMUM. IF THE BUILT-UP ROOF IS SLOPING TO A DRAIN IN
 A MANNER WHERE SOME PARTS OF THE ROOF HAVE MORE THAN
 R-19 AND SOME HAVE LESS, THEN THE RESIDENT WHOSE
 APARTMENT/CONDO IS UNDER THE ROOF SECTION WITH LESS
 THAN R- 19 WOULD BE PENALIZED WITH HIGHER HEAT LOADS
 AND HIGHER ENERGY COSTS THAN THEIR NEIGHBOR.
  
 14B) ROOF NOTE # 6 REFERENCES THE USE OF CHEN-CURB OR
 EQUAL FOR PIPE OR TUBE ROOF PENETRATIONS. THE PRODUCT
 SPECIFIED HAS TO BE SPECIFIC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. SUCH INFORMATION SHALL BE
 SPECIFIC, AND THE TECHNICAL CODES SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION.
  
 14C) ROOF DRAINAGE CALCULATIONS DO NOT PROVIDE THE RATE
 OF RAINFALL PER HR. THE CHARTS WERE DESIGN FOR.
 P] 1503.4 ROOF DRAINAGE. UNLESS ROOFS ARE SLOPED TO
 DRAIN OVER ROOF EDGES, DESIGN AND INSTALLATION OF ROOF
 DRAINAGE SYSTEMS SHALL COMPLY WITH SECTION 1503 AND THE
 FLORIDA BUILDING CODE, PLUMBING, CHAPTER 11.
  
 14D) THE QUESTION IS THE TOP OF ROOF DRAINS IS SHOWN AS
 MINUS INCHES FROM THE TOP OF ROOF, FOR EXAMPLE BOTH
 AREAS OF THE ROOF DESIGNATED AS N & P BOTH SHOW A -7
 INCHES T.O.D. OR -7 INCHES FROM THE TOP OF THE HIGHEST
 ROOF DECK WHERE THE DECK ADJOINS TO THE PARAPET WALL.
 DETAIL 5/ A7.5.1 SHOWS THE EMERGENCY OVERFLOW SET AN
 ADDITIONAL 2 INCHES ABOVE THE 7 INCHES TOP OF DRAIN OR
 9 INCHES OF DEPTH OF WATER BEFORE WATER CAN START TO
 OVERFLOW THE EMERGENCY ROOF SCUPPERS. IN ROOF ZONE P,
 THIS IS APPROXIMATELY 42,553 LBS. OF WATER WEIGHT.
  
 FBC-B 1503.4.2.1 WHEN LOOKING AT THIS SECTION THE
 INTENT IS WHEN THE ROOF IS SLOPED TO A SCUPPER THE, THE
 SCUPPER SHALL BE PLACED LEVEL (1503.4.2) TO THE ROOF
 DECK. THE EMERGENCY OVERFLOW SCUPPERS ARE TO BE PLACED
 2 -4 INCHES ABOVE THE SCUPPER. THIS IS A COMMON MISTAKE
 WHEN APPLYING 1503.4.1 SECONDARY DRAINAGE REQUIRED. IF
 THE ROOF DRAINS ARE TO BE THE PRIMARY DRAIN THEN
 SHOULDN?T THE EMERGENCY OVERFLOW SCUPPERS BE PLACED 2
 TO 4 INCHES ABOVE THE DRAIN? IF USING A SECONDARY ROOF
 DRAIN THAT IS HOW IT WOULD BE SET UP 2 TO 4 INCHES
 ABOVE THE ROOF DRAIN.
  
 14E) THE PLANS INDICATE THE USE OF PRE-ENGINEERED A/C
 STANDS. WHEN FIGURING THE REQUIRED CLEARANCES IN HEIGHT
 REQUIRED BY TABLE FBC-B 1509.7, THE CLEARANCE IS FROM
 THE FINISHED ROOF HEIGHT, ABOVE THE LIGHTWEIGHT
 CONCRETE ROOF.
  
 15) THIS IS MORE OF A CONCERN FOR THE FIRE DEPARTMENT
 AS TO HOW THE FIRE DEPARTMENT WILL BE ABLE TO GAIN
 ENTRY WHEN THE TILT GATES TO THE GARAGE ARE DOWN? WILL
 THE GARAGE TILT GATES BE ON EMERGENCY POWER CIRCUITRY?
 IN THE EVENT OF GATE FAILING TO OPEN HOW WILL EGRESS TO
 MAINTAINED ? 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED?
  
 16) PAGES 126 A7-1-1, 127 A7-2-1, 129 A7-3-1, 130
 A7-3-2, 131 A7-3-3 & 132 A7-4-1. ALL OF THESE SHEETS
 DEAL WITH THE EXTERIOR OF THE BUILDING AND WITH
 COMPONENTS & CLADDING.
  
 16A) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 16B) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC
  
 16C) IF EITHER THE CONTRACTOR OR DESIGNER OF RECORD
 WISH TO DEFER THE PRODUCT APPROVALS UNTIL AFTER PERMIT
 ISSUANCE PLEASE INFORM SO IN WRITING.
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION. 107.3.4.3
 CERTIFICATIONS BY CONTRACTORS AUTHORIZED UNDER THE
 PROVISIONS OF SECTION 489.115 FLORIDA STATUTES, SHALL
 BE CONSIDERED EQUIVALENT TO SEALED PLANS AND
 SPECIFICATIONS BY A PERSON LICENSED UNDER CHAPTER 471,
 FLORIDA STATUTES, OR CHAPTER 481 FLORIDA STATUTES, BY
 LOCAL ENFORCEMENT AGENCIES FOR PLANS REVIEW FOR
 PERMITTING PURPOSES RELATING TO COMPLIANCE WITH THE
 WIND-RESISTANCE PROVISIONS OF THE CODE OR ALTERNATE
 METHODOLOGIES APPROVED BY THE FLORIDA BUILDING
 COMMISSION FOR ONE AND TWO-FAMILY DWELLINGS. LOCAL
 ENFORCEMENT AGENCIES MAY RELY UPON SUCH CERTIFICATION
 BY CONTRACTORS THAT THE PLANS AND SPECIFICATIONS
 SUBMITTED CONFORM TO THE REQUIREMENTS OF THE CODE FOR
 WIND RESISTANCE. UPON GOOD CAUSE SHOWN, LOCAL
 GOVERNMENT CODE ENFORCEMENT AGENCIES MAY ACCEPT OR
 REJECT PLANS SEALED BY PERSONS LICENSED UNDER CHAPTERS
 471,481 OR 489, FLORIDA STATUTES.
  
 17) PAGES 163 S1.13 AND 164 S1.14. NOTE # 1 ON THESE
 SHEETS INDICATE THE PRESSURES WERE CALCULATED USING THE
 CALCULATED BY CODE ANALYTICAL METHODS. THIS TERM
 ANALYTICAL METHOD DOES NOT SHOW UP IN THE CODE WHEN A
 WORD SEARCH IS COMPLETED. IT WOULD APPEAR THAT A WIND
 TUNNEL TEST WAS COMPLETED AS ALLOWED BY FBC-B 1609.1.1
 EXCEPTION 6. WIND TUNNEL TEST ARE TO BE IN ACCORDANCE
 WITH CHAPTER 31 OF ASCE 7. PLEASE PROVIDE THE SIGNED
 AND SEALED WIND TUNNEL TEST OR PROVIDE HOW THESE
 PRESSURES WERE DERIVED.
  
 18) PAGE 165 THE FOUNDATION PLAN SHOWS ALL PILE CAP
 DIRECTLY ON THE PROPERTY LINE. A REVISION MAY BE
 REQUIRED. THE SOILS REPORT INDICATES THAT THIS SITE HAS
 LOOSE SOILS AND BECAUSE OF THE CLOSENESS OF OTHER
 BUILDINGS AROUND THE SITE, VIBROFLOTATION WAS NOT
 RECOMMENDED AND AUGERED CAST PILES CAST IN PLACE SHOULD
 BE USED TO SUPPORT THE STRUCTURE. THE SOILS REPORT WENT
 IN DEPTH OF HOW THE UTILITIES IN THE ALLEY WOULD NEED
 TO BE SUPPORTED AND HOW TO COMPLETE THIS TASK.
  
 LAST WEEK (MAY 12/2015) IN A MEETING WITH MATT STILL
 THE PROJECT MANAGER , MATT SPOKE ABOUT THE POSSIBLE USE
 OF SHEET PILING AROUND THE PERIMETER OF THE PROJECT.
 THIS WILL HAVE THE SAME EFFECT AS VIBROFLOTATION AS TO
 DAMAGE TO STRUCTURES IN THE VICINITY OF THE PROJECT. A
 RESOLUTION ON THIS MATTER WILL NEED TO TAKE PLACE IF
 SHEET PILE ARE GOING TO BE INSTALLED AROUND THE
 PERIMETER, THIS WILL AFFECT THE PLACEMENT OF THE PILE
 AND PILE CAPS.
  
 19) PAGE A7.5.3 ;
 19A) NOTE: THE POOL TRELLIS STRUCTURE (PERGOLA) THIS
 DETAIL INDICATES IT IS GOING TO BE DESIGNED BY A
 SPECIALTY ENGINEER. BEFORE SUBMITTAL TO THE BUILDING
 DEPARTMENT, THE PLANS WILL NEED TO BE REVIEWED BY THE
 ENGINEER OF RECORD. FL 61G-15-30.006 (3) THE DELEGATED
 ENGINEER SHALL FORWARD THE DELEGATED ENGINEERING
 DOCUMENTS TO THE ENGINEER OF RECORD FOR REVIEW.
  
 19B) THE POOL TRELLIS STRUCTURE (PERGOLA) THIS
 STRUCTURE INDICATES THE USE OF A PLEXIGLASS RAIN GUARD.
 PLEASE PROVIDE HOW THE PLEXIGLASS RAIN GUARD WILL MEET
 THE FIRE RESISTANCE RATINGS REQUIRED BY FBC-B TABLE 601
 AND FBC-B TABLE 1505.1.ALSO SEE FBC-B 2610 2610.4. WILL
 THERE BE FIRE SPRINKLERS BENEATH THIS STRUCTURE.
  
 20) PAGE 136 A7.5.4.
 20A) DETAIL # 5 RIGID ALUMINUM CANOPY WITH FABRIC
 WRAPPED WILL REQUIRE WIND DESIGN CRITERIA SEE OPTIONS
 FOUND UNDER FBC-B 3105.4 . ALSO: FL 61G-15-30.006 (3)
 THE DELEGATED ENGINEER SHALL FORWARD THE DELEGATED
 ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR
 REVIEW.
  
 20B) DETAIL # 5 RIGID ALUMINUM CANOPY WITH FABRIC
 WRAPPED WILL NEED TO MEET THE REQUIREMENTS OF 3105.3.1
 FABRIC USED FOR AWNINGS OR FABRIC-COVERED FRAMES SHALL
 MEET THE FLAME PROPAGATION PERFORMANCE CRITERIA OF NFPA
 701.
  
 21) PAGE 137 A7.5.5 DETAIL # 10 THE BALCONY EDGE
 ALUMINUM RAILING DOES NOT HAVE THE DESIGN CRITERIA THAT
 WILL BE REQUIRED TO MANUFACTURER, THE BALCONY RAIL WILL
 NEED TO MEET THE FOLLOWING :
 FBC-B 1607.7.1.1 CONCENTRATED LOAD & . 1607.7.1.2
 COMPONENTS.
  
 22) PAGE 139 A9.1.1 STAIRWELL NUMBER 1 DOES NOT SHOW
 THE STANDPIPE IN THE STAIRWELL NOR ARE THERE ANY NOTES
 ONE IS REQUIRED. FBC-B 905.3.1. THIS COMMENT STAND FOR
 ALL STAIRWELLS. PLEASE NOTE THE ONLY PENETRATIONS
 ALLOWED IN THE STAIRWELL ARE TOUGHS THAT COMPLY WITH:
  
 FBC-B 1022.4 PENETRATIONS. PENETRATIONS INTO AND
 OPENINGS THROUGH AN EXIT ENCLOSURE ARE PROHIBITED
 EXCEPT FOR REQUIRED EXIT DOORS, EQUIPMENT AND DUCTWORK
 NECESSARY FOR INDEPENDENT VENTILATION OR
 PRESSURIZATION, SPRINKLER PIPING, STANDPIPES,
 ELECTRICAL RACEWAY FOR FIRE DEPARTMENT COMMUNICATION
 SYSTEMS AND ELECTRICAL RACEWAY SERVING THE EXIT
 ENCLOSURE AND TERMINATING AT A STEEL BOX NOT EXCEEDING
 16 SQUARE INCHES (0.010 M2). SUCH PENETRATIONS SHALL BE
 PROTECTED IN ACCORDANCE WITH SECTION 713. THERE SHALL
 BE NO PENETRATIONS OR COMMUNICATION OPENINGS, WHETHER
 PROTECTED OR NOT, BETWEEN ADJACENT EXIT ENCLOSURES.
  
 23) PAGE 153 A11.2:
 23A) DETAIL # 1 THE TRASH TERMINATION ROOM, SHOW A
 STAINLESS STEEL ROLLING FIRE DOOR WITH 165 DEGREE
 FUSIBLE LINK, THE PLANS DO NOT INDICATE WHAT THE FIRE
 DOOR IS RATED TOO? FBC-B TABLE 715.4.
  
 23B) THE THROUGH THE FLOOR FIRE PROOFING DETAIL
 INDICATE THE USE OF MINERAL WOOL INSULATION PLEASE
 PROVIDE A LISTED ASSEMBLY FOR A 2?-0? DIAMETER STEEL
 TRASH CHUTE, NOT FOUND ON THE UL ASSEMBLY SHEET. FBC-B
 713.4.1.1 THROUGH PENETRATIONS.
 THROUGH PENETRATIONS OF FIRE-RESISTANCE-RATED
 HORIZONTAL ASSEMBLIES SHALL COMPLY WITH SECTION
 713.4.1.1.1 OR 713.4.1.1.2.
  
 23C) THROUGH PENETRATION OF FLOOR SLAB FOR TUB DRAIN IF
 TRAP IS WITHIN THE FLOOR ASSEMBLY IS NOT PROVIDED ON
 THE UL ASSEMBLY SHEETS NOR P5.1.2. THROUGH PENETRATIONS
 OF FIRE-RESISTANCE-RATED HORIZONTAL ASSEMBLIES SHALL
 COMPLY WITH SECTION 713.4.1.1.1 OR 713.4.1.1.2.
 24) PLEASE PROVIDE WHERE THE FOLLOWING REQUIREMENTS FOR
 HIGH RISE CONSTRUCTION CAN BE FOUND:
 24A)FBC-B 403.3.2 WATER SUPPLY TO REQUIRED FIRE PUMPS.
 REQUIRED FIRE PUMPS SHALL BE SUPPLIED BY CONNECTIONS TO
 A MINIMUM OF TWO WATER MAINS LOCATED IN DIFFERENT
 STREETS. SEPARATE SUPPLY PIPING SHALL BE PROVIDED
 BETWEEN EACH CONNECTION TO THE WATER MAIN AND THE
 PUMPS. EACH CONNECTION AND THE SUPPLY PIPING BETWEEN
 THE CONNECTION AND THE PUMPS SHALL BE SIZED TO SUPPLY
 THE FLOW AND PRESSURE REQUIRED FOR THE PUMPS TO
 OPERATE.
  
 24B) FBC-B [F] 403.4.3 EMERGENCY VOICE/ALARM
 COMMUNICATION SYSTEM.
 AN EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM SHALL BE
 PROVIDED IN ACCORDANCE WITH SECTION 907.5.2.2.
  
 24C) FBC-B [F] 403.4.4 EMERGENCY RESPONDER RADIO
 COVERAGE.
 EMERGENCY RESPONDER RADIO COVERAGE SHALL BE PROVIDED IN
 ACCORDANCE WITH THE FLORIDA FIRE PREVENTION CODE.
  
 24D) FBC-B 403.4.6 SMOKE REMOVAL. SMOKE CONTROL SHALL
 BE PROVIDED IN ACCORDANCE WITH SECTION 909.
  
  
 24E) FBC-B [F] 403.4.7 STANDBY POWER.
 A STANDBY POWER SYSTEM COMPLYING WITH CHAPTER 27 SHALL
 BE PROVIDED FOR STANDBY POWER LOADS SPECIFIED IN
 SECTION 403.4.7.2.
  
 24F) FBC-B [F] 403.4.7.2 STANDBY POWER LOADS.
 THE FOLLOWING ARE CLASSIFIED AS STANDBY POWER LOADS:
 1. POWER AND LIGHTING FOR THE FIRE COMMAND CENTER
 REQUIRED BY SECTION 403.4.5;
 2. VENTILATION AND AUTOMATIC FIRE DETECTION EQUIPMENT
 FOR SMOKEPROOF ENCLOSURES; AND
 3. STANDBY POWER SHALL BE PROVIDED FOR ELEVATORS IN
 ACCORDANCE WITH SECTIONS 1006.2.4, 3003, 3007 AND 3008.
  
 24G) [F] 403.4.8 EMERGENCY POWER SYSTEMS. AN EMERGENCY
 POWER SYSTEM COMPLYING WITH CHAPTER 27 SHALL BE
 PROVIDED FOR EMERGENCY POWER LOADS SPECIFIED IN SECTION
 403.4.8.1.
 [F] 403.4.8.1 EMERGENCY POWER LOADS.
 THE FOLLOWING ARE CLASSIFIED AS EMERGENCY POWER LOADS:
 1. EXIT SIGNS AND MEANS OF EGRESS ILLUMINATION REQUIRED
 BY CHAPTER 10;
 2. ELEVATOR CAR LIGHTING;
 3. EMERGENCY VOICE/ALARM COMMUNICATIONS SYSTEMS;
 4. AUTOMATIC FIRE DETECTION SYSTEMS;
 5. FIRE ALARM SYSTEMS; AND
 6. ELECTRICALLY POWERED FIRE PUMPS.
  
  
 24H) FBC-B 403.5.3.1 STAIRWAY COMMUNICATION SYSTEM.
 A TELEPHONE OR OTHER TWO-WAY COMMUNICATIONS SYSTEM
 CONNECTED TO AN APPROVED CONSTANTLY ATTENDED STATION
 SHALL BE PROVIDED AT NOT LESS THAN EVERY FIFTH FLOOR IN
 EACH STAIRWAY WHERE THE DOORS TO THE STAIRWAY ARE
 LOCKED.
  
 24I) FBC-B 403.5.4 SMOKEPROOF EXIT ENCLOSURES. EVERY
 REQUIRED EXIT STAIRWAY SERVING FLOORS MORE THAN 75 FEET
 (22 860 MM) ABOVE THE LOWEST LEVEL OF FIRE DEPARTMENT
 VEHICLE ACCESS SHALL COMPLY WITH SECTIONS 909.20 AND
 1022.9.
 24J) FBC-B 1022.8 FLOOR IDENTIFICATION SIGNS. /
 1022.8.1 SIGNAGE REQUIREMENTS.
  
 24K) FBC-B 403.5.5 LUMINOUS EGRESS PATH MARKINGS.
 LUMINOUS EGRESS PATH MARKINGS SHALL BE PROVIDED IN
 ACCORDANCE WITH SECTION 1024.1-5.
 1024.4 SELF-LUMINOUS AND PHOTOLUMINESCENT. LUMINOUS
 EGRESS PATH MARKINGS SHALL BE PERMITTED TO BE MADE OF
 ANY MATERIAL, INCLUDING PAINT, PROVIDED THAT AN
 ELECTRICAL CHARGE IS NOT REQUIRED TO MAINTAIN THE
 REQUIRED LUMINANCE. SUCH MATERIALS SHALL INCLUDE, BUT
 ARE NOT LIMITED TO, SELF-LUMINOUS MATERIALS AND
 PHOTOLUMINESCENT MATERIALS. MATERIALS SHALL COMPLY WITH
 EITHER:
 1. UL 1994; OR
 2. ASTM E 2072, EXCEPT THAT THE CHARGING SOURCE SHALL
 BE 1 FOOTCANDLE (11 LUX) OF FLUORESCENT ILLUMINATION
 FOR 60 MINUTES, AND THE MINIMUM LUMINANCE SHALL BE 30
 MILLICANDELAS PER SQUARE METER AT 10 MINUTES AND 5
 MILLICANDELAS PER SQUARE METER AFTER 90 MINUTES.
  
 1024.5 ILLUMINATION.EXIT ENCLOSURES WHERE
 PHOTOLUMINESCENT EXIT PATH MARKINGS ARE INSTALLED SHALL
 BE PROVIDED WITH THE MINIMUM MEANS OF EGRESS
 ILLUMINATION REQUIRED BY SECTION 1006 FOR AT LEAST 60
 MINUTES PRIOR TO PERIODS WHEN THE BUILDING IS OCCUPIED.
  
 25) [F] 3311.1 WHERE REQUIRED. IN BUILDINGS REQUIRED TO
 HAVE STANDPIPES BY SECTION 905.3.1, NOT LESS THAN ONE
 STANDPIPE SHALL BE PROVIDED FOR USE DURING
 CONSTRUCTION. SUCH STANDPIPES SHALL BE INSTALLED WHEN
 THE PROGRESS OF CONSTRUCTION IS NOT MORE THAN 40 FEET
 (12 192 MM) IN HEIGHT ABOVE THE LOWEST LEVEL OF FIRE
 DEPARTMENT VEHICLE ACCESS. SUCH STANDPIPE SHALL BE
 PROVIDED WITH FIRE DEPARTMENT HOSE CONNECTIONS AT
 ACCESSIBLE LOCATIONS ADJACENT TO USABLE STAIRS. SUCH
 STANDPIPES SHALL BE EXTENDED AS CONSTRUCTION PROGRESSES
 TO WITHIN ONE FLOOR OF THE HIGHEST POINT OF
 CONSTRUCTION HAVING SECURED DECKING OR FLOORING.
  
 26) [F] 3312.1 COMPLETION BEFORE OCCUPANCY.
 IN BUILDINGS WHERE AN AUTOMATIC SPRINKLER SYSTEM IS
 REQUIRED BY THIS CODE, IT SHALL BE UNLAWFUL TO OCCUPY
 ANY PORTION OF A BUILDING OR STRUCTURE UNTIL THE
 AUTOMATIC SPRINKLER SYSTEM INSTALLATION HAS BEEN TESTED
 AND APPROVED, EXCEPT AS PROVIDED IN SECTION 111.3.
  
 27) 109.3.10* IMPACT OF CONSTRUCTION. ALL CONSTRUCTION
 ACTIVITY REGULATED BY THIS CODE SHALL BE PERFORMED IN A
 MANNER SO AS NOT TO ADVERSELY IMPACT THE CONDITION OF
 ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS PERMITTED TO
 AFFECT SAID PROPERTY PURSUANT TO A CONSENT BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS & CONDITIONS
 AGREEABLE TO THE APPLICABLE PROPERTY OWNER. THIS
 INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF DUST,
 NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE
 STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE
 WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY
 REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY,
 DEVELOPERS, CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ
 FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATION FROM A LICENSED ENGINEER SHALL BE
 SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL
 OF THE FINAL INSPECTION.
  
 28) 109.3.10.1 HURRICANE PROTECTION. IT SHALL BE
 UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION RELATED
 MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24 HRS.
 AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE
 EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN
 SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY
 PERSONS WHO FAILS TO COMPLY TO REMOVE OR SECURE THE
 CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS WITHIN 24
 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE
 SUBJECT TO A FINE NOT TO EXCEED $500.00. IN ADDITION TO
 THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS
 SECTION SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO
 SECTION 113 OF THIS CHAPTER.
  
