Plan Review Details - Permit 15031311
Plan Review Stops For Permit 15031311
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2015-04-06 Cont ID  
Sent By jwitmer Date 2015-04-06 Time 12:00 Rev Time 0.00
Received By jwitmer Date 2015-04-06 Time 11:34 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-05-04 Cont ID  
Sent By rlecky Date 2015-05-04 Time 12:15 Rev Time 0.00
Received By rlecky Date 2015-05-04 Time 11:50 Sent To  
Notes
2015-05-04 12:15:53GFCI PROTECTION REQUIRED IN KITCHEN AREA. NEC 210.8

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-04-03 Cont ID  
Sent By pleduc Date 2015-04-03 Time   Rev Time 0.00
Received By pleduc Date 2015-04-01 Time 10:25 Sent To  
Notes
2015-04-03 12:05:25THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 1) SHEET T INDICATES INCORRECT FIRE CODE REFERENCES.
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2010 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2010 EDITION.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2009 EDITION.
 FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 10, 2010 EDITION.
  
 2) THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF
 THE FIRE ALARM AND SPRINKLER SYSTEM FOR CODE COVERAGE
 AND COMPLIANCE.
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-05-09 Cont ID  
Sent By tklarge Date 2015-05-09 Time 10:18 Rev Time  
Received By tklarge Date 2015-03-30 Time   Sent To  
Notes
2015-03-31 11:31:13INCOMING SENT TO C-07.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2015-05-04 Cont ID  
Sent By hmoser Date 2015-05-04 Time 14:57 Rev Time 0.00
Received By hmoser Date 2015-05-04 Time 14:57 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-05-09 Cont ID  
Sent By tklarge Date 2015-05-09 Time 10:18 Rev Time 0.00
Received By tklarge Date 2015-05-09