  
 29) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 30) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2016-02-02 Cont ID  
Sent By albarran Date 2016-02-02 Time 19:47 Rev Time 0.00
Received By albarran Date 2016-02-02 Time 18:54 Sent To  
Notes
2016-02-02 19:48:25ALL PREVIOUSLY MENTIONED DEFICIENCIES WERE
 SATISFACTORILY ADDRESSED.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2015-12-02 Cont ID  
Sent By albarran Date 2015-12-02 Time 18:50 Rev Time 0.00
Received By albarran Date 2015-12-01 Time 18:11 Sent To  
Notes
2015-12-02 18:52:23PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE SECOND ELECTRICAL REVIEW OF
 THE ABOVE MENTIONED JOB. BELOW ARE THE COMMENTS WITH
 REGARDS TO THE REQUIRED CORRECTIONS. THE PLANS SHALL BE
 REVISED TO ADDRESS FOLLOWING ITEMS; ONCE CORRECTED
 SHALL BE RESUBMITTED FOR ANOTHER REVIEW.
 PG. E2.1.1
 1. REAR MAIN LOBBY DOOR INTO VEHICULAR AREA MAY BE
 MISSING AN EXIT LIGHT.
 2. NO EXIT LIGHTS IN THE VEHICULAR AREA.
 3. EXIT LIGHT MISSING AT DOOR IN ROOM 136 TO PARKING
 AREA.
 4. NEC 408.4(B) SHOW LOCATION OF SOURCE OF POWER AND
 DISCONNECT. ALL SWITCHBOARDS SHALL BE MARKED TO
 INDICATE ORIGIN OF POWER.
 PG. E2.2.1
 1. FBC-B SECTION 1011.1 EXIT SIGN PLACEMENT SHALL BE
 SUCH THAT THERE IS NO MORE THAN 100 FT. BETWEEN SIGNS.
 2. BIKE STG. ROOM 209 MISSING AUTOMATIC LIGHTING
 CONTROL
 PG. E2.3.1, E2.4.1, E2.5.1, E2.6.1
 1. FBC-B SECTION 1011.1 EXIT SIGN [PLACEMENT SHALL BE
 SUCH THAT THERE IS NO MORE THAN 100 FT. BETWEEN SIGNS.
 PG. E2.7.1
 1. NEC 406.8(B) ALL 15 AND 20 AMP 125 TO 250 VOLT
 NON-LOCKING RECEPTACLES INSTALLED IN WET LOCATIONS
 SHALL BE RATED WEATHER RESISTANT ?WR?. (TYPICAL FOR ALL
 OUTDOOR RECEPTACLES).
 2. RELOCATE THIS TOWARDS CORNER TO MAKE IT VISIBLE FROM
 BOTH DIRECTIONS AND TO POINT TOWARDS THE ACTUAL EXIT.
 PG. E2.8.1
 1. RELOCATE THIS TOWARDS CORNER TO MAKE IT VISIBLE FROM
 BOTH DIRECTIONS AND TO POINT TOWARDS THE ACTUAL EXIT.
 PG. E2.9.1
 1. ADDITIONAL NOTE TO BE ADDED #7: NEC 406.8(B) ALL 15
 AND 20 AMP 125 TO 250 VOLT NON-LOCKING RECEPTACLES
 INSTALLED IN WET LOCATIONS SHALL BE RATED WEATHER
 RESISTANT ?WR?. (TYPICAL FOR ALL OUTDOOR RECEPTACLES).
 PG. E2.10.1
 1. SHOW PANEL ?REL? ON RISER DIAGRAM AND PANEL
 SCHEDULES.
 PG. E4.1.1
 1. FOLLOWING THE LOADS FROM BOTH, SWITCHBOARDS 1 & 2,
 THERE ARE SEVERAL PANELS WHICH DO NOT APPEAR ON THE
 RISER DIAGRAM.
 PG. E4.3.1
 1. THE POWER SOURCE FOR PANEL ?RB? IS NOT IDENTIFIED,
 OR REFLECTED ON THE RISER DIAGRAM.
 PG. E5.1.1
 1. CIRCUIT DIRECTORY/PANEL SCHEDULE FOR PANEL ?RLB? IN
 NOT INDICATED AMONG THE PANEL SCHEDULES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU
 MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH.
 PH. :(561) 805-6746

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-10-01 Cont ID  
Sent By albarran Date 2015-10-01 Time 20:12 Rev Time 0.00
Received By albarran Date 2015-09-30 Time 14:40 Sent To  
Notes
2015-10-01 20:13:37PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE SECOND ELECTRICAL REVIEW OF
 THE ABOVE MENTIONED JOB. BELOW ARE THE COMMENTS WITH
 REGARDS TO THE REQUIRED CORRECTIONS. THE PLANS SHALL BE
 REVISED TO ADDRESS FOLLOWING ITEMS; ONCE CORRECTED
 SHALL BE RESUBMITTED FOR ANOTHER REVIEW.
  
 1. THESE BEING RENTAL UNITS, THE CORRIDOR OUTLETS ARE
 UNDER THE HOUSE LOAD AND THUS WILL NOT PLACE A BURDEN
 ON ANOTHER TENANT. (RENTAL OR PRIVATE OWNERSHIP OF
 THESE UNITS HAD NOT BEEN MADE KNOW BEFORE)
 2. NEC REQUIRES THAT YOU INCLUDE A LAUNDRY CIRCUIT IN
 THE LOAD CALCS. THE OTHER GENERAL PURPOSE OUTLETS WHICH
 MAY BE IN THE LAUNDRY ROOM/AREA FALL UNDER THE GENERAL
 LIGHTING LOADS. THERE IS NOTHING PROHIBITING YOU FROM
 DOING IT THE WAY YOU HAVE, IT IS JUST NOT NECESSARY.
 3. THERE APPEARS NOT TO BE ENOUGH LIGHT TO WORK INSIDE
 THE ELECTRICAL PANEL COMING FROM THE DOWN LIGHTS IN THE
 KITCHEN ISLAND, ON PG. E3.8.1, PG. E3.9.1, PG. E3.9.1A
 4. PG. E3.16 CLUB HOUSE: MISSING CONVENIENCE GFI
 OUTLETS AT ISLAND COUNTER.
 5. PG. E3.16 CLUB HOUSE: PER NEC 422.52 ELECTRIC
 DRINKING FOUNTAINS SHALL BE ON A GFI PROTECTED CIRCUIT.
 6. PG. E3.16 CLUB HOUSE: INDICATE WHICH SIDE THE PANEL
 WILL FACE. PER NEC 210.70(3) THERE HAS TO BE AMPLE
 LIGHTING ABOUT THE ELECTRICAL PANEL.
 7. PG. E3.16 CLUB HOUSE: I DON?T SEE THE MANDATORY
 ADDITIONAL CONTROLS (OCCUPANCY SENSORS) REQUIRED BY THE
 FBC-ENERGY FOR THIS AREA.
 8. (CHECK THE EXIT DOOR BY THE RESTROOMS FOR THE PROPER
 SWING IN THE PATH OF TRAVEL.)
 9. PG. E4.1.1 PANEL G HAS A CALCULATED LOAD OF 156 AMP
 WITHOUT TAKING 125% FOR THE CONTINUOUS LOADS INTO
 ACCOUNT; #4 THWN AL IS ONLY GOOD FOR 150 AMP.
 10. PG. E4.2.1 PANEL MEL HAS A LOAD OF 11.6 AMP NOT
 8.8.
 11. PG. E4.3.1 PANEL RL HAS A CONNECTED LOAD OF 820 AMP
 ACCORDING TO YOU NUMBERS, HAVE YOU CONSIDERED THE
 CONTINUOUS LOADS AS THE FEEDERS ARE EXACT.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-05-28 Cont ID  
Sent By albarran Date 2015-05-28 Time 16:33 Rev Time 0.00
Received By albarran Date 2015-05-12 Time 09:06 Sent To  
Notes
2015-05-28 16:34:56THE ELECTRICAL REVIEW FAILED AS INDICATED ON THE
 ATTACHED DOCUMENT. A COPY OF MY NOTES HAS BEEN EMAILED
 TO DESIGN PROFESSIONAL AS WELL.
 PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE CORRECTIONS NOTED. AS THIS WAS A PAGE BY PAGE
 REVIEW, YOU WILL NOTICE REPEATED COMMENTS ON EACH
 RESPECTIVE PAGE. EACH OF THE COMMENTS NOTED HAVE BEEN
 CLOUDED OR IN SOME WAY IDENTIFIED IN A RED LAYER ON THE
 DIGITAL PLANS.
  
 PAGE E1.0.0 LEGEND & NOTES
 1. LIGHTING FIXTURE NOTES: CORRECT NOTE 1 TO INDICATE
 THE PROPER CODE SECTION ADDRESSING LUMINAIRE SUPPORT.
 2. GENERAL NOTES: CORRECT NOTE 10 TO COMPLY WITH
 CURRENT FBC REQUIREMENTS FOR FIRE SEALING AS NOTED.
 3. OUTDOOR & LANDSCAPE NOTES: CORRECT NOTE 4 TO INCLUDE
 THE REQUIREMENT OF NEC 406.8 (B)
 4. A NOTE REQUIRING COMPLIANCE WITH NEC 406.11
 TAMPER-RESISTANT RECEPTACLES IN DWELLING UNITS. IN ALL
 AREAS SPECIFIED IN 210.52, ALL 125-VOLT, 15 AND
 20-AMPERE RECEPTACLES SHALL BE LISTED TAMPER RESISTANT
 RECEPTACLES.
 5. YOU WILL NOTICE THAT ON EVERY FLOOR I HAVE MADE A
 NOTATION AS TO THE REQUIRED SERVICE OUTLET FOR THE
 INDIVIDUAL UNIT A/C EQUIPMENT IN A CLOSET IN THE COMMON
 CORRIDOR. AS A MATTER OF MY REVIEW, I HAVE MEASURED THE
 DISTANCES OF THE OUTLETS IN THE CORRIDORS AND THEY DO
 COMPLY WITH THIS REQUIREMENT BUT WILL THE BLDG. ALLOW
 THE INDIVIDUAL UNIT OWNERS TO USE THESE OUTLETS FOR
 THEIR PERSONAL USE? IF SO, A NOTE ADDRESSING THIS SHALL
 BE TO THE DRAWINGS, OTHERWISE AN ACCESSIBLE OUTLET
 POWERED FROM THE UNIT?S ELECTRICAL SERVICE SHALL BE
 INSTALLED INSIDE THE RESPECTIVE CLOSETS FOR THIS
 PURPOSE.
 6. FOR COMPLIANCE W/THE 2010 FBC-ENERGY CONSERVATION
 CODE, THERE ARE LIGHTING REQUIREMENTS THAT ARE NOT
 ADDRESSED ON THE PLANS. SUCH ARE THE GASKET REQUIREMENT
 FOR RECESSED LIGHTING, THE EFFICIENT LIGHTING
 REQUIREMENT, ETC.
  
 PAGE E2.1.1 OVERALL GROUND FLOOR PLAN
 1. IDENTIFY THE EXIT AND EXIT LIGHT IN THE GENERATOR
 ROOM
 2. MISSING THE EXIT LIGHT IN THE DOMESTIC PUMP ROOM.
 3. MISSING EXIT LIGHT FOR FIRE CONTROL ROOM
 4. MISSING EXIT LIGHT FOR TRASH ROOM
 5. MISSING EXIT LIGHT FOR VESTIBULE 116 B
 6. MISSING EXIT FOR STAIR 5 & STAIR 1
 7. MISSING EXIT LIGHT OUTSIDE OF MAINTENANCE OFFICE
 8. MISSING EXIT LIGHTS IN WORKROOM CLOUD AREA.
  
 THIS PAGE IS CO CLUTTERED THAT I MAY HAVE MISSED
 ADDITIONAL EXIT LIGHT REQUIREMENTS. PLEASE GO OVER THE
 DRAWING IN LAYERS TO SIMPLIFY EXIT LIGHT PLACEMENT.
  
 PAGE E2.2.1 OVERALL SECOND FLOOR PLAN
 1. INSTALL AN EXIT LIGHT AS MARKED TO ANNOUNCE STAIR #4
 FROM PARKING AREA.
  
 PAGE E2.3.1 OVERALL 3RD FLOOR & 5TH FLOOR PLAN
 1. BIKE STORAGE ROOM 304 MISSING O/S SENSOR (EXIT IS
 POORLY IDENTIFIED)
  
 PAGE E2.4.1 OVERALL 4TH FLOOR PLAN
 1. THE FOLLOWING ROOMS ARE MISSING THE REQUIRED O/S
 404, 405, 407, 413
  
 PAGE E2.5.1 OVERALL 5TH FLOOR PLAN
 1. BIKE STG. ROOM 504 IS MISSING THE O/S
  
 PAGE E2.6.1 OVERALL 6TH FLOOR PLAN
 1. THE FOLLOWING ROOMS ARE MISSING THE REQUIRED O/S:
 603, 604, 605, 607, 608, 609, 612, & 613
 2. FCU-2 IS MISSING THE REQUIRED LIGHTING PER NEC
 110.26(D)
 3. POOL EQUIPMENT ROOM SHALL INCLUDE THE EQUIPMENT
 BEING INSTALLED TO VERIFY PROPER CLEARANCES.
 4. NEC 680.22 (B) GFCI PROTECTIONS. OUTLETS SUPPLYING
 POOL PUMP MOTORS 15 OR 20 AMPERES, 125 VOLT OR 240
 VOLT, SINGLE PHASE, WHETHER BY RECEPTACLE OR DIRECT
 CONNECTION, SHALL BE PROVIDED WITH GROUND-FAULT
 CIRCUIT-INTERRUPTER PROTECTION FOR PERSONNEL. IF THE
 POOL HEATERS ARE TO BE STAND-ALONE, MEANING THAT THEY
 DO NOT DEPEND ON THE POOL CIRCULATING PUMPS FOR WATER
 CIRCULATION, THEY TOO SHALL BE GFCI PROTECTED.
  
 PAGE E2.7.1 OVERALL 7TH FLOOR PLAN
 1. PER NOTES, POOL IS TO BE ON SEPARATE PERMIT THUS NO
 NOTES ADDRESSING POOL.
  
 PAGE E2.8.1 OVERALL TYPICAL 8TH ? 20TH FLOOR PLAN
 1. RELOCATE EXITS SIGNS SO AS NOT TO CONFUSE
 PEDESTRIANS INTO WRONG DOORWAY.
  
 PAGE E3.1.1, UNITS 301/501
 1. 110.26(D) ILLUMINATION. ILLUMINATION SHALL BE
 PROVIDED FOR ALL WORKING SPACES ABOUT SERVICE
 EQUIPMENT, SWITCHBOARDS, AND PANELBOARDS. THERE SHALL
 BE PROPER ILLUMINATION ABOUT THE ELECTRICAL PANEL.
 2. NEC 210.52 (A)(1) SPACING. RECEPTACLES SHALL BE
 INSTALLED SUCH THAT NO POINT MEASURED HORIZONTALLY
 ALONG THE FLOOR LINE IN ANY WALL SPACE IS MORE THAN 6
 FT. FROM A RECEPTACLE OUTLET. THIS OCCURS THROUGH THE
 UNITS IN MULTIPLE LOCATIONS.
 3. NEC 210.52 (A)(2) WALL SPACE. REQUIRES AN OUTLET ON
 EVERY WALL GREATER THAN 2?. SEE CLOUDS ON THE LIVING
 ROOM AND FOYER AND CORRECT ACCORDINGLY.
 4. NEC 210.52 (C)(3) PENINSULAR COUNTERTOP SPACES.
 REQUIRES AT LEAST ONE RECEPTACLE AT EACH PENINSULA
 COUNTERTOP. THIS IS A COMMON ISSUE OCCURRING IN MOST
 ALL KITCHEN PENINSULAS, SEE CLOUDS.
 5. NEC 210.63 HVAC EQUIPMENT OUTLET. REQUIRES THAT
 THERE BE A SERVICE OUTLET WITHIN 25? OF THE EQUIPMENT
 BEING SERVICED. YOU WILL NOTICE THIS FOR MOST EVERY
 UNIT, SINCE THE HVAC EQUIPMENT IS IN THE CORRIDOR
 OUTSIDE THE UNIT. SEE MY NOTE 5 OF THE LEGEND & NOTES
 PAGE.
 6. NEC 210.70(A)(3) STORAGE OR EQUIPMENT SPACES. AT
 LEAST ONE LIGHTING OUTLET CONTAINING A SWITCH OR
 CONTROLLED BY A WALL SWITCH SHALL BE INSTALLED WHERE
 THESE SPACES ARE USED FOR STORAGE OR CONTAIN EQUIPMENT
 REQUIRING SERVICING. THE LIGHTING OUTLET SHALL BE
 PROVIDED AT OR NEAR THE EQUIPMENT REQUIRING SERVICING.
 THE CLOSET IN WHICH THE TV & TELEPHONE BOX/CABINET IS
 IN SHALL HAVE THE REQUIRED LIGHTING.
 7. NEC 314.27(A) LUMINAIRE OUTLETS. BOXES USED AT
 LUMINAIRE OR LAMP HOLDER OUTLETS IN A CEILING SHALL BE
 REQUIRED TO SUPPORT A LUMINAIRE WEIGHING A MINIMUM OF
 50 LB. ADD THIS TO THE NOTES ON CEILING BOXES ON PAGE
  
 PAGE E3.1.1, UNITS 302/502
 1. NEC 210.52 (A)(1) SPACING. RECEPTACLES SHALL BE
 INSTALLED SUCH THAT NO POINT MEASURED HORIZONTALLY
 ALONG THE FLOOR LINE IN ANY WALL SPACE IS MORE THAN 6
 FT. FROM A RECEPTACLE OUTLET. THIS OCCURS THROUGH THE
 UNITS IN MULTIPLE LOCATIONS
 2. 210.52(C)(1) WALL COUNTERTOP SPACES. A RECEPTACLE
 OUTLET SHALL BE INSTALLED AT EACH WALL COUNTERTOP SPACE
 THAT IS 12 IN. OR WIDER. RECEPTACLE OUTLETS SHALL BE
 INSTALLED SO THAT NO POINT ALONG THE WALL LINE IS MORE
 THAN 24 IN. MEASURED HORIZONTALLY FROM A RECEPTACLE
 OUTLET IN THAT SPACE.
 3. NEC 210.63 HVAC EQUIPMENT OUTLET. REQUIRES THAT
 THERE BE A SERVICE OUTLET WITHIN 25? OF THE EQUIPMENT
 BEING SERVICED. YOU WILL NOTICE THIS FOR MOST EVERY
 UNIT, SINCE THE HVAC EQUIPMENT IS IN THE CORRIDOR
 OUTSIDE THE UNIT. SEE MY NOTE 5 OF THE LEGEND & NOTES
 PAGE.
 4. NEC 210.70(A)(3) STORAGE OR EQUIPMENT SPACES. AT
 LEAST ONE LIGHTING OUTLET CONTAINING A SWITCH OR
 CONTROLLED BY A WALL SWITCH SHALL BE INSTALLED WHERE
 THESE SPACES ARE USED FOR STORAGE OR CONTAIN EQUIPMENT
 REQUIRING SERVICING. THE LIGHTING OUTLET SHALL BE
 PROVIDED AT OR NEAR THE EQUIPMENT REQUIRING SERVICING.
 THE CLOSET IN WHICH THE TV & TELEPHONE BOX/CABINET IS
 IN SHALL HAVE THE REQUIRED LIGHTING
  
 PAGE E3.1.1A UNITS 301/501 & 302/502 PANEL SCHEDULES
 1. IN THE PROCESS OF MY ELECTRICAL PLAN REVIEW I TRIED
 TO VERIFY YOUR LOAD CALCULATIONS FOR COMPLIANCE AND NOT
 ONLY DID I FIND THEM NOT TO BE CORRECT, BUT I TRIED TO
 LOCATE THE QUOTED CODE SECTIONS IN THE 2008 EDITION OF
 THE NEC AND WAS NOT ABLE TO FIND THEM
 2. I DON?T UNDERSTAND WHY YOU ARE COUNTING A LAUNDRY
 CIRCUIT AND LATER ADDING A WASHER LOAD
 3. IN DOING THE LOAD CALCS MYSELF I ARRIVED WITH A
 SMALLER LOAD USING THE STANDARD METHOD.
  
 PAGE E3.2.1, UNITS 303-503 & 304-504
 1. NEC 210.52(C)(1) WALL COUNTERTOP SPACES. A
 RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH WALL
 COUNTERTOP SPACE THAT IS 12 IN. OR WIDER. RECEPTACLE
 OUTLETS SHALL BE INSTALLED SO THAT NO POINT ALONG THE
 WALL LINE IS MORE THAN 24 IN. MEASURED HORIZONTALLY
 FROM A RECEPTACLE OUTLET IN THAT SPACE.
 2. NEC 210.63 HVAC EQUIPMENT SERVICE OUTLET. A
 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED
 RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE
 LOCATION FOR THE SERVICING OF HVAC EQUIPMENT. THE
 RECEPTACLE SHALL BE LOCATED WITHIN 25 FT. OF THE
 EQUIPMENT. SEE MY NOTE 5 ON OF PAGE E1.0.0 LEGEND &
 NOTES
 3. NFPA SECTION 29.8.3.4(6). SMOKE ALARMS AND SMOKE
 DETECTORS SHALL NOT BE INSTALLED WITHIN A 36 IN. (910
 MM) HORIZONTAL PATH FROM A DOOR TO A BATHROOM
 CONTAINING A SHOWER OR TUB UNLESS LISTED FOR
 INSTALLATION IN CLOSE PROXIMITY TO SUCH LOCATIONS.
 RELOCATE THE UNITS ACCORDINGLY
 4. IN THE PROCESS OF MY ELECTRICAL PLAN REVIEW I TRIED
 TO VERIFY YOUR LOAD CALCULATIONS FOR COMPLIANCE AND NOT
 ONLY DID I FIND THEM NOT TO BE CORRECT, BUT I TRIED TO
 LOCATE THE QUOTED CODE SECTIONS IN THE 2008 EDITION OF
 THE NEC AND WAS NOT ABLE TO FIND THEM
 5. I DON?T UNDERSTAND WHY YOU ARE COUNTING A LAUNDRY
 CIRCUIT AND LATER ADDING A WASHER LOAD
 6. IN DOING THE LOAD CALCS MYSELF I ARRIVED WITH A
 SMALLER LOAD USING THE STANDARD METHOD.
  
 PAGE E3.3.1, UNITS 305-505
 1. NEC 110.26(D) ILLUMINATION. ILLUMINATION SHALL BE
 PROVIDED FOR ALL WORKING SPACES ABOUT SERVICE
 EQUIPMENT, SWITCHBOARDS, AND PANELBOARDS. THERE SHALL
 BE PROPER ILLUMINATION ABOUT THE ELECTRICAL PANEL.
 2. NEC 210.52 (A)(1) SPACING. RECEPTACLES SHALL BE
 INSTALLED SUCH THAT NO POINT MEASURED HORIZONTALLY
 ALONG THE FLOOR LINE IN ANY WALL SPACE IS MORE THAN 6
 FT. FROM A RECEPTACLE OUTLET. THIS INCLUDES THE
 DISTANCE FROM THE EDGE OF THE WALL. SEE CLOUDED AREA IN
 KITCHEN
 3. NEC 210.52(C)(1) WALL COUNTERTOP SPACES. A
 RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH WALL
 COUNTERTOP SPACE THAT IS 12 IN. OR WIDER. RECEPTACLE
 OUTLETS SHALL BE INSTALLED SO THAT NO POINT ALONG THE
 WALL LINE IS MORE THAN 24 IN. MEASURED HORIZONTALLY
 FROM A RECEPTACLE OUTLET IN THAT SPACE. SEE CLOUDED
 AREA AND CORRECT ACCORDINGLY.
 4. NEC 210.63 HVAC EQUIPMENT SERVICE OUTLET. A
 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED
 RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE
 LOCATION FOR THE SERVICING OF HVAC EQUIPMENT. THE
 RECEPTACLE SHALL BE LOCATED WITHIN 25 FT. OF THE
 EQUIPMENT. SEE MY NOTE 5 ON OF PAGE E1.0.0 LEGEND &
 NOTES
 5. NEC 210.70(A)(3) STORAGE OR EQUIPMENT SPACES. AT
 LEAST ONE LIGHTING OUTLET CONTAINING A SWITCH OR
 CONTROLLED BY A WALL SWITCH SHALL BE INSTALLED WHERE
 THESE SPACES ARE USED FOR STORAGE OR CONTAIN EQUIPMENT
 REQUIRING SERVICING. THE LIGHTING OUTLET SHALL BE
 PROVIDED AT OR NEAR THE EQUIPMENT REQUIRING SERVICING.
 THE CLOSET IN WHICH THE TV & TELEPHONE BOX/CABINET IS
 IN SHALL HAVE THE REQUIRED LIGHTING.
 6. NFPA SECTION 29.8.3.4(6). SMOKE ALARMS AND SMOKE
 DETECTORS SHALL NOT BE INSTALLED WITHIN A 36 IN. (910
 MM) HORIZONTAL PATH FROM A DOOR TO A BATHROOM
 CONTAINING A SHOWER OR TUB UNLESS LISTED FOR
 INSTALLATION IN CLOSE PROXIMITY TO SUCH LOCATIONS.
 RELOCATE THE UNITS ACCORDINGLY
 7. IN THE PROCESS OF MY ELECTRICAL PLAN REVIEW I TRIED
 TO VERIFY YOUR LOAD CALCULATIONS FOR COMPLIANCE AND NOT
 ONLY DID I FIND THEM NOT TO BE CORRECT, BUT I TRIED TO
 LOCATE THE QUOTED CODE SECTIONS IN THE 2008 EDITION OF
 THE NEC AND WAS NOT ABLE TO FIND THEM
 8. I DON?T UNDERSTAND WHY YOU ARE COUNTING A LAUNDRY
 CIRCUIT AND LATER ADDING A WASHER LOAD
 9. IN DOING THE LOAD CALCS MYSELF I ARRIVED WITH A
 SMALLER LOAD USING THE STANDARD METHOD.
  
 PAGE E3.3.1, UNITS 306-506
 1. NEC 210.52 (A)(1) SPACING. RECEPTACLES SHALL BE
 INSTALLED SUCH THAT NO POINT MEASURED HORIZONTALLY
 ALONG THE FLOOR LINE IN ANY WALL SPACE IS MORE THAN 6
 FT. FROM A RECEPTACLE OUTLET. THIS INCLUDES THE
 DISTANCE FROM THE EDGE OF THE WALL. SEE CLOUDED AREAS
 LABELED IN FOYER, KITCHEN & BEDROOM
 2. NEC 210.52(C)(1) WALL COUNTERTOP SPACES. A
 RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH WALL
 COUNTERTOP SPACE THAT IS 12 IN. OR WIDER. RECEPTACLE
 OUTLETS SHALL BE INSTALLED SO THAT NO POINT ALONG THE
 WALL LINE IS MORE THAN 24 IN. MEASURED HORIZONTALLY
 FROM A RECEPTACLE OUTLET IN THAT SPACE. . SEE CLOUDED
 AREA AND CORRECT ACCORDINGLY.
 3. NEC 210.70(A)(3) STORAGE OR EQUIPMENT SPACES. AT
 LEAST ONE LIGHTING OUTLET CONTAINING A SWITCH OR
 CONTROLLED BY A WALL SWITCH SHALL BE INSTALLED WHERE
 THESE SPACES ARE USED FOR STORAGE OR CONTAIN EQUIPMENT
 REQUIRING SERVICING. THE LIGHTING OUTLET SHALL BE
 PROVIDED AT OR NEAR THE EQUIPMENT REQUIRING SERVICING.
 THE CLOSET IN WHICH THE TV & TELEPHONE BOX/CABINET IS
 IN SHALL HAVE THE REQUIRED LIGHTING.
 4. NEC 314.27(A) LUMINAIRE OUTLETS. BOXES USED AT
 LUMINAIRE OR LAMP HOLDER OUTLETS IN A CEILING SHALL BE
 REQUIRED TO SUPPORT A LUMINAIRE WEIGHING A MINIMUM OF
 50 LB. ADD THIS TO THE NOTES ON CEILING BOXES ON PAGE.
 5. IN THE PROCESS OF MY ELECTRICAL PLAN REVIEW I TRIED
 TO VERIFY YOUR LOAD CALCULATIONS FOR COMPLIANCE AND NOT
 ONLY DID I FIND THEM NOT TO BE CORRECT, BUT I TRIED TO
 LOCATE THE QUOTED CODE SECTIONS IN THE 2008 EDITION OF
 THE NEC AND WAS NOT ABLE TO FIND THEM
 6. I DON?T UNDERSTAND WHY YOU ARE COUNTING A LAUNDRY
 CIRCUIT AND LATER ADDING A WASHER LOAD
 7. IN DOING THE LOAD CALCS MYSELF I ARRIVED WITH A
 SMALLER LOAD USING THE STANDARD METHOD.
  
 PAGE E3.4.1, UNIT 1 (TYP. 8 - 20 FLR.)
 1. NEC 210.52(C)(3) PENINSULAR COUNTERTOP SPACES. AT
 LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH
 PENINSULAR COUNTERTOP.
 2. NEC 210.52(E)(3) BALCONIES. BALCONIES GREATER THAN
 20 SQ. FT. SHALL HAVE AT LEAST ONE RECEPTACLE OUTLET
 INSTALLED WITHIN THE PERIMETER OF THE BALCONY.
 3. NEC 210.63 HVAC EQUIPMENT SERVICE OUTLET. A
 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED
 RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE
 LOCATION FOR THE SERVICING OF HVAC EQUIPMENT. THE
 RECEPTACLE SHALL BE LOCATED WITHIN 25 FT. OF THE
 EQUIPMENT. SEE MY NOTE 5 ON OF PAGE E1.0.0 LEGEND &
 NOTES
 4. NEC 210.70(A)(3) STORAGE OR EQUIPMENT SPACES. AT
 LEAST ONE LIGHTING OUTLET CONTAINING A SWITCH OR
 CONTROLLED BY A WALL SWITCH SHALL BE INSTALLED WHERE
 THESE SPACES ARE USED FOR STORAGE OR CONTAIN EQUIPMENT
 REQUIRING SERVICING. THE LIGHTING OUTLET SHALL BE
 PROVIDED AT OR NEAR THE EQUIPMENT REQUIRING SERVICING.
 THE CLOSET IN WHICH THE TV & TELEPHONE BOX/CABINET IS
 IN SHALL HAVE THE REQUIRED LIGHTING.
 5. NEC 314.27(A) LUMINAIRE OUTLETS. BOXES USED AT
 LUMINAIRE OR LAMP HOLDER OUTLETS IN A CEILING SHALL BE
 REQUIRED TO SUPPORT A LUMINAIRE WEIGHING A MINIMUM OF
 50 LB. ADD THIS TO THE NOTES ON CEILING BOXES ON PAGE.
 6. IN THE PROCESS OF MY ELECTRICAL PLAN REVIEW I TRIED
 TO VERIFY YOUR LOAD CALCULATIONS FOR COMPLIANCE AND NOT
 ONLY DID I FIND THEM NOT TO BE CORRECT, BUT I TRIED TO
 LOCATE THE QUOTED CODE SECTIONS IN THE 2008 EDITION OF
 THE NEC AND WAS NOT ABLE TO FIND THEM
 7. I DON?T UNDERSTAND WHY YOU ARE COUNTING A LAUNDRY
 CIRCUIT AND LATER ADDING A WASHER LOAD
 8. IN DOING THE LOAD CALCS MYSELF I ARRIVED WITH A
 SMALLER LOAD USING THE STANDARD METHOD.
  
 PAGE E3.5.1, TYPICAL UNIT 2
 1. NEC 210.52 (A)(1) SPACING. RECEPTACLES SHALL BE
 INSTALLED SUCH THAT NO POINT MEASURED HORIZONTALLY
 ALONG THE FLOOR LINE IN ANY WALL SPACE IS MORE THAN 6
 FT. FROM A RECEPTACLE OUTLET. THIS INCLUDES THE
 DISTANCE FROM THE EDGE OF THE WALL. THOUGH THERE IS AN
 EXCEPTION FOR THE SLIDING DOOR WE DON?T KNOW WHICH SIDE
 IS TO REMAIN FIXED AND THE PENINSULA AFFORDS A PLACE
 FOR AN OUTLET TO SOLVE THE DISTANCE FROM AN EDGE.
 2. NEC 210.52(C)(3) PENINSULAR COUNTERTOP SPACES. AT
 LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH
 PENINSULAR COUNTERTOP.
 3. NEC 210.520(D) BATHROOMS. IN DWELLING UNITS, AT
 LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED IN
 BATHROOMS WITHIN 3 FT. OF THE OUTSIDE EDGE OF EACH
 BASIN.
 4. NEC 210.63 HVAC EQUIPMENT SERVICE OUTLET. A
 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED
 RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE
 LOCATION FOR THE SERVICING OF HVAC EQUIPMENT. THE
 RECEPTACLE SHALL BE LOCATED WITHIN 25 FT. OF THE
 EQUIPMENT. SEE MY NOTE 5 ON OF PAGE E1.0.0 LEGEND &
 NOTES
 5. NEC 210.70(A)(3) STORAGE OR EQUIPMENT SPACES. AT
 LEAST ONE LIGHTING OUTLET CONTAINING A SWITCH OR
 CONTROLLED BY A WALL SWITCH SHALL BE INSTALLED WHERE
 THESE SPACES ARE USED FOR STORAGE OR CONTAIN EQUIPMENT
 REQUIRING SERVICING. THE LIGHTING OUTLET SHALL BE
 PROVIDED AT OR NEAR THE EQUIPMENT REQUIRING SERVICING.
 THE CLOSET IN WHICH THE TV & TELEPHONE BOX/CABINET IS
 IN SHALL HAVE THE REQUIRED LIGHTING.
 6. NEC 314.27(A) LUMINAIRE OUTLETS. BOXES USED AT
 LUMINAIRE OR LAMP HOLDER OUTLETS IN A CEILING SHALL BE
 REQUIRED TO SUPPORT A LUMINAIRE WEIGHING A MINIMUM OF
 50 LB. ADD THIS TO THE NOTES ON CEILING BOXES ON PAGE.
 7. IN THE PROCESS OF MY ELECTRICAL PLAN REVIEW I TRIED
 TO VERIFY YOUR LOAD CALCULATIONS FOR COMPLIANCE AND NOT
 ONLY DID I FIND THEM NOT TO BE CORRECT, BUT I TRIED TO
 LOCATE THE QUOTED CODE SECTIONS IN THE 2008 EDITION OF
 THE NEC AND WAS NOT ABLE TO FIND THEM
 8. I DON?T UNDERSTAND WHY YOU ARE COUNTING A LAUNDRY
 CIRCUIT AND LATER ADDING A WASHER LOAD
 9. IN DOING THE LOAD CALCS MYSELF I ARRIVED WITH A
 SMALLER LOAD USING THE STANDARD METHOD.
  
 PAGE E3.6.1, UNIT 3, (TYP. FOR 7 ? 19 FLR.)
 1. NEC 210.52 (A)(1) SPACING. RECEPTACLES SHALL BE
 INSTALLED SUCH THAT NO POINT MEASURED HORIZONTALLY
 ALONG THE FLOOR LINE IN ANY WALL SPACE IS MORE THAN 6
 FT. FROM A RECEPTACLE OUTLET. THIS INCLUDES THE
 DISTANCE FROM THE EDGE OF THE WALL. THOUGH THERE IS AN
 EXCEPTION FOR THE SLIDING DOOR WE DON?T KNOW WHICH SIDE
 IS TO REMAIN FIXED AND THE PENINSULA AFFORDS A PLACE
 FOR AN OUTLET TO SOLVE THE DISTANCE FROM AN EDGE.
 2. NEC 210.52(C)(3) PENINSULAR COUNTERTOP SPACES. AT
 LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH
 PENINSULAR COUNTERTOP.
 3. NEC 210.520(D) BATHROOMS. IN DWELLING UNITS, AT
 LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED IN
 BATHROOMS WITHIN 3 FT. OF THE OUTSIDE EDGE OF EACH
 BASIN.
 4. NEC 210.63 HVAC EQUIPMENT SERVICE OUTLET. A
 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED
 RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE
 LOCATION FOR THE SERVICING OF HVAC EQUIPMENT. THE
 RECEPTACLE SHALL BE LOCATED WITHIN 25 FT. OF THE
 EQUIPMENT. SEE MY NOTE 5 ON OF PAGE E1.0.0 LEGEND &
 NOTES
 5. NEC 210.70(A)(3) STORAGE OR EQUIPMENT SPACES. AT
 LEAST ONE LIGHTING OUTLET CONTAINING A SWITCH OR
 CONTROLLED BY A WALL SWITCH SHALL BE INSTALLED WHERE
 THESE SPACES ARE USED FOR STORAGE OR CONTAIN EQUIPMENT
 REQUIRING SERVICING. THE LIGHTING OUTLET SHALL BE
 PROVIDED AT OR NEAR THE EQUIPMENT REQUIRING SERVICING.
 THE CLOSET IN WHICH THE TV & TELEPHONE BOX/CABINET IS
 IN SHALL HAVE THE REQUIRED LIGHTING.
 6. NEC 314.27(A) LUMINAIRE OUTLETS. BOXES USED AT
 LUMINAIRE OR LAMP HOLDER OUTLETS IN A CEILING SHALL BE
 REQUIRED TO SUPPORT A LUMINAIRE WEIGHING A MINIMUM OF
 50 LB. ADD THIS TO THE NOTES ON CEILING BOXES ON PAGE.
 7. IN THE PROCESS OF MY ELECTRICAL PLAN REVIEW I TRIED
 TO VERIFY YOUR LOAD CALCULATIONS FOR COMPLIANCE AND NOT
 ONLY DID I FIND THEM NOT TO BE CORRECT, BUT I TRIED TO
 LOCATE THE QUOTED CODE SECTIONS IN THE 2008 EDITION OF
 THE NEC AND WAS NOT ABLE TO FIND THEM
 8. I DON?T UNDERSTAND WHY YOU ARE COUNTING A LAUNDRY
 CIRCUIT AND LATER ADDING A WASHER LOAD
 9. IN DOING THE LOAD CALCS MYSELF I ARRIVED WITH A
 SMALLER LOAD USING THE STANDARD METHOD.
 10. YOU MAY WANT TO CHECK YOUR CALCULATOR, SEE SMALL
 APPLIANCE LOAD ANALYSIS UNIT 3.
  
 PAGE E3.6.1, UNIT 3, (TYP. FOR 7 ? 19 FLR.)
 1. NEC 210.52 (A)(1) SPACING. RECEPTACLES SHALL BE
 INSTALLED SUCH THAT NO POINT MEASURED HORIZONTALLY
 ALONG THE FLOOR LINE IN ANY WALL SPACE IS MORE THAN 6
 FT. FROM A RECEPTACLE OUTLET. THIS INCLUDES THE
 DISTANCE FROM THE EDGE OF THE WALL. THOUGH THERE IS AN
 EXCEPTION FOR THE SLIDING DOOR WE DON?T KNOW WHICH SIDE
 IS TO REMAIN FIXED AND THE PENINSULA AFFORDS A PLACE
 FOR AN OUTLET TO SOLVE THE DISTANCE FROM AN EDGE.
 2. NEC 210.52(C)(3) PENINSULAR COUNTERTOP SPACES. AT
 LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH
 PENINSULAR COUNTERTOP.
 3. NEC 210.520(D) BATHROOMS. IN DWELLING UNITS, AT
 LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED IN
 BATHROOMS WITHIN 3 FT. OF THE OUTSIDE EDGE OF EACH
 BASIN.
 4. NEC 210.63 HVAC EQUIPMENT SERVICE OUTLET. A
 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED
 RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE
 LOCATION FOR THE SERVICING OF HVAC EQUIPMENT. THE
 RECEPTACLE SHALL BE LOCATED WITHIN 25 FT. OF THE
 EQUIPMENT. SEE MY NOTE 5 ON OF PAGE E1.0.0 LEGEND &
 NOTES
 5. NEC 210.70(A)(3) STORAGE OR EQUIPMENT SPACES. AT
 LEAST ONE LIGHTING OUTLET CONTAINING A SWITCH OR
 CONTROLLED BY A WALL SWITCH SHALL BE INSTALLED WHERE
 THESE SPACES ARE USED FOR STORAGE OR CONTAIN EQUIPMENT
 REQUIRING SERVICING. THE LIGHTING OUTLET SHALL BE
 PROVIDED AT OR NEAR THE EQUIPMENT REQUIRING SERVICING.
 THE CLOSET IN WHICH THE TV & TELEPHONE BOX/CABINET IS
 IN SHALL HAVE THE REQUIRED LIGHTING.
 6. NEC 314.27(A) LUMINAIRE OUTLETS. BOXES USED AT
 LUMINAIRE OR LAMP HOLDER OUTLETS IN A CEILING SHALL BE
 REQUIRED TO SUPPORT A LUMINAIRE WEIGHING A MINIMUM OF
 50 LB. ADD THIS TO THE NOTES ON CEILING BOXES ON PAGE.
 7. IN THE PROCESS OF MY ELECTRICAL PLAN REVIEW I TRIED
 TO VERIFY YOUR LOAD CALCULATIONS FOR COMPLIANCE AND NOT
 ONLY DID I FIND THEM NOT TO BE CORRECT, BUT I TRIED TO
 LOCATE THE QUOTED CODE SECTIONS IN THE 2008 EDITION OF
 THE NEC AND WAS NOT ABLE TO FIND THEM
 8. I DON?T UNDERSTAND WHY YOU ARE COUNTING A LAUNDRY
 CIRCUIT AND LATER ADDING A WASHER LOAD
 9. UNIT 3 OF PAGE E3.6.1 IS OF THE SAME SIZE, YET THE
 A/C LOAD ON ONE IS 5400VA AND THE OTHER HAS 8000VA
 10. IN DOING THE LOAD CALCS MYSELF I ARRIVED WITH A
 SMALLER LOAD USING THE STANDARD METHOD.
  
 PAGE E3.7.1, UNIT 4
 1. NEC 210.52 (A)(1) SPACING. RECEPTACLES SHALL BE
 INSTALLED SUCH THAT NO POINT MEASURED HORIZONTALLY
 ALONG THE FLOOR LINE IN ANY WALL SPACE IS MORE THAN 6
 FT. FROM A RECEPTACLE OUTLET. THIS INCLUDES THE
 DISTANCE FROM THE EDGE OF THE WALL. THOUGH THERE IS AN
 EXCEPTION FOR THE SLIDING DOOR WE DON?T KNOW WHICH SIDE
 IS TO REMAIN FIXED
 2. NEC 210.52(C)(3) PENINSULAR COUNTERTOP SPACES. AT
 LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH
 PENINSULAR COUNTERTOP.
 3. NEC 210.520(D) BATHROOMS. IN DWELLING UNITS, AT
 LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED IN
 BATHROOMS WITHIN 3 FT. OF THE OUTSIDE EDGE OF EACH
 BASIN.
 4. NEC 210.63 HVAC EQUIPMENT SERVICE OUTLET. A
 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED
 RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE
 LOCATION FOR THE SERVICING OF HVAC EQUIPMENT. THE
 RECEPTACLE SHALL BE LOCATED WITHIN 25 FT. OF THE
 EQUIPMENT. SEE MY NOTE 5 ON OF PAGE E1.0.0 LEGEND &
 NOTES
 5. NEC 314.27(A) LUMINAIRE OUTLETS. BOXES USED AT
 LUMINAIRE OR LAMP HOLDER OUTLETS IN A CEILING SHALL BE
 REQUIRED TO SUPPORT A LUMINAIRE WEIGHING A MINIMUM OF
 50 LB. ADD THIS TO THE NOTES ON CEILING BOXES ON PAGE.
 6. IN THE PROCESS OF MY ELECTRICAL PLAN REVIEW I TRIED
 TO VERIFY YOUR LOAD CALCULATIONS FOR COMPLIANCE AND NOT
 ONLY DID I FIND THEM NOT TO BE CORRECT, BUT I TRIED TO
 LOCATE THE QUOTED CODE SECTIONS IN THE 2008 EDITION OF
 THE NEC AND WAS NOT ABLE TO FIND THEM
 7. I DON?T UNDERSTAND WHY YOU ARE COUNTING A LAUNDRY
 CIRCUIT AND LATER ADDING A WASHER LOAD
 8. IN DOING THE LOAD CALCS MYSELF I ARRIVED WITH A
 SMALLER LOAD USING THE STANDARD METHOD
 9. IN THE PROCESS OF MY ELECTRICAL PLAN REVIEW I TRIED
 TO VERIFY YOUR LOAD CALCULATIONS FOR COMPLIANCE AND NOT
 ONLY DID I FIND THEM NOT TO BE CORRECT, BUT I TRIED TO
 LOCATE THE QUOTED CODE SECTIONS IN THE 2008 EDITION OF
 THE NEC AND WAS NOT ABLE TO FIND THEM
 10. I DON?T UNDERSTAND WHY YOU ARE COUNTING A LAUNDRY
 CIRCUIT AND LATER ADDING A WASHER LOAD
 11. IN DOING THE LOAD CALCS MYSELF I ARRIVED WITH A
 SMALLER LOAD USING THE STANDARD METHOD
 12. YOU MUST BE USING THE SAME CALCULATOR, SEE SMALL
 APPLIANCE LOAD ANALYSIS UNIT 4.
  
 PAGE E3.8.1, UNITS 5
 1. NEC 110.26(D) ILLUMINATION. ILLUMINATION SHALL BE
 PROVIDED FOR ALL WORKING SPACES ABOUT SERVICE
 EQUIPMENT, SWITCHBOARDS, AND PANELBOARDS. THERE SHALL
 BE PROPER ILLUMINATION ABOUT THE ELECTRICAL PANEL.
 2. NEC 210.52 (A)(2) WALL SPACE. ANY SPACE 2 FT. OR
 MORE IN WIDTH. SEE CLOUD MASTER BEDROOM
 3. NEC 210.52(C)(3) PENINSULAR COUNTERTOP SPACES. AT
 LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH
 PENINSULAR COUNTERTOP
 4. NEC 210.63 HVAC EQUIPMENT SERVICE OUTLET. A
 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED
 RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE
 LOCATION FOR THE SERVICING OF HVAC EQUIPMENT. THE
 RECEPTACLE SHALL BE LOCATED WITHIN 25 FT. OF THE
 EQUIPMENT. SEE MY NOTE 5 ON OF PAGE E1.0.0 LEGEND &
 NOTES
 5. NEC 210.70(A)(3) STORAGE OR EQUIPMENT SPACES. AT
 LEAST ONE LIGHTING OUTLET CONTAINING A SWITCH OR
 CONTROLLED BY A WALL SWITCH SHALL BE INSTALLED WHERE
 THESE SPACES ARE USED FOR STORAGE OR CONTAIN EQUIPMENT
 REQUIRING SERVICING. THE LIGHTING OUTLET SHALL BE
 PROVIDED AT OR NEAR THE EQUIPMENT REQUIRING SERVICING.
 THE CLOSET IN WHICH THE TV & TELEPHONE BOX/CABINET IS
 IN SHALL HAVE THE REQUIRED LIGHTING.
 6. NEC 314.27(A) LUMINAIRE OUTLETS. BOXES USED AT
 LUMINAIRE OR LAMP HOLDER OUTLETS IN A CEILING SHALL BE
 REQUIRED TO SUPPORT A LUMINAIRE WEIGHING A MINIMUM OF
 50 LB. ADD THIS TO THE NOTES ON CEILING BOXES ON PAGE.
 7. IN THE PROCESS OF MY ELECTRICAL PLAN REVIEW I TRIED
 TO VERIFY YOUR LOAD CALCULATIONS FOR COMPLIANCE AND NOT
 ONLY DID I FIND THEM NOT TO BE CORRECT, BUT I TRIED TO
 LOCATE THE QUOTED CODE SECTIONS IN THE 2008 EDITION OF
 THE NEC AND WAS NOT ABLE TO FIND THEM
 8. I DON?T UNDERSTAND WHY YOU ARE COUNTING A LAUNDRY
 CIRCUIT AND LATER ADDING A WASHER LOAD
 9. IN DOING THE LOAD CALCS MYSELF I ARRIVED WITH A
 SMALLER LOAD USING THE STANDARD METHOD
 10. JUST HAPPEN TO NOTICE THE BATHROOM COUNTER
 EXTENDING INTO THE PATH OF THE DOOR
 11. SEE CLOUD IN MASTER BATH COUNTER 805.05
  
 PAGE E3.9.1, UNITS 6, 7, 8, 9, 10, 12
 1. NEC 110.26(D) ILLUMINATION. ILLUMINATION SHALL BE
 PROVIDED FOR ALL WORKING SPACES ABOUT SERVICE
 EQUIPMENT, SWITCHBOARDS, AND PANELBOARDS. THERE SHALL
 BE PROPER ILLUMINATION ABOUT THE ELECTRICAL PANEL.
 2. NEC 210.52 (A)(2) WALL SPACE. ANY SPACE 2 FT. OR
 MORE IN WIDTH. SEE FOYER
 3. NEC 210.52(C)(3) PENINSULAR COUNTERTOP SPACES. AT
 LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH
 PENINSULAR COUNTERTOP
 4. NEC 210.63 HVAC EQUIPMENT SERVICE OUTLET. A
 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED
 RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE
 LOCATION FOR THE SERVICING OF HVAC EQUIPMENT. THE
 RECEPTACLE SHALL BE LOCATED WITHIN 25 FT. OF THE
 EQUIPMENT. SEE MY NOTE 5 ON OF PAGE E1.0.0 LEGEND &
 NOTES
 5. NEC 210.70(A)(3) STORAGE OR EQUIPMENT SPACES. AT
 LEAST ONE LIGHTING OUTLET CONTAINING A SWITCH OR
 CONTROLLED BY A WALL SWITCH SHALL BE INSTALLED WHERE
 THESE SPACES ARE USED FOR STORAGE OR CONTAIN EQUIPMENT
 REQUIRING SERVICING. THE LIGHTING OUTLET SHALL BE
 PROVIDED AT OR NEAR THE EQUIPMENT REQUIRING SERVICING.
 THE CLOSET IN WHICH THE TV & TELEPHONE BOX/CABINET IS
 IN SHALL HAVE THE REQUIRED LIGHTING.
 6. NEC 314.27(A) LUMINAIRE OUTLETS. BOXES USED AT
 LUMINAIRE OR LAMP HOLDER OUTLETS IN A CEILING SHALL BE
 REQUIRED TO SUPPORT A LUMINAIRE WEIGHING A MINIMUM OF
 50 LB. ADD THIS TO THE NOTES ON CEILING BOXES ON PAGE.
 7. IN THE PROCESS OF MY ELECTRICAL PLAN REVIEW I TRIED
 TO VERIFY YOUR LOAD CALCULATIONS FOR COMPLIANCE AND NOT
 ONLY DID I FIND THEM NOT TO BE CORRECT, BUT I TRIED TO
 LOCATE THE QUOTED CODE SECTIONS IN THE 2008 EDITION OF
 THE NEC AND WAS NOT ABLE TO FIND THEM
 8. I DON?T UNDERSTAND WHY YOU ARE COUNTING A LAUNDRY
 CIRCUIT AND LATER ADDING A WASHER LOAD
 9. IN DOING THE LOAD CALCS MYSELF I ARRIVED WITH A
 SMALLER LOAD USING THE STANDARD METHOD
  
 PAGE E3.9.1A, TYPICAL UNIT 7, 9
 1. ACCORDING TO THE PAGE HEADING, THESE UNITS ARE
 SUPPOSED TO BE MIRRORED OF EACH OTHER, YET THERE ARE
 TWO PANEL SCHEDULES EACH WITH ITS RESPECTIVE LOAD
 ANALYSIS; BOTH OF WHICH ARE DIFFERENT. CORRECT THE LOAD
 ANALYSIS AND PANEL SCHEDULES OR REMOVE THE MIRROR
 REFERENCE.
 2. NEC 110.26(D) ILLUMINATION. ILLUMINATION SHALL BE
 PROVIDED FOR ALL WORKING SPACES ABOUT SERVICE
 EQUIPMENT, SWITCHBOARDS, AND PANELBOARDS. THERE SHALL
 BE PROPER ILLUMINATION ABOUT THE ELECTRICAL PANEL.
 3. NEC 210.52 (A)(2) WALL SPACE. ANY SPACE 2 FT. OR
 MORE IN WIDTH. SEE FOYER
 4. NEC 210.52(C)(3) PENINSULAR COUNTERTOP SPACES. AT
 LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH
 PENINSULAR COUNTERTOP
 5. NEC 210.63 HVAC EQUIPMENT SERVICE OUTLET. A
 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED
 RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE
 LOCATION FOR THE SERVICING OF HVAC EQUIPMENT. THE
 RECEPTACLE SHALL BE LOCATED WITHIN 25 FT. OF THE
 EQUIPMENT. SEE MY NOTE 5 ON OF PAGE E1.0.0 LEGEND &
 NOTES
 6. NEC 210.70(A)(3) STORAGE OR EQUIPMENT SPACES. AT
 LEAST ONE LIGHTING OUTLET CONTAINING A SWITCH OR
 CONTROLLED BY A WALL SWITCH SHALL BE INSTALLED WHERE
 THESE SPACES ARE USED FOR STORAGE OR CONTAIN EQUIPMENT
 REQUIRING SERVICING. THE LIGHTING OUTLET SHALL BE
 PROVIDED AT OR NEAR THE EQUIPMENT REQUIRING SERVICING.
 THE CLOSET IN WHICH THE TV & TELEPHONE BOX/CABINET IS
 IN SHALL HAVE THE REQUIRED LIGHTING.
 7. NEC 314.27(A) LUMINAIRE OUTLETS. BOXES USED AT
 LUMINAIRE OR LAMP HOLDER OUTLETS IN A CEILING SHALL BE
 REQUIRED TO SUPPORT A LUMINAIRE WEIGHING A MINIMUM OF
 50 LB. ADD THIS TO THE NOTES ON CEILING BOXES ON PAGE.
 8. IN THE PROCESS OF MY ELECTRICAL PLAN REVIEW I TRIED
 TO VERIFY YOUR LOAD CALCULATIONS FOR COMPLIANCE AND NOT
 ONLY DID I FIND THEM NOT TO BE CORRECT, BUT I TRIED TO
 LOCATE THE QUOTED CODE SECTIONS IN THE 2008 EDITION OF
 THE NEC AND WAS NOT ABLE TO FIND THEM
 9. I DON?T UNDERSTAND WHY YOU ARE COUNTING A LAUNDRY
 CIRCUIT AND LATER ADDING A WASHER LOAD
 10. IN DOING THE LOAD CALCS MYSELF I ARRIVED WITH A
 SMALLER LOAD USING THE STANDARD METHOD
  
 PAGE E3.10.1, TYPICAL UNIT 11
 1. NEC 210.52 (A)(1) SPACING. RECEPTACLES SHALL BE
 INSTALLED SUCH THAT NO POINT MEASURED HORIZONTALLY
 ALONG THE FLOOR LINE IN ANY WALL SPACE IS MORE THAN 6
 FT. FROM A RECEPTACLE OUTLET. THIS INCLUDES THE
 DISTANCE FROM THE EDGE OF THE WALL. SEE DEN & FOYER
 2. NEC 210.52(C)(1) WALL COUNTERTOP SPACES. A
 RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH WALL
 COUNTERTOP SPACE THAT IS 12 IN. OR WIDER. RECEPTACLE
 OUTLETS SHALL BE INSTALLED SO THAT NO POINT ALONG THE
 WALL LINE IS MORE THAN 24 IN. MEASURED HORIZONTALLY
 FROM A RECEPTACLE OUTLET IN THAT SPACE.
 3. NEC 210.52(C)(3) PENINSULAR COUNTERTOP SPACES. AT
 LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH
 PENINSULAR COUNTERTOP.
 4. NEC 210.63 HVAC EQUIPMENT SERVICE OUTLET. A
 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED
 RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE
 LOCATION FOR THE SERVICING OF HVAC EQUIPMENT. THE
 RECEPTACLE SHALL BE LOCATED WITHIN 25 FT. OF THE
 EQUIPMENT. SEE MY NOTE 5 ON OF PAGE E1.0.0 LEGEND &
 NOTES
 5. NEC 210.70(A)(3) STORAGE OR EQUIPMENT SPACES. AT
 LEAST ONE LIGHTING OUTLET CONTAINING A SWITCH OR
 CONTROLLED BY A WALL SWITCH SHALL BE INSTALLED WHERE
 THESE SPACES ARE USED FOR STORAGE OR CONTAIN EQUIPMENT
 REQUIRING SERVICING. THE LIGHTING OUTLET SHALL BE
 PROVIDED AT OR NEAR THE EQUIPMENT REQUIRING SERVICING.
 THE CLOSET IN WHICH THE TV & TELEPHONE BOX/CABINET IS
 IN SHALL HAVE THE REQUIRED LIGHTING.
 6. NEC 314.27(A) LUMINAIRE OUTLETS. BOXES USED AT
 LUMINAIRE OR LAMP HOLDER OUTLETS IN A CEILING SHALL BE
 REQUIRED TO SUPPORT A LUMINAIRE WEIGHING A MINIMUM OF
 50 LB. ADD THIS TO THE NOTES ON CEILING BOXES ON PAGE.
 7. IN THE PROCESS OF MY ELECTRICAL PLAN REVIEW I TRIED
 TO VERIFY YOUR LOAD CALCULATIONS FOR COMPLIANCE AND NOT
 ONLY DID I FIND THEM NOT TO BE CORRECT, BUT I TRIED TO
 LOCATE THE QUOTED CODE SECTIONS IN THE 2008 EDITION OF
 THE NEC AND WAS NOT ABLE TO FIND THEM
 8. I DON?T UNDERSTAND WHY YOU ARE COUNTING A LAUNDRY
 CIRCUIT AND LATER ADDING A WASHER LOAD
 9. IN DOING THE LOAD CALCS MYSELF I ARRIVED WITH A
 SMALLER LOAD USING THE STANDARD METHOD
 10. THE SMOKE DETECTOR IN THE DEN IS NOT REQUIRED AS
 THIS IS NOT CONSIDERED A SLEEPING AREA; IF IT TO
 REMAIN, IT SHALL BE RELOCATED TO COMPLY WITH NFPA
 SECTION 29.8.3.4(6) WHICH REQUIRES THAT THE SMOKE
 DETECTOR NOT BE WITHIN 36? OF A BATHROOM WITH A SHOWER
 OR TUB. RELOCATE THIS UNIT ACCORDINGLY.
  
 PAGE E3.11.1, UNIT 11A, 7TH FLR
 1. NEC 210.52 (A)(1) SPACING. RECEPTACLES SHALL BE
 INSTALLED SUCH THAT NO POINT MEASURED HORIZONTALLY
 ALONG THE FLOOR LINE IN ANY WALL SPACE IS MORE THAN 6
 FT. FROM A RECEPTACLE OUTLET. THIS INCLUDES THE
 DISTANCE FROM THE EDGE OF THE WALL.
 2. NEC 210.52(C)(3) PENINSULAR COUNTERTOP SPACES. AT
 LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH
 PENINSULAR COUNTERTOP.
 3. NEC 210.63 HVAC EQUIPMENT SERVICE OUTLET. A
 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED
 RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE
 LOCATION FOR THE SERVICING OF HVAC EQUIPMENT. THE
 RECEPTACLE SHALL BE LOCATED WITHIN 25 FT. OF THE
 EQUIPMENT. SEE MY NOTE 5 ON OF PAGE E1.0.0 LEGEND &
 NOTES
 4. NEC 210.70(A)(3) STORAGE OR EQUIPMENT SPACES. AT
 LEAST ONE LIGHTING OUTLET CONTAINING A SWITCH OR
 CONTROLLED BY A WALL SWITCH SHALL BE INSTALLED WHERE
 THESE SPACES ARE USED FOR STORAGE OR CONTAIN EQUIPMENT
 REQUIRING SERVICING. THE LIGHTING OUTLET SHALL BE
 PROVIDED AT OR NEAR THE EQUIPMENT REQUIRING SERVICING.
 THE CLOSET IN WHICH THE TV & TELEPHONE BOX/CABINET IS
 IN SHALL HAVE THE REQUIRED LIGHTING.
 5. NEC 314.27(A) LUMINAIRE OUTLETS. BOXES USED AT
 LUMINAIRE OR LAMP HOLDER OUTLETS IN A CEILING SHALL BE
 REQUIRED TO SUPPORT A LUMINAIRE WEIGHING A MINIMUM OF
 50 LB. ADD THIS TO THE NOTES ON CEILING BOXES ON PAGE.
 6. IN THE PROCESS OF MY ELECTRICAL PLAN REVIEW I TRIED
 TO VERIFY YOUR LOAD CALCULATIONS FOR COMPLIANCE AND NOT
 ONLY DID I FIND THEM NOT TO BE CORRECT, BUT I TRIED TO
 LOCATE THE QUOTED CODE SECTIONS IN THE 2008 EDITION OF
 THE NEC AND WAS NOT ABLE TO FIND THEM
 7. I DON?T UNDERSTAND WHY YOU ARE COUNTING A LAUNDRY
 CIRCUIT AND LATER ADDING A WASHER LOAD
 8. IN DOING THE LOAD CALCS MYSELF I ARRIVED WITH A
 SMALLER LOAD USING THE STANDARD METHOD
 9. JUST HAPPEN TO NOTICE THE BATHROOM COUNTER EXTENDING
 INTO THE PATH OF THE DOOR
  
 PAGE E3.12.1, UNIT 13
 1. NEC 210.52 (A)(1) SPACING. RECEPTACLES SHALL BE
 INSTALLED SUCH THAT NO POINT MEASURED HORIZONTALLY
 ALONG THE FLOOR LINE IN ANY WALL SPACE IS MORE THAN 6
 FT. FROM A RECEPTACLE OUTLET. THIS INCLUDES THE
 DISTANCE FROM THE EDGE OF THE WALL. SEE MASTER BEDROOM
 & BEDROOM 2.
 2. NEC 210.52 (A)(2) WALL SPACE. ANY SPACE 2 FT. OR
 MORE IN WIDTH. SEE FOYER.
 3. NEC 210.52(C)(3) PENINSULAR COUNTERTOP SPACES. AT
 LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH
 PENINSULAR COUNTERTOP. SEE BOTH KITCHEN PENINSULAS.
 4. NEC 210.520(D) BATHROOMS. IN DWELLING UNITS, AT
 LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED IN
 BATHROOMS WITHIN 3 FT. OF THE OUTSIDE EDGE OF EACH
 BASIN. SEE MASTER BATH.
 5. NEC 210.63 HVAC EQUIPMENT SERVICE OUTLET. A
 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED
 RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE
 LOCATION FOR THE SERVICING OF HVAC EQUIPMENT. THE
 RECEPTACLE SHALL BE LOCATED WITHIN 25 FT. OF THE
 EQUIPMENT. SEE MY NOTE 5 ON OF PAGE E1.0.0 LEGEND &
 NOTES
 6. NEC 210.70(A)(3) STORAGE OR EQUIPMENT SPACES. AT
 LEAST ONE LIGHTING OUTLET CONTAINING A SWITCH OR
 CONTROLLED BY A WALL SWITCH SHALL BE INSTALLED WHERE
 THESE SPACES ARE USED FOR STORAGE OR CONTAIN EQUIPMENT
 REQUIRING SERVICING. THE LIGHTING OUTLET SHALL BE
 PROVIDED AT OR NEAR THE EQUIPMENT REQUIRING SERVICING.
 THE CLOSET IN WHICH THE TV & TELEPHONE BOX/CABINET IS
 IN SHALL HAVE THE REQUIRED LIGHTING.
 7. NEC 314.27(A) LUMINAIRE OUTLETS. BOXES USED AT
 LUMINAIRE OR LAMP HOLDER OUTLETS IN A CEILING SHALL BE
 REQUIRED TO SUPPORT A LUMINAIRE WEIGHING A MINIMUM OF
 50 LB. ADD THIS TO THE NOTES ON CEILING BOXES ON PAGE.
 8. IN THE PROCESS OF MY ELECTRICAL PLAN REVIEW I TRIED
 TO VERIFY YOUR LOAD CALCULATIONS FOR COMPLIANCE AND NOT
 ONLY DID I FIND THEM NOT TO BE CORRECT, BUT I TRIED TO
 LOCATE THE QUOTED CODE SECTIONS IN THE 2008 EDITION OF
 THE NEC AND WAS NOT ABLE TO FIND THEM
 9. I DON?T UNDERSTAND WHY YOU ARE COUNTING A LAUNDRY
 CIRCUIT AND LATER ADDING A WASHER LOAD
 10. IN DOING THE LOAD CALCS MYSELF I ARRIVED WITH A
 SMALLER LOAD USING THE STANDARD METHOD
  
 PAGE E3.13.1, UNIT 14
 1. NEC 110.26(D) ILLUMINATION. ILLUMINATION SHALL BE
 PROVIDED FOR ALL WORKING SPACES ABOUT SERVICE
 EQUIPMENT, SWITCHBOARDS, AND PANELBOARDS. THERE SHALL
 BE PROPER ILLUMINATION ABOUT THE ELECTRICAL PANEL.
 2. NEC 210.52 (A)(1) SPACING. RECEPTACLES SHALL BE
 INSTALLED SUCH THAT NO POINT MEASURED HORIZONTALLY
 ALONG THE FLOOR LINE IN ANY WALL SPACE IS MORE THAN 6
 FT. FROM A RECEPTACLE OUTLET. THIS INCLUDES THE
 DISTANCE FROM THE EDGE OF THE WALL. SEE MASTER BEDROOM.
 3. NEC 210.52 (A)(2) WALL SPACE. ANY SPACE 2 FT. OR
 MORE IN WIDTH. SEE FOYER.
 4. NEC 210.52(C)(3) PENINSULAR COUNTERTOP SPACES. AT
 LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH
 PENINSULAR COUNTERTOP. SEE BOTH KITCHEN PENINSULAS.
 5. NEC 210.63 HVAC EQUIPMENT SERVICE OUTLET. A
 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED
 RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE
 LOCATION FOR THE SERVICING OF HVAC EQUIPMENT. THE
 RECEPTACLE SHALL BE LOCATED WITHIN 25 FT. OF THE
 EQUIPMENT. SEE MY NOTE 5 ON OF PAGE E1.0.0 LEGEND &
 NOTES
 6. NEC 314.27(A) LUMINAIRE OUTLETS. BOXES USED AT
 LUMINAIRE OR LAMP HOLDER OUTLETS IN A CEILING SHALL BE
 REQUIRED TO SUPPORT A LUMINAIRE WEIGHING A MINIMUM OF
 50 LB. ADD THIS TO THE NOTES ON CEILING BOXES ON PAGE.
 7. IN THE PROCESS OF MY ELECTRICAL PLAN REVIEW I TRIED
 TO VERIFY YOUR LOAD CALCULATIONS FOR COMPLIANCE AND NOT
 ONLY DID I FIND THEM NOT TO BE CORRECT, BUT I TRIED TO
 LOCATE THE QUOTED CODE SECTIONS IN THE 2008 EDITION OF
 THE NEC AND WAS NOT ABLE TO FIND THEM
 8. I DON?T UNDERSTAND WHY YOU ARE COUNTING A LAUNDRY
 CIRCUIT AND LATER ADDING A WASHER LOAD
 9. IN DOING THE LOAD CALCS MYSELF I ARRIVED WITH A
 SMALLER LOAD USING THE STANDARD METHOD
  
 PAGE E3.14.1, UNIT 15
 1. NEC 110.26(D) ILLUMINATION. ILLUMINATION SHALL BE
 PROVIDED FOR ALL WORKING SPACES ABOUT SERVICE
 EQUIPMENT, SWITCHBOARDS, AND PANELBOARDS. THERE SHALL
 BE PROPER ILLUMINATION ABOUT THE ELECTRICAL PANEL.
 2. NEC 210.52 (A)(1) SPACING. RECEPTACLES SHALL BE
 INSTALLED SUCH THAT NO POINT MEASURED HORIZONTALLY
 ALONG THE FLOOR LINE IN ANY WALL SPACE IS MORE THAN 6
 FT. FROM A RECEPTACLE OUTLET. THIS INCLUDES THE
 DISTANCE FROM THE EDGE OF THE WALL. SEE LIVING ROOM,
 DINING ROOM & BEDROOM 2.
 3. NEC 210.52 (A)(2) WALL SPACE. ANY SPACE 2 FT. OR
 MORE IN WIDTH. SEE DINING ROOM & WALL ADJACENT TO
 ELECTRIC PANEL
 4. NEC 210.52(C)(3) PENINSULAR COUNTERTOP SPACES. AT
 LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH
 PENINSULAR COUNTERTOP. SEE BOTH KITCHEN PENINSULAS.
 5. NEC 210.63 HVAC EQUIPMENT SERVICE OUTLET. A
 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED
 RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE
 LOCATION FOR THE SERVICING OF HVAC EQUIPMENT. THE
 RECEPTACLE SHALL BE LOCATED WITHIN 25 FT. OF THE
 EQUIPMENT. SEE MY NOTE 5 ON OF PAGE E1.0.0 LEGEND &
 NOTES
 6. NEC 314.27(A) LUMINAIRE OUTLETS. BOXES USED AT
 LUMINAIRE OR LAMP HOLDER OUTLETS IN A CEILING SHALL BE
 REQUIRED TO SUPPORT A LUMINAIRE WEIGHING A MINIMUM OF
 50 LB. ADD THIS TO THE NOTES ON CEILING BOXES ON PAGE.
 7. IN THE PROCESS OF MY ELECTRICAL PLAN REVIEW I TRIED
 TO VERIFY YOUR LOAD CALCULATIONS FOR COMPLIANCE AND NOT
 ONLY DID I FIND THEM NOT TO BE CORRECT, BUT I TRIED TO
 LOCATE THE QUOTED CODE SECTIONS IN THE 2008 EDITION OF
 THE NEC AND WAS NOT ABLE TO FIND THEM
 8. I DON?T UNDERSTAND WHY YOU ARE COUNTING A LAUNDRY
 CIRCUIT AND LATER ADDING A WASHER LOAD
 9. IN DOING THE LOAD CALCS MYSELF I ARRIVED WITH A
 SMALLER LOAD USING THE STANDARD METHOD
  
 PAGE E15.1, UNIT 15A, 7TH FLR
 1. NEC 110.26(D) ILLUMINATION. ILLUMINATION SHALL BE
 PROVIDED FOR ALL WORKING SPACES ABOUT SERVICE
 EQUIPMENT, SWITCHBOARDS, AND PANELBOARDS. THERE SHALL
 BE PROPER ILLUMINATION ABOUT THE ELECTRICAL PANEL.
 2. NEC 210.52 (A)(1) SPACING. RECEPTACLES SHALL BE
 INSTALLED SUCH THAT NO POINT MEASURED HORIZONTALLY
 ALONG THE FLOOR LINE IN ANY WALL SPACE IS MORE THAN 6
 FT. FROM A RECEPTACLE OUTLET. THIS INCLUDES THE
 DISTANCE FROM THE EDGE OF THE WALL. SEE LIVING & DINING
 ROOMS.
 3. NEC 210.52(C)(3) PENINSULAR COUNTERTOP SPACES. AT
 LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH
 PENINSULAR COUNTERTOP. SEE BOTH KITCHEN PENINSULAS.
 4. NEC 210.52(E)(3) BALCONIES. BALCONIES GREATER THAN
 20 SQ. FT. SHALL HAVE AT LEAST ONE RECEPTACLE OUTLET
 INSTALLED WITHIN THE PERIMETER OF THE BALCONY. THOUGH I
 DON?T SEE THE TERRACE DELINEATION, ROOM 715.12
 INDICATES A TERRACE. NO CLOUD DUE TO UNCERTAINTY OF
 TERRACE.
 5. NEC 210.63 HVAC EQUIPMENT SERVICE OUTLET. A
 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED
 RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE
 LOCATION FOR THE SERVICING OF HVAC EQUIPMENT. THE
 RECEPTACLE SHALL BE LOCATED WITHIN 25 FT. OF THE
 EQUIPMENT. SEE MY NOTE 5 ON OF PAGE E1.0.0 LEGEND &
 NOTES
 6. NEC 210.70(A)(3) STORAGE OR EQUIPMENT SPACES. AT
 LEAST ONE LIGHTING OUTLET CONTAINING A SWITCH OR
 CONTROLLED BY A WALL SWITCH SHALL BE INSTALLED WHERE
 THESE SPACES ARE USED FOR STORAGE OR CONTAIN EQUIPMENT
 REQUIRING SERVICING. THE LIGHTING OUTLET SHALL BE
 PROVIDED AT OR NEAR THE EQUIPMENT REQUIRING SERVICING.
 THE CLOSET IN WHICH THE TV & TELEPHONE BOX/CABINET IS
 IN SHALL HAVE THE REQUIRED LIGHTING. SEE BEDROOM 2
 CLOSET.
 7. NEC 314.27(A) LUMINAIRE OUTLETS. BOXES USED AT
 LUMINAIRE OR LAMP HOLDER OUTLETS IN A CEILING SHALL BE
 REQUIRED TO SUPPORT A LUMINAIRE WEIGHING A MINIMUM OF
 50 LB. ADD THIS TO THE NOTES ON CEILING BOXES ON PAGE.
 8. I REVIEWED YOUR LOAD CALCULATIONS FOR COMPLIANCE AND
 NOT ONLY DID I FIND THEM NOT TO BE CORRECT, BUT I TRIED
 TO LOCATE THE QUOTED CODE SECTIONS IN THE 2008 EDITION
 OF THE NEC AND WAS NOT ABLE TO FIND THEM
 9. YOU ARE COUNTING A LAUNDRY CIRCUIT AND LATER ADDING
 A WASHER LOAD
 10. IN DOING THE LOAD CALCS MYSELF I ARRIVED WITH A
 SMALLER LOAD USING THE STANDARD METHOD
  
 PAGE E4.1.1 PANEL SCHEDULES
 1. INCLUDE THE RETAIL MAIN
  
 PAGE E5.1.1 POWER RISER
 1. YOUR NOTES ON PAGE E5.2.1 DESCRIBE THESE CONDUCTORS
 AS HAVING THHN INSULATION. CORRECT THAT TO COMPLY WITH
 THE REQUIREMENTS OF NEC 300.5 B, STATING THAT THE
 INTERIOR OF AN UNDERGROUND RACEWAY SHALL BE CONSIDERED
 A WET LOCATION AND THUS THWN IS REQUIRED.
  
 PAGE E6.3.1 ENLARGED ROOMS
 1. NEC 110.26 A1 REQUIRES A MINIMUM OF 3? CLEAR WORKING
 SPACE IN FRONT OF ELECTRICAL EQUIPMENT; ACCORDING TO
 THE DRAWINGS THERE SEEMS TO BE ENCROACHMENT OF THIS
 SPACE IN THE ELECTRICAL ROOMS OF LEVELS 7, 9, 11, 14,
 16, & 18. CHECK AND REVISE AS NECESSARY.
  
 PAGE E7.1.1 LIGHT FIXTURE SCHEDULES
 1. I HAVE NOT SEEN ANYWHERE ON THE DRAWINGS A NOTE AS
 TO THE COMPLIANCE WITH THE 2010 FBC-ENERGY CONSERVATION
 CODE.
  
 THESE PLANS WERE REVIEWED FOR COMPLIANCE WITH THE 2008
 EDITION OF THE NEC, THE 2013 EDITION OF THE NFPA72, THE
 APPLICABLE CHAPTERS OF THE 2010 EDITION OF THE FLORIDA
 BUILDING CODE, FLORIDA BUILDING CODE RESIDENTIAL AND
 FLORIDA BUILDING CODE ENERGY CONSERVATION.
  
 FOR QUESTIONS ON THE ABOVE, PLEASE CONTACT:
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 PH: (561) 805-6743
 EMAIL: [email protected]
  
 FIRE ALARM REVIEW UNDER SEPARATE COVER.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.

Review Stop ENG ENGINEERING CSD
Rev No 2 Status N Date 2015-09-02 Cont ID  
Sent By cranford Date 2015-09-02 Time 08:52 Rev Time 0.00
Received By cranford Date 2015-09-02 Time 08:52 Sent To  
Notes
2015-09-02 08:52:30SEE E14120021 FOR CIVIL (POTABLE WATER, SANITARY SEWER,
 AND STORMWATER) REVIEW.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2015-05-08 Cont ID  
Sent By cranford Date 2015-05-08 Time 08:54 Rev Time 0.00
Received By cranford Date 2015-04-29 Time 11:17 Sent To  
Notes
2015-05-08 08:54:46SEE E14120021 FOR CIVIL (POTABLE WATER, SANITARY SEWER,
 AND STORMWATER) REVIEW.

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2015-12-09 Cont ID  
Sent By wjolin Date 2015-12-09 Time 08:11 Rev Time 0.00
Received By wjolin Date 2015-12-09 Time 07:55 Sent To  
Notes
2015-12-09 08:11:28333 FERN STREET
 PERMIT #15031312
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 RESPONSE COMMENT: DOORS LOCKED WITH MAGNETS ARE
 REQUIRED TO AUTOMATICALLY UNLOCK WITH AN OCCUPANT
 SENSOR. THE "PUSH TO EXIT" BUTTON CANNOT BE THE PRIMARY
 MEANS FOR RELEASING THE DOOR, IT MUST BE SECONDARY TO
 THE AUTOMATIC OCCUPANT SENSOR.
 REPEAT COMMENT - SHEET LS-7.0: BOTH SECONDARY EXITS
 FROM COMMON ROOM 701.01 HAVE CARD READERS (KEY/TOOL) AT
 THE EXIT ACCESS DOOR LEADING TO THE POOL DECK.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2015-09-18 Cont ID  
Sent By wjolin Date 2015-09-18 Time 12:51 Rev Time 0.00
Received By wjolin Date 2015-09-11 Time 12:21 Sent To  
Notes
2015-09-11 12:22:04333 FERN STREET
 PERMIT #15031312
 REVIEW COMMENTS - FIRE DEPARTMENT
 NOTE: UNLESS NOTED OTHERWISE, ALL FIRE/LIFE SAFETY
 REVIEW COMMENTS REFERENCE NFPA 101-THE LIFE SAFETY CODE
 (2012 EDITION WITH FLORIDA AMENDMENTS.)
  
 RESPONSE COMMENT - SINCE THIS BACKFLOW PREVENTER IS
 LOCATED ON PRIVATE PROPERTY WPB UTILITIES DOES NOT HAVE
 JURISDICTION. PER FLORIDA STATUTE 633 THE FIRE MARSHAL
 IS RESPONSIBLE FOR ENFORCEMENT OF THE FIRE CODE;
 THEREFORE, COMPLIANCE WITH THE COMMENT BELOW IS
 REQUIRED.
 ORIGINAL COMMENT - SHEET C-09: PER NFPA 24 SECTION
 6.2.1, BACKFLOW PREVENTER CONTROL VALVES SHALL BE
 INSTALLED IN A FIRE-RATED ROOM ACCESSIBLE FROM THE
 EXTERIOR.
  
 SHEET LS-7.0: THE COOKING GRILL LOCATED ON THE POOL
 DECK SHALL COMPLY WITH NFPA 96 OR SHALL BE LOCATED AT
 LEAST 10 FEET FROM ANY BUILDING, STRUCTURE, OR
 COMBUSTIBLES PER NFPA 1 SECTION 10.11.6.1. IF THE GRILL
 WILL BE USED UNDER A ROOF STRUCTURE, THE DESIGN SHALL
 COMPLY WITH NFPA 96.
  
 REPEAT COMMENT - SHEET LS-7.0: BOTH SECONDARY EXITS
 FROM COMMON ROOM 701.01 HAVE CARD READERS (KEY/TOOL) AT
 THE EXIT ACCESS DOOR LEADING TO THE POOL DECK.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  
  
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2015-05-08 Cont ID  
Sent By wjolin Date 2015-05-08 Time 16:29 Rev Time 0.00
Received By wjolin Date 2015-05-08 Time 10:53 Sent To  
Notes
2015-05-08 11:01:18333 FERN STREET
 PERMIT #15031312
 REVIEW COMMENTS - FIRE DEPARTMENT
 NOTE: UNLESS NOTED OTHERWISE, ALL FIRE/LIFE SAFETY
 REVIEW COMMENTS REFERENCE NFPA 101-THE LIFE SAFETY CODE
 (2012 EDITION WITH FLORIDA AMENDMENTS.)
  
  
 SHEET C-09: PER NFPA 24 SECTION 6.2.1, BACKFLOW
 PREVENTER CONTROL VALVES SHALL BE INSTALLED IN A
 FIRE-RATED ROOM ACCESSIBLE FROM THE EXTERIOR.
  
 SHEET LS-7.0: ALL THREE SECONDARY EXITS FROM COMMON
 ROOM 701.01 HAVE CARD READERS (KEY/TOOL) AT THE EXIT
 ACCESS DOOR LEADING TO THE POOL DECK.
  
 SHEET A2.1.1: EXIT ACCESS CORRIDOR #115 APPEARS TO
 ACTUALLY BE AN EXIT PASSAGEWAY.
  
 SHEET A7.1.1: ELEVATOR CONTROL ROOM #609 IS INDICATED
 AS BEING A FIRE RATED ROOM ON SHEET LS-6.0; HOWEVER,
 THE DOOR SCHEDULE INDICATES DOOR 609 DOES NOT HAVE A
 FIRE RESISTANCE RATING.
  
 ELEVATOR #4: COULD NOT LOCATE AN ELEVATOR LOBBY OR
 HOISTWAY PRESSURIZATION FAN AS IS REQUIRED FOR
 HIGH-RISE BUILDINGS.
  
 SIGNAGE: PER SECTION 7.2.2.5.4 - STAIRWAY
 IDENTIFICATION: NEW ENCLOSED STAIRS SERVING THREE OR
 MORE STORIES AND EXISTING ENCLOSED STAIRS SERVING FIVE
 OR MORE STORIES SHALL COMPLY WITH (A) THROUGH (L).
 (A) THE STAIRS SHALL BE PROVIDED WITH SPECIAL SIGNAGE
 WITHIN THE ENCLOSURE AT EACH FLOOR LANDING.
 (B) THE SIGNAGE SHALL INDICATE THE FLOOR LEVEL.
 (C) THE SIGNAGE SHALL INDICATE THE TERMINUS OF THE TOP
 AND BOTTOM OF THE STAIR ENCLOSURE.
 (D) THE SIGNAGE SHALL INDICATE THE IDENTIFICATION OF
 THE STAIR ENCLOSURE.
 (E) THE SIGNAGE SHALL INDICATE THE FLOOR LEVEL OF, AND
 THE DIRECTION TO, EXIT DISCHARGE.
 (F) THE SIGNAGE SHALL BE LOCATED INSIDE THE ENCLOSURE
 APPROXIMATELY 60-INCHES ABOVE THE FLOOR LANDING IN A
 POSITION THAT IS VISIBLE WHEN THE DOOR IS IN THE OPEN
 OR CLOSED POSITION.
 (G) THE FLOOR LEVEL DESIGNATION SHALL ALSO BE TACTILE.
 (H) THE SIGNAGE SHALL BE PAINTED OR STENCILED ON THE
 WALL OR ON A SEPARATE SIGN SECURELY ATTACHED TO THE
 WALL.
 (I) THE STAIRWAY IDENTIFICATION LETTER SHALL BE LOCATED
 AT THE TOP OF THE SIGN IN MINIMUM 1-INCH HIGH
 LETTERING.
 (J) SIGNAGE THAT READS "NO ROOF ACCESS" AND IS LOCATED
 UNDER THE STAIRWAY IDENTIFICATION LETTER SHALL
 DESIGNATE STAIRWAYS THAT DO NOT PROVIDE ROOF ACCESS.
 LETTERING SHALL BE A MINIMUM OF 1-INCH HIGH.
 (K) THE FLOOR LEVEL NUMBER SHALL BE LOCATED IN THE
 MIDDLE OF THE SIGN IN MINIMUM 5-INCH HIGH NUMBERS.
 MEZZANINE LEVELS SHALL HAVE THE LETTER "M" OR OTHER
 APPROPRIATE IDENTIFICATION LETTER PRECEDING THE FLOOR
 NUMBER, WHILE BASEMENT LEVELS SHALL HAVE THE LETTER "B"
 OR OTHER APPROPRIATE IDENTIFICATION LETTER PRECEDING
 THE FLOOR LEVEL NUMBER.
 (L) IDENTIFICATION OF THE LOWER AND UPPER TERMINUS OF
 THE STAIRWAY SHALL BE LOCATED AT THE BOTTOM OF THE SIGN
 IN MINIMUM 1-INCH HIGH LETTERS OR NUMBERS.
  
 SHEET FP2-1-1: THE PLANS INDICATE TWO FIRE MAINS
 SUPPLYING THE FIRE PUMP; HOWEVER, THE THESE TWO MAINS
 REDUCE TO ONE MAIN IMMEDIATELY INSIDE THE BUILDING. THE
 MAINS NEED TO BE REMAIN SEPARATE UNTIL THEY REACH THE
 PUMP ROOM.
  
 SHEET FA5-1-1: PROVIDE BI-DIRECTIONAL AMPLIFIER/TWO-WAY
 RADIO COMMUNICATION ENHANCEMENT SYSTEMS COMPLYING WITH
 NFPA 72.
  
 SITE: WHERE ARE THE CONSTRUCTION TRAILERS INTENDED TO
 BE LOCATED? PER NFPA 241 SECTION 4.2.2: DETACHMENT
 BETWEEN TEMPORARY STRUCTURES, ADEQUATE TEMPORARY FIXED
 FIRE PROTECTION SYSTEMS, AND PORTABLE EQUIPMENT SHALL
 BE PROVIDED AS REQUIRED BY THE AUTHORITY HAVING
 JURISDICTION.
  
 SITE: PER NFPA 241- STANDARD FOR SAFEGUARDING
 CONSTRUCTION, ALTERATION, AND DEMOLITION OPERATIONS,
 SECTION 4.2: TEMPORARY OFFICES, TRAILERS, AND OTHER
 FACILITIES OF COMBUSTIBLE CONSTRUCTION OR HOUSING
 COMBUSTIBLE CONTENTS SHALL BE SEPARATED FROM ADJACENT
 BUILDINGS, TRAILERS OR STRUCTURES IN ACCORDANCE
 WITHTABLE 4.2.1.
 PER TABLE 4.2.1:
 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 30 FEET
 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 35 FEET
 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 40 FEET
 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 45 FEET
 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 50 FEET
 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE
 SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET
 **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL
 BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC
 SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE.
  
 NOTE: PER FFPC SECTION 11.9.4 AND FBC SECTION 911.1.5 -
 THE FIRE COMMAND CENTER SHALL COMPLY WITH NFPA 72 AND
 SHALL CONTAIN THE FOLLOWING FEATURES:
 1. THE EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM
 CONTROL UNIT.
 2. THE FIRE DEPARTMENT COMMUNICATIONS SYSTEM.
 3. FIRE DETECTION AND ALARM SYSTEM ANNUNCIATOR.
 4. ANNUNCIATOR UNIT VISUALLY INDICATING THE LOCATION OF
 THE ELEVATORS AND WHETHER THEY ARE OPERATIONAL.
 5. STATUS INDICATORS AND CONTROLS FOR AIR DISTRIBUTION
 SYSTEMS.
 6. THE FIRE-FIGHTER'S CONTROL PANEL REQUIRED BY SECTION
 909.16 FOR SMOKE CONTROL SYSTEMS INSTALLED IN THE
 BUILDING.
 7. CONTROLS FOR UNLOCKING STAIRWAY DOORS
 SIMULTANEOUSLY.
 8. SPRINKLER VALVE AND WATERFLOW DETECTOR DISPLAY
 PANELS.
 9. EMERGENCY AND STANDBY POWER STATUS INDICATORS.
 10. A TELEPHONE FOR FIRE DEPARTMENT USE WITH CONTROLLED
 ACCESS TO THE PUBLIC TELEPHONE SYSTEM.
 11. FIRE PUMP STATUS INDICATORS.
 12. SCHEMATIC BUILDING PLANS INDICATING THE TYPICAL
 FLOOR PLAN AND DETAILING THE BUILDING CORE, MEANS OF
 EGRESS, FIRE PROTECTION SYSTEMS, FIRE-FIGHTING
 EQUIPMENT AND FIRE DEPARTMENT ACCESS AND THE LOCATION
 OF FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS, SMOKE
 BARRIERS AND SMOKE PARTITIONS.
 13. WORK TABLE.
 14. GENERATOR SUPERVISION DEVICES, MANUAL START AND
 TRANSFER FEATURES.
 15. PUBLIC ADDRESS SYSTEM, WHERE SPECIFICALLY REQUIRED
 BY OTHER SECTIONS OF THIS CODE.
 16. ELEVATOR FIRE RECALL SWITCH IN ACCORDANCE WITH ASME
 A17.1.
 17. ELEVATOR EMERGENCY OR STANDBY POWER SELECTOR
 SWITCH(ES), WHERE EMERGENCY OR STANDBY POWER IS
 PROVIDED.
  
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2015-12-09 Cont ID  
Sent By wjolin Date 2015-04-29 Time 07:54 Rev Time 0.00
Received By wjolin Date 2015-04-29 Time 15:38 Sent To  
Notes
2015-04-29 15:38:36333 FERN STREET
 PERMIT #15031312
 REVIEW COMMENTS - FIRE DEPARTMENT
 NOTE: UNLESS NOTED OTHERWISE, ALL FIRE/LIFE SAFETY
 REVIEW COMMENTS REFERENCE NFPA 101-THE LIFE SAFETY CODE
 (2012 EDITION WITH FLORIDA AMENDMENTS.)
  
  
 SHEET C-09: PER NFPA 24 SECTION 6.2.1, BACKFLOW
 PREVENTER CONTROL VALVES SHALL BE INSTALLED IN A
 FIRE-RATED ROOM ACCESSIBLE FROM THE EXTERIOR.
  
 SHEET LS-0.1: DEAD-END CORRIDORS IN STORAGE AND
 APARTMENT OCCUPANCIES SHALL NOT EXCEED 20 FEET PER
 TABLE 42.2.5 AND SECTION 30.2.5.4.2 RESPECTIVELY.
  
 SHEET LS-1.0: DEAD-ENDS EXCEED 20 FEET OF TRAVEL IN
 OWNERS' STORAGE #133.
  
 SHEET LS-3.0: CORRIDOR HAS A DEAD-END MEASURING 40
 FEET. NEW APARTMENT DEAD-END CORRIDORS ARE LIMITED TO
 20 FEET PER NFPA 101 SECTION 30.2.5.4.2.
  
 SHEET LS-7.0: POOL CORRIDOR #706 CREATES A DEAD-END
 EXCEEDING 20 FEET IN LENGTH.
  
 SHEET LS-7.0: ALL THREE SECONDARY EXITS FROM COMMON
 ROOM 701.01 HAVE CARD READERS (KEY/TOOL) AT THE EXIT
 ACCESS DOOR LEADING TO THE POOL DECK.
  
 SHEET A2.1.1: EXIT ACCESS CORRIDOR #115 APPEARS TO
 ACTUALLY BE AN EXIT PASSAGEWAY.
  
 SHEET A7.1.1: TWO-HOUR TRASH CHUTE IS PROTECTED BY
 45-MINUTE FIRE RATED DOORS.
  
 SHEET FP2-1-1: THE PLANS INDICATE TWO FIRE MAINS
 SUPPLYING THE FIRE PUMP; HOWEVER, THE THESE TWO MAINS
 REDUCE TO ONE MAIN IMMEDIATELY INSIDE THE BUILDING. THE
 MAINS NEED TO BE REMAIN SEPARATE UNTIL THEY REACH THE
 FIRE PUMP ROOM.
  
 SHEET FA5-1-1: PROVIDE BI-DIRECTIONAL AMPLIFIER/TWO-WAY
 RADIO COMMUNICATION ENHANCEMENT SYSTEMS COMPLYING WITH
 NFPA 72.
  
 SITE: WHERE ARE THE CONSTRUCTION TRAILERS INTENDED TO
 BE LOCATED? PER NFPA 241 SECTION 4.2.2: DETACHMENT
 BETWEEN TEMPORARY STRUCTURES, ADEQUATE TEMPORARY FIXED
 FIRE PROTECTION SYSTEMS, AND PORTABLE EQUIPMENT SHALL
 BE PROVIDED AS REQUIRED BY THE AUTHORITY HAVING
 JURISDICTION.
  
 SITE: PER NFPA 241- STANDARD FOR SAFEGUARDING
 CONSTRUCTION, ALTERATION, AND DEMOLITION OPERATIONS,
 SECTION 4.2: TEMPORARY OFFICES, TRAILERS, AND OTHER
 FACILITIES OF COMBUSTIBLE CONSTRUCTION OR HOUSING
 COMBUSTIBLE CONTENTS SHALL BE SEPARATED FROM ADJACENT
 BUILDINGS, TRAILERS OR STRUCTURES IN ACCORDANCE WITH
 TABLE 4.2.1. PER TABLE 4.2.1:
 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 30 FEET
 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 35 FEET
 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 40 FEET
 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 45 FEET
 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 50 FEET
 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE
 SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET
 **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL
 BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC
 SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE.
  
 NOTE: PER FFPC SECTION 11.9.4 AND FBC SECTION 911.1.5 -
 THE FIRE COMMAND CENTER SHALL COMPLY WITH NFPA 72 AND
 SHALL CONTAIN THE FOLLOWING FEATURES:
 1. THE EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM
 CONTROL UNIT.
 2. THE FIRE DEPARTMENT COMMUNICATIONS SYSTEM.
 3. FIRE DETECTION AND ALARM SYSTEM ANNUNCIATOR.
 4. ANNUNCIATOR UNIT VISUALLY INDICATING THE LOCATION OF
 THE ELEVATORS AND WHETHER THEY ARE OPERATIONAL.
 5. STATUS INDICATORS AND CONTROLS FOR AIR DISTRIBUTION
 SYSTEMS.
 6. THE FIRE-FIGHTER'S CONTROL PANEL REQUIRED BY SECTION
 909.16 FOR SMOKE CONTROL SYSTEMS INSTALLED IN THE
 BUILDING.
 7. CONTROLS FOR UNLOCKING STAIRWAY DOORS
 SIMULTANEOUSLY.
 8. SPRINKLER VALVE AND WATERFLOW DETECTOR DISPLAY
 PANELS.
 9. EMERGENCY AND STANDBY POWER STATUS INDICATORS.
 10. A TELEPHONE FOR FIRE DEPARTMENT USE WITH CONTROLLED
 ACCESS TO THE PUBLIC TELEPHONE SYSTEM.
 11. FIRE PUMP STATUS INDICATORS.
 12. SCHEMATIC BUILDING PLANS INDICATING THE TYPICAL
 FLOOR PLAN AND DETAILING THE BUILDING CORE, MEANS OF
 EGRESS, FIRE PROTECTION SYSTEMS, FIRE-FIGHTING
 EQUIPMENT AND FIRE DEPARTMENT ACCESS AND THE LOCATION
 OF FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS, SMOKE
 BARRIERS AND SMOKE PARTITIONS.
 13. WORK TABLE.
 14. GENERATOR SUPERVISION DEVICES, MANUAL START AND
 TRANSFER FEATURES.
 15. PUBLIC ADDRESS SYSTEM, WHERE SPECIFICALLY REQUIRED
 BY OTHER SECTIONS OF THIS CODE.
 16. ELEVATOR FIRE RECALL SWITCH IN ACCORDANCE WITH ASME
 A17.1.
 17. ELEVATOR EMERGENCY OR STANDBY POWER SELECTOR
 SWITCH(ES), WHERE EMERGENCY OR STANDBY POWER IS
 PROVIDED.
  
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-03-31 Cont ID  
Sent By wjolin Date 2015-03-31 Time 17:05 Rev Time 0.00
Received By wjolin Date 2015-03-31 Time 14:30 Sent To  
Notes
2015-03-31 14:32:03333 FERN STREET
 PERMIT #15031312
 REVIEW COMMENTS - FIRE DEPARTMENT
 NOTE: UNLESS NOTED OTHERWISE, ALL FIRE/LIFE SAFETY
 REVIEW COMMENTS REFERENCE NFPA 101-THE LIFE SAFETY CODE
 (2012 EDITION WITH FLORIDA AMENDMENTS.)
  
  
 SHEET C-09: PER NFPA 24 SECTION 6.2.1, BACKFLOW
 PREVENTER CONTROL VALVES SHALL BE INSTALLED IN A
 FIRE-RATED ROOM ACCESSIBLE FROM THE EXTERIOR.
  
 SHEET LS-0.1: DEAD-END CORRIDORS IN STORAGE AND
 APARTMENT OCCUPANCIES SHALL NOT EXCEED 20 FEET PER
 TABLE 42.2.5 AND SECTION 30.2.5.4.2 RESPECTIVELY.
  
 SHEET LS-1.0: DEAD-ENDS EXCEED 20 FEET OF TRAVEL IN
 OWNERS' STORAGE #133.
  
 SHEET LS-3.0: CORRIDOR HAS A DEAD-END MEASURING 40
 FEET. NEW APARTMENT DEAD-END CORRIDORS ARE LIMITED TO
 20 FEET PER NFPA 101 SECTION 30.2.5.4.2.
  
 SHEET LS-7.0: POOL CORRIDOR #706 CREATES A DEAD-END
 EXCEEDING 20 FEET IN LENGTH.
  
 SHEET LS-7.0: ALL THREE SECONDARY EXITS FROM COMMON
 ROOM 701.01 HAVE CARD READERS (KEY/TOOL) AT THE EXIT
 ACCESS DOOR LEADING TO THE POOL DECK.
  
 SHEET A2.1.1: EXIT ACCESS CORRIDOR #115 APPEARS TO
 ACTUALLY BE AN EXIT PASSAGEWAY.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2016-02-16 Cont ID  
Sent By ccole Date 2016-02-16 Time 12:24 Rev Time 0.00
Received By ccole Date 2016-02-12 Time 09:43 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-02-12 Cont ID  
Sent By shill Date 2016-02-12 Time 08:43 Rev Time 0.00
Received By shill Date 2016-01-22 Time 15:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-12-16 Cont ID  
Sent By lmarchan Date 2015-12-16 Time 16:30 Rev Time 0.00
Received By lmarchan Date 2015-11-13 Time 09:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-10-06 Cont ID  
Sent By cpuell Date 2015-10-06 Time 14:02 Rev Time 0.00
Received By cpuell Date 2015-08-19 Time 14:08 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-08-19 Cont ID  
Sent By lmarchan Date 2015-06-23 Time 09:28 Rev Time 0.00
Received By lmarchan Date 2015-04-14 Time 13:06 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2015-09-28 Cont ID  
Sent By jwitmer Date 2015-09-28 Time 15:41 Rev Time 0.00
Received By jwitmer Date 2015-09-28 Time 15:41 Sent To  
Notes
2015-09-28 15:42:33RECEIPT # 2015-0821-214
 TRACKING # MU-2015-019232-0000
 $1,465,542.10

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-05-19 Cont ID  
Sent By jwitmer Date 2015-05-19 Time 06:27 Rev Time 0.00
Received By jwitmer Date 2015-05-19 Time 06:27 Sent To  
Notes
2015-05-19 06:28:58IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION. PLEASE CONTACT THE P.B. C. IMPACT FEE
 OFFICE TO SEE IF THERE ARE ANY CREDITS THAT CAN BE
 TAKEN FOR STRUCTURES DEMOLISHED.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2016-02-16 Cont ID  
Sent By ccole Date 2016-02-16 Time 11:38 Rev Time 0.00
Received By ccole Date 2016-02-16 Time 11:38 Sent To  
Notes
2016-02-16 12:15:12MECHANICAL PROVISOS:
 PERMIT #15031312
 333 DOWNTOWN
 2/16/16
  
 1) PRIOR TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY,
 AIR DISTRIBUTION SYSTEM TESTING, ADJUSTING AND
 BALANCING IS REQUIRED IN ACCORDANCE WITH SECTION
 503.2.9 FBC-10 ENERGY CONSERVATION.
 503.2.9.1: AIR DISTRIBUTION SYSTEM TESTING, ADJUSTING
 AND BALANCING.
 CONSTRUCTION DOCUMENTS SHALL REQUIRE THAT A WRITTEN
 BALANCE REPORT BE PROVIDED TO THE OWNER OR THE
 DESIGNATED REPRESENTATIVE OF THE BUILDING OWNER FOR
 HVAC SYSTEMS SERVING ZONES WITH A TOTAL CONDITIONED
 AREA EXCEEDING 5000 SQUARE FEET (465 M2). AIR
 DISTRIBUTION SYSTEMS SHALL BE TESTED, ADJUSTED, AND
 BALANCED BY A LICENSED ENGINEER OR A COMPANY OR
 INDIVIDUAL HOLDING A CURRENT CERTIFICATION FROM A
 RECOGNIZED TESTING AND BALANCING AGENCY ORGANIZATION IN
 ACCORDANCE WITH GENERALLY ACCEPTED ENGINEERING
 STANDARDS.
 EXCEPTIONS:
 A) BUILDINGS WITH COOLING OR HEATING SYSTEM CAPACITIES
 OF 15 TONS OR LESS PER SYSTEM MAY BE TESTED AND
 BALANCED BY A MECHANICAL CONTRACTOR LICENSED TO DESIGN
 AND INSTALL SUCH SYSTEM(S).
 B) BUILDINGS WITH COOLING OR HEATING SYSTEM CAPACITIES
 OF 65,000 BTU/H OR LESS PER SYSTEM ARE EXEMPT FROM THE
 REQUIREMENTS OF THIS SECTION.
  
 2) THE PERMIT IS BEING ISSUED WITHOUT APPROVED
 SUBMITTALS FOR MECHANICAL EQUIPMENT AND COMPONENTS
 INCLUDING ROOF TOP HVAC STANDS AND CURBS, EXTERIOR
 LOUVERS, FIRE AND FIRE/SMOKE DAMPERS, OUTSIDE AIR
 MOTORIZED DAMPERS, SMOKE DETECTORS, C0 AND NITROGEN
 DETECTORS, REFRIGERANT PIPING INSULATION, AC EQUIPMENT
 ETC. PLEASE REVIEW THE FOLLOWING:
 DEFERRED SUBMITTAL: 107.3.4.2 DEFERRED SUBMITTALS. FOR
 THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE
 DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT
 SUBMITTED AT THE TIME OF THE
 APPLICATION AND THAT ARE TO BE SUBMITTED TO THE
 BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. DEFERRAL
 OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF
 THE BUILDING OFFICIAL. THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE
 DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS FOR
 REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
 DEFERRED SUBMITTAL. 2010 FBC 107.3.4.1 PRODUCT
 APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE
 DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2016-02-01 Cont ID  
Sent By ccole Date 2016-02-01 Time 07:06 Rev Time 0.00
Received By ccole Date 2016-02-01 Time 07:06 Sent To  
Notes
2016-02-01 07:07:574TH REVIEW: FBC 2014 MECHANICAL
 PERMIT #15031312
 333 DOWNTOWN
 1/29/16
  
 1) PLEASE REFER TO SHEETS M2.1.1 AND A3.3: THE SURVEY
 IS INDICATING AN ALLEYWAY ON THE NORTH SIDE OF THE
 BUILDING SPANNING 14'4" TO THE ADJOINING PROPERTY LINE.
 THE NORTH IS THE LOCATION SIDE FOR MANY AIR INTAKE
 INLETS AND EXHAUST OUTLETS FROM THE GROUND FLOOR TO THE
 SIXTH FLOOR PARKING LEVELS. THERE ARE SEVERAL ISSUES
 HERE THAT MAY HAVE GONE UNNOTICED BY THE DESIGN
 PROFESSIONALS. A) SECTION 401.4 (1) FBC-10 MECHANICAL:
 THIS SECTION IS REQUIRING A 10' CLEARANCE DISTANCE TO
 LOT LINES FOR INTAKE OPENINGS, HOWEVER THE DISTANCE IS
 TO BE MEASURED TO THE CENTER OF THE STREET OR PUBLIC
 WAY. THE ALLEY WAY CENTERLINE IS 7'2" WHICH WOULD MEAN
 THE AIR INLET LOCATIONS DO NOT APPEAR TO MEET THE CODE.
 B) REFER TO SECTION 501.2.1.1: THIS SECTION PROHIBITS
 EXHAUST TO BE DIRECTED ONTO WALKWAYS. IT APPEARS BY THE
 DRAWINGS THAT THE GARAGE AND GENERATOR EXHAUST
 TERMINATIONS ARE NOT IN COMPLIANCE. C) REFER TO
 SECTIONS 401.4(2) AND 401.4.1: IT APPEARS BY THESE CODE
 SECTIONS THAT THE GENERATOR EXHAUST TERMINATION MAY BE
 LOCATED TOO CLOSE TO THE GRAVITY OPENING INTO THE
 GENERATOR ROOM.
 2) REGARDING THE MITSUBISHI PIPING DIAGRAMS, I AM STILL
 SEEING AC 2-5 IN THE DIAGRAM BUT NOT IN THE AC
 SCHEDULE, AND AC 1A-2 IN THE SCHEDULE BUT NOT IN THE
 DIAGRAM.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2015-12-03 Cont ID  
Sent By ccole Date 2015-12-03 Time 10:37 Rev Time 0.00
Received By ccole Date 2015-11-30 Time 11:56 Sent To  
Notes
2015-12-03 10:39:263RD REVIEW 2010 MECHANICAL
 PERMIT #15031312
 12/3/15
  
 1) THE REVISED AC LOAD CALCULATIONS FOR THE MITSUBISHI
 FCU?S FOR CORRIDORS 3RD AND 5TH LEVEL INDICATE 1 TON OF
 COOLING FOR EACH CORRIDOR, HOWEVER THE AC SCHEDULES ARE
 INDICATING 10 TON UNITS HAVE BEEN SELECTED FOR THOSE
 AREAS: PLEASE CLARIFY AND NOTE THAT NO O/A AIR DATA IS
 SHOWN IN THE CALCULATIONS.
 2) THE ENERGY EFFICIENCY FORM 506-2010 WAS SUBMITTED
 AGAIN WITHOUT THE COMPLIANCE CHECKLIST COMPLETED-
 PLEASE COMPLY.
 3) REVISED MITSUBISHI REFRIGERANT PIPING DIAGRAM SHEET
 1-1: A) THE DIAGRAM INDICATES CU-R-2, BUT THE SCHEDULE
 INDICATES CU-R-5. B)THE DIAGRAM INDICATES AC- 2-5 WHICH
 IS NOT IN THE AC EQUIPMENT SCHEDULE. C) AC-1A-2 SHOWN
 IN THE SCHEDULE IS NOT SHOWN IN THE DIAGRAM.
 4) REVISED PIPING DIAGRAM SHEET 1-2: A) CU-R-1 IS SHOWN
 IN THE DIAGRAM/CU-R-4 IN THE SCHEDULE. B) MITSUBISHI
 PKFY MODELS ARE SHOWN IN THE DIAGRAM/PLFY MODELS IN THE
 SCHEDULE.
 5) THE REVISED PLAN INDICATES DRYER BOOSTER FANS TO BE
 USED IN UNITS 2, 3, AND 4. PLEASE NOTE THE WEST PALM
 BEACH FIRE DEPARTMENT PROHIBITS THE USE OF BOOSTER FANS
 IN HIGH-RISE BUILDINGS.
 6) SHEET A2.1.1: PLACE A NOTE ON THE PLAN TO IDENTIFY
 THE LOCATIONS OF THE 2HR. FIRE-RATED DUCT ENCLOSURES,
 AND INDICATE ON WHICH SHEET THE ASSEMBLY DETAILS CAN BE
 FOUND.
 7) SHEET M4.03: NOA #09-0720.01 NOTED IN THE CONDENSER
 UNIT DETAIL IS EXPIRED. PLEASE PROVIDE A CURRENT NOA #.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2015-09-16 Cont ID  
Sent By ccole Date 2015-09-16 Time 17:03 Rev Time 0.00
Received By ccole Date 2015-09-16 Time 17:03 Sent To  
Notes
2015-09-16 17:16:122ND REVIEW: FBC 2010 MECHANICAL
 PERMIT #15031312
 333 FERN ST.
  
 PLEASE REFER TO THE 1ST REVIEW COMMENTS AND THE
 SUBMITTED NARRATIVE RESPONSE.
  
 1) COMMENT #1 FROM THE 1ST REVIEW, REQUEST FOR AC
 CALCULATIONS: THE CALCULATIONS HAVE BEEN SUBMITTED
 HOWEVER, PLEASE REVIEW UPLOADED FILE TITLED "ISIS
 COMMON AREAS" I AM FINDING SOME OF THE SYSTEM TITLES ON
 THE CALCS DO NOT MATCH THE SYSTEM TITLES ON THE
 SCHEDULES I.E. AC 2-2 IS TITLED "ELEVATOR SERVICE" IN
 THE CALCS BUT LISTED AS 2ND LEVEL VESTIBULE IN THE
 SCHEDULE, AC-2-5 IN THE CALCS BUT NOT IN THE SCHEDULES.
 IN ADDITION, I AM NOT FINDING CALCULATIONS FOR RTU-1,
 AND PACU-1 & 2, AND ALL OF THE MITSUBISHI GROUND FLOOR
 SYSTEMS HAVE OVERSIZED HEATING CAPACITIES PER THE
 CALCS- REFER TO SECTION 503.2.2 FBC-10 ENERGY
 CONSERVATION.
 2) COMMENT #2 FROM THE 1ST REVIEW, REQUEST FOR ENERGY
 CALCS: ENERGY EFFICIENCY FORM 506-2010 HAS BEEN
 SUBMITTED, HOWEVER THERE ARE A FEW ISSUES CORRELATING
 THE CALCS WITH THE AC SYSTEMS: A) REFER TO SHEET M4.00
 "SPLIT AC UNIT SCHEDULE"- CU'S 4A & 5A ARE NOT IN THE
 CALCS. B) M4.00 "DUCTLESS SPLIT SYSTEM COMMON AREAS"-
 THE SCHEDULE INDICATES 2.0 TON/20.7 SEER SYSTEMS FOR
 RETAIL, HOWEVER THE CALCS INDICATE RETAIL A (40,800
 BTU'S/19 SEER) & RETAIL B (19,000 BTU'S/20 SEER). C)
 M.400 "DUCTLESS SPLIT SYSTEM COMMON AREAS"- THE COOLING
 AND HEATING CAPACITIES AND SEERS IN THE SCHEDULE DON'T
 MATCH WITH THE CALCS. D) M4.01 "SPLIT AIR CONDITIONING
 UNIT SCHEDULE"- THE COOLING AND HEATING CAPACITIES, THE
 TAG #S, THE SEERS, AND THE LOCATIONS OF THE SYSTEMS AS
 SHOWN IN THE SCHEDULE DO NOT MATCH THE CALCS. PLEASE
 REVIEW AND REVISE ACCORDINGLY, AND COMPLETE THE
 COMPLIANCE CHECKLIST ON PAGE 31- PLACE A CHECK MARK IN
 EACH APPLICABLE BOX.
 3) COMMENT #4 FROM THE 1ST REVIEW: MANUFACTURER'S
 SPECIFICATIONS FROM CARRIER AND MITSUBISHI HAVE BEEN
 UPLOADED FOR REVIEW, HOWEVER MANY OF THE SHEETS SHOWING
 PIPE DIAGRAMS ARE CUT-OFF ON THE RIGHT SIDES OF THE
 PAGES LEAVING INCOMPLETE DIAGRAMS- PLEASE CORRECT. IN
 ADDITION, THE SECOND PART OF THE COMMENT REGARDING PIPE
 PENETRATION SEALS WAS NOT ADDRESSED IN THE RESPONSE
 NARRATIVE.
 4) COMMENT #5: THE O/A CALCULATIONS FOR THE FITNESS
 CENTERS ARE NOT IN COMPLIANCE WITH TABLE 403.3.- 20 CFM
 PER PERSON/0.06 CFM PER SQ. FT. REQUIRED.
 5) COMMENT #9C: I HAVE REVIEWED SHEET E5.2.1 AND DO NOT
 SEE ANY DIRECT CORRELATION BETWEEN THE GENERATOR AND
 THE SMOKE CONTROL SYSTEM. PLEASE INDICATE WHICH OF THE
 CONNECTED METER CENTERS CONTAINS THE FAN CIRCUITRY.
 6) COMMENT #14: REFER TO SHEET M4.07 AND CORRECT THE
 NOTE SPECIFYING CO LEVEL SETPOINT AT 35PPM TO READ
 25PPM PER SECTION 404.1 FBC-10 MECHANICAL.
 7) COMMENT #15: REFER TO TABLE 403.3 FOR FITNESS CENTER
 O/A. THE TABLE INDICATES 20 CFM PER PERSON AND 0.06 PER
 SQ. FT. PLEASE REVISE THE SCHEDULE AND PLANS.
 8) COMMENT #16: PROVIDE SIZING CALCULATIONS FOR THE
 RETURN AIR PLENUM SMOKE EXHAUST SYSTEM SHOWN ON THE
 GROUND FLOOR.
 9) COMMENT #18: THE REVISED PLAN DOES NOT CLEARLY
 INDICATE THE REQUIRED 10' CLEARANCE DISTANCE FOR THE
 GENERATOR EXHAUST TO THE SWITCH GEAR ROOM AIR INTAKE.
 10) COMMENT #20: PROVIDE UL TESTED AND APPROVED
 ASSEMBLY DETAILS FOR CONSTRUCTION OF THE 2HR FIRE-RATED
 ENCLOSURE HOUSING THE POOL EQUIPMENT COMBUSTION AIR
 INTAKE.
 11) COMMENT #25: PLEASE SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE DRYERS, AS PREVIOUSLY REQUESTED.
 12) COMMENT #26: THE LOUVER NOA #10-0921.10 LISTED IN
 THE SCHEDULE HAS EXPIRED. PLEASE PROVIDE A CURRENT NOA
 # AND SUBMITTAL.
 13) COMMENT #27: THE REQUESTED WIND LOAD ENGINEERING
 FOR THE ROOF TOP AC UNITS AND OTHER EQUIPMENT IS
 INCOMPLETE PENDING STRUCTURAL ENGINEER'S DESIGN
 CRITERIA AND DETAILS. PLEASE REFER TO M2-9-1 AND
 PROVIDE TIE-DOWN DETAILS FOR ALL EQUIPMENT AND
 COMPONENTS INCLUDING THE RTU, PACU'S, AC CONDENSERS AND
 STANDS, THE SUPPLY AND EXHAUST DUCTWORK, THE STAIRWELL
 PRESSURIZATION FANS, FAN CURBS, LOUVERS, ETC.
 14) PROVIDE AIR DISTRIBUTION SCHEDULES INDICATING THE
 VARIOUS MAKES AND MODELS OF SUPPLY DIFFUSERS, RETURN
 AND TRANSFER GRILLS ETC. TO BE UISED IN THE COMMON
 AREAS AND THE APARTMENTS
 15) PROVIDE UL TESTED AND APPROVED ASSEMBLY DETAILS FOR
 CONSTRUCTION OF THE 2HR FIRE-RATED ENCLOSURES HOUSING
 THE STAIRWELL PRESSURIZATION DUCTS ON THE GROUND FLOOR.
 16) SMOKE CONTROL RATIONAL ANALYSIS: REFER TO THE
 SECTION ENTITLED "SYSTEM IMPLEMENTATION REQUIREMENTS"
 AND PROVIDE PRODUCT DATA SHEETS FOR THE SMOKE CONTROL
 FANS WITH REVIEW AND APPROVAL STAMPS AND SIGNATURES
 FROM THE ENGINEER OF RECORD. B) PROVIDE ON THE
 MECHANICAL PLANS AIR EQUIPMENT SCHEDULES FOR ALL
 COMPONENTS OF THE SMOKE CONTROL SYSTEM INCLUDING DUCTS,
 DIFFUSERS, RETURN GRILLS, DAMPERS ETC, SMOKE DETECTORS
 ETC. PLEASE INCLUDE NOTES FOR ITEMIZING ALL REQUIRED
 TESTING PROCEDURES AS OUTLINED IN THE RATIONAL ANALYSIS
 INCLUDING LEAK TESTING OF DUCTWORK AND DAMPERS PURSUANT
 TO THE SYSTEM REQUIREMENTS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-06-08 Cont ID  
Sent By ccole Date 2015-06-05 Time 11:01 Rev Time 0.00
Received By ccole Date 2015-05-29 Time 11:01 Sent To  
Notes
2015-06-05 17:13:32 
 1ST REVIEW: FBC 2010 MECHANICAL
 PERMIT #15031312
 5/29/15- 6/5/15
  
 1) PROVIDE AC COOLING AND HEATING CALCULATIONS IN
 ACCORDANCE WITH ASHRAE OR ACCA MANUAL N- SECTION
 503.2.1 FBC-10 ENERGY CONSERVATION
  
 2) PROVIDE ENERGY CALCULATIONS: SUBMIT TWO COPIES OF
 EITHER FORM 502 OR 506- 2010. SEE SECTION 103.2.1 AND
 TABLE 103.2.1 FBC-10 ENERGY CONSERVATION
  
 3) SUBMIT THE FOLLOWING LIST OF MANUFACTURER'S PRODUCT
 DATA SHEETS REQUIRED FOR A COMPLETE MECHANICAL REVIEW.
 PLEASE NOTE THAT ALL EQUIPMENT AND SYSTEM COMPONENTS
 INSTALLED IN BUILDING AREAS SUBJECT TO WIND PRESSURES
 AND WIND BORNE DEBRIS WILL REQUIRE ADDITIONAL SUBMITTAL
 OF VALID FLORIDA PRODUCT APPROVALS AND/OR MIAMI DADE
 NOTICES OF ACCEPTANCE:
 A) FIRE DAMPERS
 B) FIRE/SMOKE DAMPERS
 C) CO2 SENSORS
 D) PACKAGED FRESH AIR AC UNITS
 E) SPLIT SYSTEM AC UNITS (DUCTED AND DUCTLESS PER THE
 SCHEDULES: SHEETS M4-00, M4-01).
 F) RTU-1
 G) VENTILATION FANS AS LISTED IN THE SCHEDULE-
 (M4.01A).
 H) EXHAUST AND AIR INTAKE LOUVERS AND GRILLS
 I) AC ROOF STANDS AND CURBS
 J) POOL AND SPA HEATERS
 K) DRYER AND DRYER VENTS
 NOTE: ALL SUBMITTALS SHALL BE REVIEWED AND APPROVED BY
 THE DESIGN PROFESSIONAL OF RECORD.
  
 4) AS THE PLAN INDICATES EXTENSIVE VERTICAL REFRIGERANT
 PIPING RUNS FROM THE EQUIPMENT ON THE LOW FLOORS TO
 CONDENSING UNITS ON THE ROOF (SUCH AS THE FAN COIL
 UNITS ON THE 3RD AND 5TH FLOORS) DOCUMENTATION OF
 MAXIMUM PIPING RUNS PER EACH SYSTEM MANUFACTURER SHALL
 BE PROVIDED. PLEASE MODIFY THE SCHEDULES TO SHOW THE
 DATA OR PROVIDE A SEPARATE PIPING TABLE IN THE PLANS
 INDICATING THE TYPE OF PIPING, LENGTH OF THE PIPING
 RUN, AND THE TYPE AND AMOUNT OF REFRIGERANT IN EACH
 SYSTEM- TABLE 1103.1 FBC-10 MECH. ADDITIONALLY, THROUGH
 PENETRATION FIRE STOPPING DETAILS ARE REQUIRED FOR
 PIPES RUN THROUGH RATED WALLS AND CEILINGS- PLEASE NOTE
 SHAFT ENCLOSURES MAY BE REQUIRED SECTION 1107.2.2
 FBC-10 MECH.
  
 5) PROVIDE VENTILATION TABLES INDICATING THE REQUIRED
 MINIMUM VENTILATION RATES (O/A AND EXHAUST) FOR ALL
 OCCUPIED ROOMS AND SPACES, AND SYSTEM SIZING
 CALCULATIONS FOR ALL FANS LISTED IN THE SCHEDULE ON
 M4.01- TABLE 403.3 FBC-10 MECHANICAL, AND ASHRAE 62.1.
 CORRELATE THE REQUIRED O/A CFM'S WITH THE CFM AMOUNTS
 SHOWN ON THE AC EQUIPMENT SCHEDULES. PROVIDE
 CALCULATIONS INDICATING HOW O/A IS BEING ADEQUATELY
 PROVIDED FOR THE ELEVATOR CARS, ELEVATOR LOBBIES AND
 VESTIBULES THAT ARE BEING SUPPLIED BY DUCTLESS
 MINI-SPLIT SYSTEMS.
  
 6) PROVIDE SIZING CALCULATIONS FOR ALL COMPONENTS OF
 THE SMOKE CONTROL AND EXHAUST SYSTEMS INCLUDING
 STAIRWAY AND ELEVATOR PRESSURIZATION FANS, THE
 ROOF-MOUNTED SMOKE EXHAUST FAN SEF-1, AND THE ELEVATOR
 HOISTWAY RELIEF LOUVERED OPENINGS (SEE COMMENT 8 FOR
 FURTHER SMOKE CONTROL REQUIREMENTS). CALCULATIONS ARE
 ALSO REQUIRED FOR OTHER FANS LISTED IN THE SCHEDULE NOT
 RELATED TO THE SMOKE CONTROL.
  
 7) REFERENCE SHEET M4.07 AND M2.3.1- M2.6.1: THE SMOKE
 CONTROL SYSTEM DESCRIPTION AND SEQUENCE OF OPERATIONS
 OUTLINE ON M4.07 MAKES NO REFERENCES TO ZONE SYSTEMS
 FOR THE APARTMENTS AND CORRIDORS ON THE 3RD AND 5TH
 FLOORS, NOR ARE ANY SYSTEMS SHOWN FOR SMOKE CONTROL AND
 STAIRWAY/ELEVATOR PRESSURIZATIONS ON THESE FLOORS.
 PLEASE CLARIFY WHY STAIRWELL #3 IS INCLUDED IN THE
 PRESSURIZATION FAN FLOW DIAGRAM ON M4.07.
  
 8) M4.07 SEQUENCE OF OPERATIONS: PLEASE CLARIFY NOTE 2
 UNDER ZONES 2-14. WILL THE TYPICAL O/A FSD?S ON THE
 FLOOR OF THE SMOKE ZONE REMAIN OPEN OR CLOSED AT THE
 CORRIDOR, AND AT THE AC CLOSETS
  
 9) THE DESIGN PROFESSIONAL OF RECORD SHALL SUBMIT A
 RATIONAL ANALYSIS FOR THE PROPOSED SMOKE CONTROL SYSTEM
 IN COMPLIANCE WITH 513 FBC-10 MECHANICAL. PLEASE REVIEW
 AND COMPLY THE FOLLOWING SECTIONS:
  
 513.2 GENERAL DESIGN REQUIREMENTS.
 BUILDINGS, STRUCTURES, OR PARTS THEREOF REQUIRED BY
 THIS CODE TO HAVE A SMOKE CONTROL SYSTEM OR SYSTEMS
 SHALL HAVE SUCH SYSTEMS DESIGNED IN ACCORDANCE WITH THE
 APPLICABLE REQUIREMENTS OF SECTION 909 OF THE FLORIDA
 BUILDING CODE, BUILDING AND THE GENERALLY ACCEPTED AND
 WELL-ESTABLISHED PRINCIPLES OF ENGINEERING RELEVANT TO
 THE DESIGN. THE CONSTRUCTION DOCUMENTS SHALL INCLUDE
 SUFFICIENT INFORMATION AND DETAIL TO DESCRIBE
 ADEQUATELY THE ELEMENTS OF THE DESIGN NECESSARY FOR THE
 PROPER IMPLEMENTATION OF THE SMOKE CONTROL SYSTEMS.
 THESE DOCUMENTS SHALL BE ACCOMPANIED WITH SUFFICIENT
 INFORMATION AND ANALYSIS TO DEMONSTRATE COMPLIANCE WITH
 THESE PROVISIONS
  
 513.3 SPECIAL INSPECTION AND TEST REQUIREMENTS.
 IN ADDITION TO THE ORDINARY INSPECTION AND TEST
 REQUIREMENTS WHICH BUILDINGS, STRUCTURES AND PARTS
 THEREOF ARE REQUIRED TO UNDERGO, SMOKE CONTROL SYSTEMS
 SUBJECT TO THE PROVISIONS OF SECTION 909 OF THE FLORIDA
 BUILDING CODE, BUILDING SHALL UNDERGO SPECIAL
 INSPECTIONS AND TESTS SUFFICIENT TO VERIFY THE PROPER
 COMMISSIONING OF THE SMOKE CONTROL DESIGN IN ITS FINAL
 INSTALLED CONDITION. THE DESIGN SUBMISSION ACCOMPANYING
 THE CONSTRUCTION DOCUMENTS SHALL CLEARLY DETAIL
 PROCEDURES AND METHODS TO BE USED AND THE ITEMS SUBJECT
 TO SUCH INSPECTIONS AND TESTS. SUCH COMMISSIONING SHALL
 BE IN ACCORDANCE WITH GENERALLY ACCEPTED ENGINEERING
 PRACTICE AND, WHERE POSSIBLE, BASED ON PUBLISHED
 STANDARDS FOR THE PARTICULAR TESTING INVOLVED. THE
 SPECIAL INSPECTIONS AND TESTS REQUIRED BY THIS SECTION
 SHALL BE CONDUCTED UNDER THE SAME TERMS AS FOUND IN
 SECTION 909.18 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 513.4 ANALYSIS.
 A RATIONAL ANALYSIS SUPPORTING THE TYPES OF SMOKE
 CONTROL SYSTEMS TO BE EMPLOYED, THEIR METHODS OF
 OPERATION, THE SYSTEMS SUPPORTING THEM AND THE METHODS
 OF CONSTRUCTION TO BE UTILIZED SHALL ACCOMPANY THE
 SUBMITTED CONSTRUCTION DOCUMENTS AND SHALL INCLUDE, BUT
 NOT BE LIMITED TO, THE ITEMS INDICATED IN SECTIONS
 513.4.1 THROUGH 513.4.6.
 513.4.1 STACK EFFECT.
 THE SYSTEM SHALL BE DESIGNED SUCH THAT THE MAXIMUM
 PROBABLE NORMAL OR REVERSE STACK EFFECTS WILL NOT
 ADVERSELY INTERFERE WITH THE SYSTEM?S CAPABILITIES. IN
 DETERMINING THE MAXIMUM PROBABLE STACK EFFECTS,
 ALTITUDE, ELEVATION, WEATHER HISTORY AND INTERIOR
 TEMPERATURES SHALL BE USED.
 513.4.2 TEMPERATURE EFFECT OF FIRE.
 BUOYANCY AND EXPANSION CAUSED BY THE DESIGN FIRE IN
 ACCORDANCE WITH SECTION 513.9 SHALL BE ANALYZED. THE
 SYSTEM SHALL BE DESIGNED SUCH THAT THESE EFFECTS DO NOT
 ADVERSELY INTERFERE WITH ITS CAPABILITIES.
 513.4.3 WIND EFFECT.
 THE DESIGN SHALL CONSIDER THE ADVERSE EFFECTS OF WIND.
 SUCH CONSIDERATION SHALL BE CONSISTENT WITH THE
 WIND-LOADING PROVISIONS OF THE FLORIDA BUILDING CODE,
 BUILDING.
 513.4.4 HVAC SYSTEMS.
 THE DESIGN SHALL CONSIDER THE EFFECTS OF THE HEATING,
 VENTILATING AND AIR-CONDITIONING (HVAC) SYSTEMS ON BOTH
 SMOKE AND FIRE TRANSPORT. THE ANALYSIS SHALL INCLUDE
 ALL PERMUTATIONS OF SYSTEMS? STATUS. THE DESIGN SHALL
 CONSIDER THE EFFECTS OF FIRE ON THE HVAC SYSTEMS.
 513.4.5 CLIMATE.
 THE DESIGN SHALL CONSIDER THE EFFECTS OF LOW
 TEMPERATURES ON SYSTEMS, PROPERTY AND OCCUPANTS. AIR
 INLETS AND EXHAUSTS SHALL BE LOCATED SO AS TO PREVENT
 SNOW OR ICE BLOCKAGE.
 513.4.6 DURATION OF OPERATION.
 ALL PORTIONS OF ACTIVE OR PASSIVE SMOKE CONTROL SYSTEMS
 SHALL BE CAPABLE OF CONTINUED OPERATION AFTER DETECTION
 OF THE FIRE EVENT FOR A PERIOD OF NOT LESS THAN EITHER
 20 MINUTES OR 1.5 TIMES THE CALCULATED EGRESS TIME,
 WHICHEVER IS LESS.
  
 9A) THE DESIGN PROFESSIONAL SHALL PROVIDE EVIDENCE AND
 DOCUMENTATION VERIFYING COMPLIANCE WITH SECTION 513.6.1
 MINIMUM PRESSURE DIFFERENCE ACROSS SMOKE BARRIERS, AND
 513.6.2 MAXIMUM PRESSURE DIFFERENCE ACROSS A SMOKE
 BARRIER BY REQUIRED DOOR-OPENING OR CLOSING FORCES.
  
 9B) THE DESIGN PROFESSIONAL SHALL REVIEW AND APPROVE
 ALL EQUIPMENT AND COMPONENTS OF THE SMOKE CONTROL
 SYSTEM INCLUDING FANS, DUCTS, AUTOMATIC FIRE AND SMOKE
 DAMPERS AND BALANCING DAMPERS PER SECTION 513.10 FBC-10
 MECHANICAL INCLUSIVE OF ALL SUB-SECTIONS.
  
 9C) THE DESIGN PROFESSIONAL SHALL PROVIDE EVIDENCE OF
 COMPLIANCE WITH SECTION 513.11 FOR TWO SOURCES OF POWER
 FOR THE SYSTEM INCLUDING A SECONDARY MEANS BY AN
 APPROVED STANDBY SOURCE, AND MAXIMUM AUTO TRANSFER TIME
 OF 60 SECONDS TO FULL STANDBY POWER FROM PRIMARY
 FAILURE TIME.
  
 10) PROVIDE EQUIPMENT SCHEDULES FOR THE FIRE AND
 FIRE/SMOKE DAMPERS INCLUDING MAKES AND MODELS, UL
 LISTINGS, FIRE-RESISTANCE HOURLY RATINGS, AND LIST
 THEIR PROPOSED INSTALLATION LOCATIONS IN THE BUILDING,
 AND HOW THEY WILL BE ACTUATE- BY FUSIBLE LINK OR
 CONNECTION TO THE SMOKE CONTROL SYSTEM ETC.
  
 11) PROVIDE TYPICAL INSTALLATION DETAILS FOR THE
 DAMPERS INCLUDING ACCESS PANEL LOCATIONS.
  
 12) PROVIDE UL TESTED AND APPROVED THROUGH-PENETRATION
 FIRE STOPPING ASSEMBLIES FOR THE REFRIGERANT PIPING,
 AND AC DUCTS PENETRATING THE VARIOUS RATED WALLS AND
 FLOOR CEILING ASSEMBLIES.
  
 13) SHEET M2-1.1: THE OUTSIDE AIR (O/A) INTAKE INLET
 FOR AC-F IN THE GROUND FLOOR GARAGE/STORAGE WALL IS
 WITHIN THE 10 FT. ALLOWABLE HORIZONTAL DISTANCE TO THE
 DRIVE AREA: PLEASE CORRECT PER SECTION 401.4 FBC-10
 MECH.
  
 14) M2.1.1- M2.6.1: GROUND FLOOR TO 6TH FLOOR GARAGES:
 PROVIDE A SEQUENCE OF OPERATION DIAGRAM FOR THE CO
 ACTUATED EXHAUST SYSTEMS. PROVIDE INSTALLATION DETAILS
 FOR THE SENSORS INCLUDING MOUNTING HEIGHT AFF, AND
 MAXIMUM SPACING. SUBMIT MANUFACTURER?S PRODUCT DATA
 SHEETS REVIEWED AND APPROVED BY THE DESIGN PROFESSIONAL
 OF RECORD- SEE SECTIONS 404.1 AND 404.2 FBC-10 MECH.
 PLEASE NOTE THAT CONTINUOUS VENTILATION IS REQUIRED
 UNLESS THE FANS WILL OPERATE AUTOMATICALLY UPON
 DETECTION OF A CONCENTRATION OF CARBON MONOXIDE OF 25
 PARTS PER MILLION.
  
 15) M2.1.1- M2.6.1- POSITIVE PRESSURE AND MINIMUM O/A
 VENTILATION MUST BE MAINTAINED FOR THE VARIOUS ELEVATOR
 LOBBIES, VESTIBULES, ETC. THAT ARE CONNECTING AT THE
 CENTER OF THE PARKING GARAGES PER SECTION 404.3. HOW
 WILL THIS BE ACCOMPLISHED? THE CURRENT PLAN DOES NOT
 INDICATE ANY O/A DUCTS BRINGING FRESH AIR INTO THESE
 SPACES.
  
 16) M2.1.1: DUCT SMOKE DETECTORS ARE REQUIRED IN THE
 SUPPLY AND RETURN AIR SYSTEMS OF AC-D & AC-E (FITNESS
 CENTER)- SECTION 606.2.2. PLEASE NOTE THAT ALTHOUGH
 AREA SMOKE DETECTORS ARE SHOWN IN THE CENTER ON
 FA2.1.1, THERE ARE NO NOTES ON FA1.00 PERTAINING TO FAN
 SHUT DOWN OF THE UNITS.
  
 17) M2.1.1: RETURN AIR TRANSFERS FROM THE CONFERENCE
 AND WORK ROOMS INTO THE CORRIDORS ARE PROHIBITED PER
 SECTION 601.2. PROVIDE DUCTED RETURNS.
  
 18) M2.1.1: INDICATE THE CLEARANCE DISTANCES FOR THE
 GENERATOR EXHAUST OUTLET AND EF-1-4 TO THE SUPPLY FAN
 INLET SERVING THE SWITCHGEAR ROOM, TO THE PUMP ROOM AIR
 INLET OPENINGS, AND TO THE PUBLIC WALKWAY.
  
 19) M2.3.1 & M2.5.1: IN REFERENCE TO THE NOTE REGARDING
 THE 6"X4" DUCT PENETRATING THE RATED CORRIDOR, PROVIDE
 EVIDENCE THAT THE MATERIAL USED TO FILL THE ANNULAR
 SPACE AROUND THE DUCT PENETRATION MEETS THE ASTM E 119
 OR UL 263 FOR PREVENTION OF PASSAGE OF FLAME AND HOT
 GASES PER SECTION 713.3.1 FBC-10 BUILDING.
  
 20) M2.6.1: A) CLARIFY IF THE COMBUSTION AIR
 CALCULATIONS INCLUDE BOTH THE SPA AND POOL HEATERS, AND
 SUBMIT MANUFACTURER?S SPECIFICATIONS FOR EACH UNIT, THE
 INDUCTION FAN, AND VENT PIPING. B) PROVIDE ENLARGED
 FRONT AND PLAN VIEW DRAWINGS OF THE EQUIPMENT ROOM
 INDICATING CLEARANCE DISTANCES AROUND THE EQUIPMENT AND
 ASSOCIATED POOL AND GAS PIPING, CONTROLS ETC. FOR
 SERVICE ACCESS. C) PROVIDE A VENTING DIAGRAM PER
 MANUFACTURER?S RECOMMENDATIONS. THE DIAGRAM SHALL
 INDICATE THE TYPE AND SIZE OF VENT PIPING, LENGTH OF
 CONNECTORS, HEIGHT OF THE RISER, TOTAL RISE AND RUN OF
 THE FLUE, AND METHOD OF HANGING AND SUPPORT OF THE
 PIPING.- SEE SECTION 503.6, 504 FBC-10 FUEL. D) PROVIDE
 A FIRE DAMPER AND THROUGH PENETRATION FIRE STOPPING FOR
 THE VENT PIPE PENETRATING THE FIRE-RATED WALL. PLEASE
 NOTE ALL SUBMITTALS SHALL BE REVIEWED AND APPROVED BY
 THE DESIGN PROFESSIONAL OF RECORD.
  
 21) M2.6.1) A VESTIBULE PROVIDING A TWO DOORWAY
 SEPARATION IS REQUIRED FOR THE CONNECTION OF THE POOL
 AND SPA HEATER ROOM TO THE ADJACENT GARAGE- SECTION
 305.3.2 FBC-10 FUEL GAS. CORRECT THE PLANS OR PROVIDE
 DOCUMENTATION VERIFYING THE HEATERS HAVE IGNITION
 SOURCES ELEVATED HIGHER THAN18 INCHES ABOVE THE FLOOR-
 SECTION 305.3.
  
 22) M2.6.1: THE LOCATION OF THE COMBUSTION AIR INTAKES
 ADJACENT TO GARAGE PARKING SPACES IS NOT PERMITTED PER
 SECTION 304.12 FBC-10 FUEL GAS. PLEASE PROVIDE
 COMBUSTION AIR FROM THE OUTDOORS.
  
 23) M2.4.1 & M2.6.1: AUTOMATIC SHUT OFF DAMPERS ARE
 REQUIRED FOR THE O/A INTAKES FOR FCU-1 AND FCU-2 PER
 SECTION 503.2.4.4 FBC-10 ENERGY CONSERVATION.
  
 24) M2.7.1: CLARIFY THE PURPOSE OF THE INLINE CORROSIVE
 RESISTANT FAN IN THE CORRIDOR CLOSET AND HOW IT WILL BE
 ACTIVATED. SUBMIT REVIEWED AND APPROVED SPECIFICATIONS,
 AND PROVIDE A UL APPROVED THROUGH-PENETRATION FIRE
 STOPPING DETAIL AND DETAILS FOR HANGING AND SUPPORTING
 THE EXHAUST DUCT.
  
 25) ALL RESIDENTIAL UNITS 3RD 5TH, 7TH, & 8TH- 20TH: A)
 PROVIDE INSTALLATION DETAILS FOR THE AIR HANDLERS IN
 THE SHOWING REQUIRED CLEARANCES INSIDE THE CLOSET PER
 SECTION 603.1.3, AND PRIMARY AND SECONDARY CONDENSATE
 DISPOSAL DETAILS- SECTION 307.2.1 & 307.2.3 FBC-10
 MECH., AND CONNECTION OF THE SUPPLY AND RETURN PLENUMS.
 B) PROVIDE A DETAIL FOR SUPPORT OF THE REFRIGERANT
 PIPING IN THE CLOSETS AND INDICATE THE TYPE AND
 THICKNESS OF THE PIPING INSULATION- PLEASE NOTE THE
 PIPING INSULATION SHALL BE PLENUM-RATED AND APPROVED BY
 THE DESIGN PROFESSIONAL PER SECTION 602.2.1. C)
 REFERENCE FIRESTOPPING DETAIL PER PREVIOUS COMMENT #
 12. B) IN REFERENCE TO NOTE #5 SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE DRYER REVIEWED AND APPROVED.
  
 26) PROVIDE AN EQUIPMENT SCHEDULE FOR ALL THE VARIOUS
 EXTERIOR EXHAUST AND AIR INTAKE LOUVERS AND GRILLS.
 LIST THE MAKES AND MODELS, TYPES AND SIZES, AND INSTALL
 LOCATIONS.
  
 27) MECHANICAL ROOF: PROVIDE WIND LOAD ENGINEERED
 DETAILS FOR TIE-DOWN OF THE ALL THE EQUIPMENT AND
 COMPONENTS INDICATED ON THE PLAN: CONDENSERS, AND
 CONDENSER RACKS, PACKAGE UNITS AND CURBS, SUPPLY AND
 EXHAUST FANS AND CURBS, REFRIGERATION PIPING RACKS AND
 STANDS ETC. INCLUDE SECTION CUTS SHOWING ATTACHMENT
 DETAILS, AND REQUIRED ROOF CLEARANCES FOR THE RACKS,
 AND CURB HEIGHTS.
  
 28) INDICATE HOW THE REFRIGERATION PIPING AND PIPING
 INSULATIONS WILL BE PROTECTED FROM WEATHER AND UV
 DAMAGE.
  
  
 CHRISTOPHER COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  
  
  
  
  
  
  
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2016-01-29 Cont ID  
Sent By tklarge Date 2016-01-29 Time 04:30 Rev Time 0.00
Received By tklarge Date 2016-01-29 Time 03:43 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2015-11-18 Cont ID  
Sent By tklarge Date 2015-11-18 Time 08:32 Rev Time 0.00
Received By tklarge Date 2015-11-17 Time 11:05 Sent To  
Notes
2015-11-17 15:06:531) SUBMIT COMPLETE SPECIFICATIONS/INSTALL MANUAL FOR
 THE TANKLESS WATER HEATER. THE ONE SHEET THAT WAS
 SUBMITTED IS INADEQUATE.WPB AMEND. TO FBC SEC. 107.2.1.
 2) THE WATER CLOSETS IN THE DWELLING UNITS SHALL BE
 LOCATED 18 INCHES FROM AN ADJACENT WALL PER THE FAIR
 HOUSING GUIDELINES, NOT 16"-18" AS NOTED ON THE
 PLANS.THE 18 INCHES FROM THE CENTERLINE OF THE WATER
 CLOSET TO THE WALL IS AN ABSOLUTE MEASUREMENT AND WILL
 ACCOMMODATE A GRAB BAR AND THE SHOULDERS OF A PERSON
 SEATED ON THE TOILET.
 3) SHT.A.6.14.1. - TYPICAL UNIT #15 - THE DOOR ON THE
 ACCESSIBLE SHOWER IN THE MASTER BATH WILL NOT ALLOW A
 PERSON IN A WHEELCHAIR ACCESS TO THE CONTROLS AND THE
 SHOWER DOOR ENCROACHES INTO THE REQUIRED CLEAR FLOOR
 SPACE ADJACENT TO THE SHOWER OPENING PREVENTING ACCESS.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2015-09-15 Cont ID  
Sent By tklarge Date 2015-09-15 Time 13:01 Rev Time 0.00
Received By tklarge Date 2015-09-08 Time 09:06 Sent To  
Notes
2015-09-10 12:50:25PLUMBING:
 1) SHT.A6.2.1 - IDENTIFIES THE UNITS AS 303/503 &
 304/504 IN THE BOTTOM RIGHT HAND CORNER OF THE PLAN BY
 THE DRAWING NUMBER BUT DETAILS #1 & #2 HAVE THE UNITS
 LABELED AS UNITS 302/502. CLARIFY
 2) SHT. A 6.3.1 - IDENTIFIES THE UNITS AS 305/505 &
 306/506 IN THE LOWER RIGHT HAND CORNER OF THE PLAN BY
 THE DRAWING NUMBER BUT DETAILS #1 & #2 HAVE THE UNITS
 LABELED AS 303/503. CLARIFY.
 3) SHT.A 6.10.1 - SHOW THE LENGTH OF THE WING WALL
 ADJACENT TO THE WATER CLOSET IN THE MASTER BATH. THE
 WING WALL SHALL NOT EXCEED 24 INCHES PER THE FHA
 GUIDELINES.
 4) SHT. A 6.11.1 -SHOW THE LENGTH OF THE WING WALL
 ADJACENT TO THE WATER CLOSET IN THE MASTER BATH. THE
 WING WALL SHALL NOT EXCEED 24 INCHES PER THE FHA
 GUIDELINES.
 5) SHT. A 6.15.1 - SHOW THE LENGTH OF THE SHOWER WALL
 ADJACENT TO THE WATER CLOSET IN THE MASTER BATH.THE
 MEASUREMENT SHALL BE TAKEN FROM THE FACE OF THE WALL
 BEHIND THE WATER CLOSET TO THE OFFSET. THIS CANNOT
 EXCEED 24 INCHES.
 6) SHT. P 2.1.1 - THE NOTE AT THE GENERATOR REFERS TO
 "P6-02" - WHAT IS THIS? THERE IS NO SUCH DRAWING IN THE
 PLAN. CLARIFY.
 7) SHT. P 4.1.8. - THERE IS A HORIZONTAL STORM DRAIN
 LINE FROM 2-4" DD'S ( 940 SQ. FT.& 950 SQ. FT.) ON THE
 7TH FLOOR DISCHARGING A TOTAL OF 1890 SQUARE FEET. THE
 HORIZONTAL LINE IS NOT SIZED BUT THIS LINE NEEDS TO BE
 A MINIMUM OF 5". THE MAXIMUM SQUARE FOOTAGE A 4"
 HORIZONTAL STORM DRAIN CAN CARRY AT A 5" DESIGN
 RAINFALL RATE IS 1504 SQUARE FEET. THIS SECTION NEEDS
 TO BE INCREASED TO A MINIMUM SIZE OF 5 INCH.
 8) SHT. P 5.1.2. - ELEVATOR SUMP DETAIL - A FULL OPEN
 GATE VALVE IS REQD. ON THE DOWNSTREM (DISCHARGE) SIDE
 OF THE CHECK VALVE PER 2010 FBC-PLUMBING SEC.712.2.
 9) SUBMIT SPECIFICATIONS FOR THE TANKLESS WATER HEATER.
 WPB AMEND. TO FBC SEC. 107.2.1.
 10) THE DETAIL FOR THE WATER HEATER & RELIEF VALVE
 DISCHARGE ON SHT.P5.1.2 MEETS CODE BUT THE RISERS ON
 SHT.P4.1.10 STILL SHOW THE RELIEF LINES & PAN DRAINS
 INTO THE SAME RISER. PLACE A NOTE ON P4.1.10 TO SEE
 SHT. P5.1.2 FOR RELIEF VALVE & PAN DRAIN DETAIL.
  
 SWIMMING POOL & SPA
 1) INDICATE ON THE PLAN HOW THE OCCUPANT LOAD OF 31
 PERSONS FOR THE POOL WAS CALCULATED.WPB AMEND. TO 2010
 FBC SEC. 107.2.1.
 2) THE POOL & SPA PLANS SHOW THE WASTE WATER
 DISCHARGING TO THE SANITARY SYSTEM. SEE SHEET #367,
 POOL 4 OF 4 & SHT.370 SPA 2. POOL WATER CANNOT
 DISCHARGE TO THE SANITARY OR TO THE STORM SYSTEM PER
 CITY ORDINANCE SEC.90-126 (5) AND SEC. 90-203 (A) ,
 90-204, 90-205 (1).
 3) THE MAXIMUM FILTRATION RATE IN GALLONS PER MINUTE
 PER SQUARE FOOT OF FILTER AREA SHALL BE 0.075 FOR
 CARTRIDGE FILTERS PER 2010 FBC SEC.424.1.6.5.5.
 INDICATE COMPLIANCE ON THE PLANS FOR BOTH THE POOL &
 SPA.
 4) SUBMIT VERIFICATION FROM THE PALM BEACH COUNTY
 HEALTH DEPARTMENT THAT AN APPLICATION FOR AN OPERATING
 PERMIT HAS BEEN SUBMITTED TO THEM FOR THIS POOL & SPA.
 5) PIPING AND INFLUENT, EFFLUENT AND BYPASS VALVES
 WHICH ALLOW ISOLATION OR REMOVAL OF THE HEATER FROM THE
 SYSTEM SHALL BE PROVIDED PER 2010 FBC SEC.424.1.6.5.14.
 SEE RETURN LINE ON THE POOL & SPA.
 6) THE CAPACITY OF THE COLLECTOR TANKS SHALL BE AT
 LEAST 1 MINUTE OF OF THE RECIRCULATED FLOW PER 2010 FBC
 SEC.424.1.6.5.10.5. PLEASE EXPLAIN THE METHOD OF
 ARRIVING AT THE REDUCED SIZE OF THE COLLECTOR TANKS FOR
 THE POOL & SPA..
 7) SIZE ALL THE PIPING TO AND FROM THE POOL HEATERS ON
 THE POOL AND SPA PIPING RISERS.WPB AMEND. TO FBC SEC.
 107.2.1.
 8) SUBMIT MSDS DOCUMENTS FOR THE POOL CHEMICALS.WPB
 AMEND. TO FBC SEC. 107.2.1.
 9) INDICATE THE LOCATION OF THE CHEMICALS ON THE POOL,
 SPA AND BUILDING PLANS.WPB AMEND. TO FBC SEC. 107.2.1.
 10) SHT.370 (SPA 2) SHOWS 50 GAL. ACID & CHLORINE TANKS
 SHARED WITH POOL AND SHT. 367 (POOL 4) SHOWS 30 GAL.
 ACID & CHLORINE TANKS.ARE THESE TWO SEPARATE SETS OF
 TANKS OR SHARED AND WHAT IS THE PROPER CAPACITY?
 CLARIFY.
 11) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE POOL
 HEATERS. THE HEATERS SHALL BE LISTED AND LABELED IN
 ACCORDANCE WITH 2010 FBC-FUEL GAS SEC. 301.3.
 12) SUBMIT MANUFACTURER'S SPECIFICATIONS OF RTHE MAIN
 DRAIN GRATES FOR THE POOL AND SPA.WPB AMEND. TO FBC
 SEC. 107.2.1, ANSI/APSP-7 SEC.4.5.
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  
  
 REVIEW NOT COMPLETE

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-06-23 Cont ID  
Sent By tklarge Date 2015-06-23 Time 14:19 Rev Time 0.00
Received By tklarge Date 2015-06-06 Time 11:24 Sent To  
Notes
2015-06-14 07:35:491)THE BREAK ROOM SINK ON THE FIRST FLOOR ( RM. 125A)
 SHALL COMPLY W/ FL. ACCESSIBILITY CODE SEC. 212 AND
 606.
 2)SUPPLY A KEYNOTE LEGEND ON THE PLANS FOR THE HEXAGON,
 CIRCLE, SQUARE AND DIAMOND SYMBOLS. WPB AMEND. TO 2010
 FBC SEC. 107.2.1.
 3)THE SWIMMING POOL AND DECK ARE COVERED UNDER THE FAIR
 HOUSING ACT WHICH ONLY REQUIRES ACCESS TO THE POOL
 AREA. HOWEVER, IF THE CONDOMINIUM ASSOCIATION ELECTS
 THAT THE COMMUNITY ROOM, POOL AND POOL DECK TO BE
 RENTED OUT FOR PARTIES TO THE PUBLIC, THEN FULL
 COMPLIANCE WITH SEC. 1009 OF THE FL. ACCESSIBILITY CODE
 IS REQUIRED.
 4)INDICATE ON THE STORM DRAINAGE PLANS THE RAINFALL
 RATE THAT WAS USED FOR THE SIZING OF THE STORM DRAINAGE
 SYSTEM. THE RAINFALL RATE FOR THIS AREA IS 5 INCHES PER
 HOUR. FBC 1503.4, FPC FIGURE 1106.1.
 5)SHT. A7.5.2 -THE TOP OF THE ROOF DRAIN STRAINER SHALL
 EXTEND NO LESS THAN 4 INCHES ABOVE THE ROOF SURFACE
 IMMEDIATELY ADJACENT TO THE ROOF DRAIN PER 2010 FPC
 SEC.1105.1.
 6)SHEET P5.1.2- SUBMIT DETAILS FOR THE FIRESTOP SYSTEM
 FOR THE TUB DRAINS IN THE FLOOR SLABS. FBC 713.4.1.1.1,
 713.4.1.1.2.
 7)SHT. LS-0.2 - DETAIL 1 THE MINIMUM AND MAXIMUM
 HEIGHTS ARE INCORRECT FOR THE GRAB BAR BACKING FOR THE
 WATER CLOSETS.. THE BOTTOM OF THE REINFORCEMENT SHALL
 BE AT 32 INCHES MAXIMUM ABOVE THE FLOOR AND THE TOP OF
 THE REINFORCEMENT SHALL BE LOCATED 38 INCHES MINIMUM
 PER DETAIL # 3 OF THE FHA GUIDELINES.
 8)SHT. LS-0.2 - BATHTUB- BACK WALL - THE REINFORCEMENT
 SHALL BE LOCATED A MAXIMUM OF 6 INCHES FROM THE SIDE
 WALLS ON BOTH SIDES. FHA FIGURE # 4.
 9)SHT. LS-0.2 - THE TOP OF THE REINFORCEMENT ON THE
 BACK WALL OF THE TUB SHALL BE LOCATED A MINIMUM OF 38
 INCHES ABOVE THE FLOOR, NOT 38 INCHES MAXIMUM AS SHOWN.
 FHA FIGURE #4.
 10)SHT. LS-0.2- THE BOTTOM OF THE REINFORCEMENT AT THE
 FOOT OF THE TUB SHALL BE AT 32 INCHES MAXIMUM AND THE
 TOP SHALL BE AT 38 INCHES MINIMUM ABOVE THE FINISH
 FLOOR. FHA FIGURE #4. THE SAME APPLIES TO THE
 REINFORCEMENT AT THE HEAD OF THE TUB.
 11)SHT. LS-0.2 - THE REINFORCEMENT FOR THE FOR THE
 SHOWER SIDES SHALL BE LOCATED 32 INCHES MAXIMUM TO THE
 BOTTOM AND THE WIDTH OF THE REINFORCEMENT SHALL BE A
 MINIMUM OF 6 INCHES WIDE. FHA FIGURE #5.
 12)SHT.LS-0.2 - FHA GENERAL NOTES - ACCESSIBLE UNITS
 NOTE 4 (D) REFERS TO A LAVATORY DETAIL THIS SHEET.
 THERE IS NO DETAIL SHOWING THE DISTANCE OF LAVATORY TO
 A WALL. CLARIFY.
 13)SHT.A2.1.1 - PLAN NOTES #1- STATES SEE SHT.G1.1 FOR
 GENERAL NOTES AND SYMBOLS. THERE IS NO SUCH SHEET IN
 THE PLANS. CLARIFY.
 14)ON THE ENLARGED PLANS FOR THE UNITS, SHOW THE
 REQUIRED CLEAR FLOOR SPACE FOR THE FIXTURES PER THE FHA
 IN THE ACCESSIBLE BATHROOMS AND THE KITCHEN. IN
 ADDITION, SHOW WHICH BATHROOM COMPLIES WITH THE FHA AS
 THE ADAPTABLE BATHROOM FOR THE UNITS WITH MORE THAN ONE
 BATHROOM.
 15)INDICATE THE LENGTH OF THE SHOWERS ON THE PLANS. WPB
 AMEND. TO 2010 FBC SEC. 107.2.1.
 16)SHOW THE REQUIRED 30 INCH BY 48 INCH CLEAR FLOOR
 SPACE ADJACENT TO THE SHOWER IN THE ADAPTABLE UNITS.
 FHA GUIDELINES REQ. #7.
 17) SHT.P2.1.1 -IDENTIFY THE SPECIFIC ELECTRICAL AND
 MECHANICAL DRAWINGS WHERE THE ADDITIONAL INFORMATION
 FOR THE GENERATOR IS LOCATED. WPB AMEND. TO 2010 FBC
 SEC. 107.2.1.
 18)SHT.P2.1.1 SHOWS A 4" FIRE HUB DRAIN IN THE
 STAIRWELLS. 2010 FBC SEC. 1022.4 LIMITS PENETRATIONS IN
 THE EXIT ENCLOSURE TO ITEMS THAT SERVING THE EXIT
 ENCLOSURE.
 19)SUBMIT A KEYNOTE LEGEND FOR THE SQUARES, CIRCLES AND
 DIAMONDS WITH NUMBERS LOCATED WITHIN THE SYMBOLS.
 20)THE ROOM IN WHICH THE POOL HEATERS ARE LOCATED SHALL
 COMPLY WITH THE 2010 FUEL GAS CODE SEC. 305.3.2.
 21)SUBMIT A WATER RISER FOR UNITS 303 & 503. ALTHOUGH
 THESE UNITS ARE A MIRROR OF UNITS 304 & 504, A WATER
 RISER IS REQUIRED PER THE CITY OF WPB ADMIN. AMEND. TO
 2010 FBC SEC. 107.3.5.1.3.
 22)A RELIEF VENT IS REQUIRED ON THE SOIL AND WASTE
 STACKS THAT ARE MORE THAN 10 BRANCH INTERVALS. THE
 RELIEF VENT SHALL BE PROVIDED AT EACH TENTH INTERVAL
 INSTALLED, BEGINNING WITH THE TOP FLOOR PER 2010 FPC
 SEC. 914.1, 914.2.
 23)SHT. P4.1.1. - SUBMIT THE LENGTH OF THE BRANCH VENT
 CONNECTING STACKS #2, #3, & #4 TO STACK # 46. BRANCH
 VENTS EXCEEDING 40 FEET IN DEVELOPED LENGTH SHALL BE
 INCREASED BY ONE NOMINAL SIZE FOR THE ENTIRE DEVELOPED
 LENGTH OF THE VENT PIPE PER 2010 FPC SEC. 916.4.1.THE
 SAME APPLIES TO THE BRANCH VENT CONNECTING STACKS #13.
 14, 15 & 16 AND STACKS #47, 48, 49, 50. IN ADDITION,
 ALSO LOOK AT SHT. P4.1.5.
 24)SHT. P4.1.1.1 - STACKS #29 & 13 - INDICATE ON THE
 RISER WHERE THE STACKS PENETRATES THE UPPER FLOORS.WPB
 ADMIN. AMEND. TO 2010 FBC SEC. 107.2.1.
 25) SHT.P4.1.3. - RISERS 24, 25, 26 - THE NOTE STATES
 SEE SHT. P4.1.3 FOR CONTINUATION MATCH POINT D. THERE
 IS NO MATCH POINT "D" ON P4.1.3. CLARIFY.
 26)SHT.P4.1.3 ? STACK #48 AT THE 6TH FLOOR LEVEL- SHOWS
 A RISER COMING OFF THE HORIZONTAL DRAIN AND CONNECTING
 RIGHT BACK INTO THE STACK VENT. CLARIFY. THIS AREA WAS
 NOTED WITH A MARKUP.
 27)SHT.P4.1.5 - DOMESTIC WATER BOOSTER DETAIL SHOWS A 6
 INCH SUPPLY AND A 6 INCH DISCHARGE LINE AND THE WATER
 RISER SHOWS 5 INCH SUPPLY AND DISCHARGE. CLARIFY.
 28)SUBMIT INFORMATION AS TO HOW THE CONTROL OF THERMAL
 EXPANSION WILL BE ACCOMPLISHED IN ACCORDANCE WITH 2010
 FPC SEC.607.3, 607.3.2.
 29)SHT. P4.1.7 SHOWS A 4 INCH ROOF DRAIN COLLECTING
 1608 SQUARE FEET OF ROOF AREA. THE MAXIMUM SQUARE
 FOOTAGE THAT A HORIZONTAL 4 STORM DRAIN CAN CARRY AT
 1/8 INCH PER FOOT AT A 5 INCH RAINFALL RATE IS 1504
 SQUARE FEET PER TABLE 1106.3 OF 2010 FPC.
 30)SHT.P4.1.7. SHOWS A 5 INCH ROOF DRAIN COLLECTING
 2840 SQUARE FEET OF ROOF AREA. THE MAXIMUM SQUARE
 FOOTAGE THAT A HORIZONTAL 5" STORM DRAIN CAN CARRY AT
 1/8? PER FOOT AT A 5 INCH RAINFALL RATE IS 2672 SQUARE
 FEET.
 31)SHT. P4.1.9 - GAS RISER - SUPPLY THE LOW PRESSURE
 GAS INFORMATION FOR THE GENERATOR. THE RISER DIAGRAM
 SHOWS A PRESSURE REGULATOR AT THE GENERATOR.
 32)SHT.P4.1.9 - THE TOTAL SYSTEM LOAD INFO IS
 CONFUSING; THE GENERATOR LOAD IS INCLUDED IN THE TOTAL
 LOAD BUT THE PIPING IS SHOWN AS METALLIC PIPE BUT THE
 GENERATOR IS BEING SUPPLIED BY PE PIPE. CLARIFY.
 33)SHT. P4.1.10 - THE PLAN SHOWS THE T & P LINES
 CONNECTING INTO THE SAME LINE AS THE PAN DRAINS. THESE
 TWO SYSTEMS SHALL BE 2 INDEPENDENT AND SEPARATE SYSTEMS
 PER THE 2010 FPC SEC. 504.6(4).
 34)THE DISCHARGE PIPE FOR A TEMPERATURE & PRESSURE
 RELIEF VALVE SHALL COMPLY WITH 2010 FPC SEC. 504.6,
 1-13.
 35)SHT. P5.1.2 - SUBMIT MANUFACTURER'S SPECIFICATIONS
 FOR THE OIL GUARD PUMP SYSTEM.
 36)A WATER HAMMER ARRESTOR SHALL BE INSTALLED ON THE
 FLUSHING RING FOR THE TRASH CHUTE PER 2010 FPC SEC.
 604.9.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status N Date 2016-02-12 Cont ID  
Sent By shill Date 2016-02-12 Time 08:38 Rev Time 0.00
Received By shill Date 2016-02-12 Time 08:37 Sent To  
Notes
2016-02-12 08:38:43ROOF PERMIT APPLICATION AND ROOF PRODUCT APPROVALS
 REVIEWED BY DOR ARE TO BE SUBMITTED PRIOR TO
 INSTALLATION
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2015-05-19 Cont ID  
Sent By jwitmer Date 2015-05-19 Time 06:26 Rev Time 0.00
Received By jwitmer Date 2015-05-19 Time 06:26 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2016-02-26 Cont ID  
Sent By shill Date 2016-02-26 Time 14:42 Rev Time 0.00
Received By shill Date 2016-02-26 Time 14:41 Sent To  
Notes
2016-02-26 14:42:52SEE 15030731 (SHELL PERMIT), ORIGINAL SIGNED AND SEALED
 SURVEY AND SOILS SUBMITTED
 THRESHOLD INSPECTION PLAN RECEIVED VIA EMAIL AND SENT
 TO LMARCHANT/CPUELL
  
 PEDDS FOR FIRST SUBMITTAL DATED 4/2/2015 - OK
 PEDDS FOR FIRST RESUBMITTAL DATED 8/18/2015 - OK
 PEDDS FOR SECOND RESUB DATED 10/26/15 - OK
 PEDDS FOR THIRD RESUB DATED 1/21/16 - OK
 PEDDS FOR FOURTH RESUB DATED 2/10/16 - OK
  
 PROVISOS:
  
 SUBMIT SIGNATURE DOCUMENT OR ORIGINAL ACOUSTIC REPORT
 (PREPARED BY JOE CUSCHIERI, PE) OR SEND A DIGITALLY
 SIGNED REPORT VIA EMAIL.
  
 SUBMIT EITHER AN ORIGINAL "GS&P CODE COMPLIANCE LETTER
 06-09-15.PDF" IN HARD COPY FORM OR SEND THE LETTER,
 DIGITALLY SIGNED, VIA EMAIL.
  
 POOL/SPA PAGES HAVE BEEN VOIDED; SEPARATE PERMIT
 REQUIRED (NO REVIEWS DONE FOR POOL 1-4, SPA 1-3; NO
 PEDDS SUBMITTED)
  
 ACCESS CONTROL (SE1 THROUGH SE7) HAVE BEEN VOIDED;
 SEPARATE PERMIT REQUIRED (NOTE THAT DAVID FAERMAN, PE'S
 TITLE BLOCK IS NOT ON THE SHEETS. THE PEDDS SUBMITTED
 FOR SE1 - SE7 PREPARED BY DAVID FAERMAN, PE INCLUDE THE
 STATEMENT (ON THE "SIGNATURE DOCUMENT" PAGE):
 WARNING: THIS SIGNATURE DOCUMENT SIGNS NO FILES!!!!
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2016-02-26 Cont ID  
Sent By shill Date 2016-02-26 Time 10:18 Rev Time 0.00
Received By shill Date 2016-02-24 Time 18:37 Sent To  
Notes
2016-02-24 18:39:58****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. I WAS UNABLE TO LOCATE THE THRESHOLD INSPECTION PLAN
 IN THE PEDDS SUBMITTED, AND THE DRAWING INDEX DOES NOT
 INDICATE ON WHICH SHEET THIS CAN BE FOUND.
  
 PLEASE ADVISE; IS THIS ON ONE OF THE STRUCTURAL SHEETS?
 OR WAS AN ORIGINAL SUBMITTED WITH THE SHELL PERMIT?
  
 ALTERNATIVELY, THIS DOCUMENT CAN BE SENT VIA EMAIL WITH
 A DIGITAL SIGNATURE.
  
 2. AFTER THE THRESHOLD INSPECTION PLAN ISSUE IS
 RESOLVED, THE SIGNATURE REVIEW WILL BE PASSED WITH THE
 FOLLOWING NOTES:
  
 SEE 15030731 (SHELL PERMIT), ORIGINAL SIGNED AND SEALED
 SURVEY AND SOILS SUBMITTED
  
 PEDDS FOR FIRST SUBMITTAL DATED 4/2/2015 - OK
 PEDDS FOR FIRST RESUBMITTAL DATED 8/18/2015 - OK
 PEDDS FOR SECOND RESUB DATED 10/26/15 - OK
 PEDDS FOR THIRD RESUB DATED 1/21/16 - OK
 PEDDS FOR FOURTH RESUB DATED 2/10/16 - OK
  
 PROVISOS:
  
 SUBMIT SIGNATURE DOCUMENT OR ORIGINAL ACOUSTIC REPORT
 (PREPARED BY JOE CUSCHIERI, PE) OR SEND A DIGITALLY
 SIGNED REPORT VIA EMAIL.
  
 SUBMIT EITHER AN ORIGINAL "GS&P CODE COMPLIANCE LETTER
 06-09-15.PDF" IN HARD COPY FORM OR SEND THE LETTER,
 DIGITALLY SIGNED, VIA EMAIL.
  
 POOL/SPA PAGES HAVE BEEN VOIDED; SEPARATE PERMIT
 REQUIRED (NO REVIEWS DONE FOR POOL 1-4, SPA 1-3; NO
 PEDDS SUBMITTED)
  
 ACCESS CONTROL (SE1 THROUGH SE7) HAVE BEEN VOIDED;
 SEPARATE PERMIT REQUIRED (NOTE THAT DAVID FAERMAN, PE'S
 TITLE BLOCK IS NOT ON THE SHEETS. THE PEDDS SUBMITTED
 FOR SE1 - SE7 PREPARED BY DAVID FAERMAN, PE INCLUDE THE
 STATEMENT (ON THE "SIGNATURE DOCUMENT" PAGE):
 WARNING: THIS SIGNATURE DOCUMENT SIGNS NO FILES!!!!
  
  
2016-02-24 12:42:37PEDDS GIVEN TO SKENNEDY

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2016-02-18 Cont ID  
Sent By shill Date 2016-02-18 Time 13:55 Rev Time 0.00
Received By shill Date 2016-02-16 Time 13:48 Sent To  
Notes
2016-02-18 13:58:29****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 THE PEDDS SUBMITTED TO DATE DO NOT START WITH THE
 EARLIEST VERSION OF THE PLANS SUBMITTED. PEDDS HAVE
 BEEN SUBMITTED THREE TIMES, AND AT QUICK GLANCE IT
 APPEARS THAT EACH PEDDS SUBMITTAL HAS BEEN FOR THE
 SHEETS IN EACH RESUBMITTAL. PEDDS FOR REVIEW CYCLES 1
 AND 2 HAVE NOT BEEN SUBMITTED. FOR AN EXAMPLE, PLEASE
 SEE THE SCREEN SHOT (SENT VIA EMAIL TO
 [email protected]) OF THE CIVIL DRAWINGS (C01 THROUGH
 C12, VARIOUS SUBMITTAL DATES) AND THE PEDDS SUBMITTED
 FOR THE CIVIL DRAWINGS (SHEETS C5, 6, 9 AND 12 ONLY).
 THE ARCHITECTURAL PEDDS ARE ALSO INCOMPLETE. I HAVE
 CONFIRMED THAT OUR OFFICE HAS NOT RECEIVED ANY PEDDS
 PRIOR TO 12/9/2015.
  
 IN THE PROJECTDOX "SIGNATURE" FOLDER, DOCUMENTS WHICH
 APPEAR TO BE RELATED TO PEDDS WERE UPLOADED ON
 4/7/2015. PEDDS ARE REQUIRED TO BE ORIGINAL SIGNED,
 SEALED, DATED DOCUMENTS AND ARE TO BE COMPLETE. THE
 DOCUMENTS UPLOADED ARE INCOMPLETE AS THEY DO NOT
 INCLUDE THE PAGE NAMES SEALED. FOR AN EXAMPLE OF THIS,
 PLEASE SEE THE SCREEN SHOTS AT THE BOTTOM OF THIS
 EMAIL.
  
 PLEASE PROVIDE THE MISSING PEDDS (OR OTHER SIGNATURE
 DOCUMENTS) TO THE BUILDING DIVISION FOR REVIEW. IF YOU
 NEED ASSISTANCE, PLEASE FEEL FREE TO CONTACT ME AT YOUR
 CONVENIENCE.
  
 2/18/16 PEDDS SUBMITTALS DATED 1/25/16, 12/9/15,
 2/16/16 ROUTED TO PEDDS BOX
  
2016-02-17 13:45:582/17/16 PEDDS GIVEN TO SHILL
2016-01-25 16:37:541.25.16 NEW PEDDS RECEIVED, WAITING ON PLAN REVIEW TO
 BE COMPLETED. LEM
2015-12-09 11:15:25PEDDS SUBMITTED 12/9/15 WAITING ON FULL PASSED PLAN
 REVIEW TO GIVE TO SKENNEDY, IN THE PEDDS BOX AT THE
 MOMENT

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status P Date 2016-02-12 Cont ID  
Sent By shill Date 2016-02-12 Time 08:37 Rev Time 0.00
Received By shill Date 2016-02-11 Time 12:48 Sent To  
Notes
2016-02-11 13:09:20INSPECTOR - ARDAMAN & ASSOCIATES (ROBERTO BALBIS),
 JERALD SMITH
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2015-12-14 Cont ID  
Sent By aaponte Date 2015-12-14 Time 16:09 Rev Time 0.00
Received By aaponte Date 2015-12-14 Time 16:09 Sent To  
Notes
2015-12-14 16:10:09PROVISO:
 1. NORTH AND EAST GARAGE ELEVATIONS SHALL INCLUDE A
 MURAL.
 2. FERN STREET SHALL FOLLOW CITY'S FERN STREETSCAPE
 DESIGN.

Review Stop Z ZONING
Rev No 2 Status F Date 2015-10-06 Cont ID  
Sent By aaponte Date 2015-10-06 Time 08:45 Rev Time 0.00
Received By aaponte Date 2015-10-06 Time 08:45 Sent To  
Notes
2015-10-06 13:07:57PREVIOUS COMMENTS:
 1. SATISFIED.
 2. PLEASE CONSIDER THE POSIBILITY OF MOVING THE MEDIAN
 ON DIXIE HWAY PARKING OUT AS MUCH AS POSSIBLE,
 MAINTAINING TURNING RADIUS TO ACCESS GARAGE, TO PROVIDE
 A WIDER CLEAR SIDEWALK.
 3. STRUCTURAL SOIL SHALL BE INTALLED AROUND RELOCATED
 OAK TREE AND NEW TREE ON DIXIE HWAY.
 4. NOT ADDRESSED. PLANTING AREA NOT INDICATED ON
 DRAWINGS.
 5. PLEASE INDICATE THE LOCATION OF THE TILT GATE
 DETAILS TO CONFIRM REQUIRED SCREENING BY DAC.
 6. SATISFIED.
 7. DAC APPROVAL REQUIRED ENHANCED MATERIALS AT GROUND
 FLOOR. PLEASE INDICATE WHAT ARE THE PROPOSED ENHANCE
 MATERIALS ON THE GROUND.
 8. SATISFIED.
 9. SATISFIED.
 10. DISCREPANCY STILL EXISTING BETWEEN DRAWINGS.
 11. NOT SATISFIED.
 12. EASEMENTS WILL BE NECESSARY FOR ENTRANCE CANOPY,
 GARAGE TRELLIS, BALCONIES AND POOL DECK. PLEASE PREPARE
 LEGAL DESCRIPTION AND SKETCH FOR EACH OF THE ELEMENTS
 ENCROACHING INTO THE ROW. CITY COMMISSION APPROVAL
 REQUIRED.
 ADDITIONAL COMMENTS:
 13. DRAWINGS INDICATE A NEW WATER MAIN ON THE SIDEWALK.
 PLEASE VERIFY THERE IS NOT CONFLICT WITH THE PROPOSED
 STREET TREES ALONG FERN STREET ACCORDING TO THE REVISED
 DESIGN.
 14.STOP BARS FOR GARAGE EXIST SHALL BE INSIDE FRONTAGE
 LINE. ADDITIONAL STOP BARS CAN BE PLACED AT THE ROADWAY
 APPROACH IF NEEDED.
 15. CTIY COMPLETED THE DESIGN FOR THE FERN STREET
 PROJECT. PLEASE REVISE STREETSCAPE TO CONFORM TO FINAL
 CITY DESIGN.
 16. SITE PLAN SHOWS 2 IN-BOUND LANES AND 1-OUT- BOUND
 LANE ON DIXIE HWAY. ORIGINAL APPROVAL HAD 2 IN-BOUND
 LANES AND 1-OUT-BOUND. PLEASE CORRECT.
 17. DIXIE HWAY DRIVEWAY SHALL BE ADJUSTED TO PROVIDE
 ENOUGH SPACE FOR THE 2 IN-BOUND LANES. REDUCE THE
 OUT-BOUND LANE TO 10.5' TO ALLOW ADDITIONAL SPACE FOR
 IN-BOUND LANES.
 18. DECORATIVE ALUMINUM TRELLIS ABOVE GARAGE ENTRANCE
 SHALL BE LOWERED TO MEET THE AWNING HEIGHT OR CLOSE TO
 IT.
 19. A MAINTENANCE AGREEMENT WILL BE NECESSARY FOR THE
 MAINTENANCE OF ALL THE STREETSCAPE ON DIXIE HWAY AND
 FERN STREET.
 20. PLEASE INCLUDE THE FOLLOWING INFORMATION IN THE
 SITE PLAN SHEET SP1.1:
 TDR CALCULATION:
 TOTAL GSF= 293,296SF
 TOTAL GSF FLOOR 1-5 (ZONING BY RIGHT)= 84,241SF
 TOTAL GSF FLOOR 6-16 = 209,055SF
 TDRS FROM PARK (12,500SF) = 62,500SF
 ADDITIONAL TDRS NEEDED= 146,555SF
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.

Review Stop Z ZONING
Rev No 1 Status F Date 2015-06-15 Cont ID  
Sent By aaponte Date 2015-06-15 Time 16:06 Rev Time 0.00
Received By aaponte Date 2015-06-15 Time 16:06 Sent To  
Notes
2015-06-15 16:31:201. PARKING ENTRANCES SHALL BE FLUSHED WITH THE SIDEWALK
 LEVEL.
 2. PROPOSED MEDIAN ON DIXIE HWAY PARKING ENTRANCE SHALL
 BE MOVED CLOSER TO STREET TO ALLOW SIDEWALK TO BE AT
 LEAST8 FEET WIDTH AT THE DRIVEWAY CROSSING.
 3. STRUCTURAL SOIL SHALL BE INSTALLED AROUND THE
 RELOCATED OAK TREE AND NEW TREE ON DIXIE HIGHWAY.
 4. INDICATED CONFEDERATE JASMIN ON THE WALL DOES NOT
 SEEM TO HAVE AN ASSOCIATED PLANTING AREA AT GROUND
 LEVEL. PLANTING SHALL BE AT LEAST 24" IN WIDTH TO
 PROVIDE ENOUGH GROUND FOR THE JASMIN TO GROW 50 FEET
 VERTICALLY.
 5. DAC APPROVAL REQUIRED A DECORATIVE SCREENING FOR THE
 FERN STREET GARAGE AND THE BACK FLOW PREVENTOR. PLEASE
 INDICATE HOW IS THAT SCREENING.
 6. PLEASE CLARIFY ELEVATION TO INDICATE ELEMENTS ON THE
 FRONTAGE LINE AND ELEMENTS BEHIND, ON INTERIOR
 ELEVATIONS.
 7. DAC APPROVAL REQUIRED ENHANCED MATERIALS AT GROUND
 FLOOR.
 8. PARKING SPACES AT GROUND LEVEL CAN BE COMPACT, BUT
 THEY SHALL HAVE AN EXTRA FOOT IF A COLUMN IS IN ONE
 SIDE OF THE SPACE.
 9. DRIVE AISLE SHALL BE 24 FEET IN WIDTH WHEN 90 DEGREE
 PARKING NEXT TO IT. AISLE CLOSER TO ENTRANCE IS ONLY 22
 FEET. REDUCE SPACES TO 16 FEET LONG.
 10.ALLEY EXIT FROM GROUND FLOOR PARKING SHOWS TWO
 TRAVEL LANES ON SP1-1, BUT ONLY ONE OF CIVIL DRAWINGS.
 11. DAC VARIANCE REQUIRED ADDITIONAL ARCHITECTURAL
 TREATMENT ON NORTH AND EAST GARAGE ELEVATION. PROPOSED
 DESIGN ON BUILDING PERMIT HAS LESS ELEMENTS THAN
 ORIGINAL SUBMITTAL PRESENTED TO DAC.
 12. PLEASE INDICATE PROPERTY LINE ON ALL FLOOR PLANS
 AND ELEVATIONS TO DETERMINE NEED FOR AERIAL EASEMENTS.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved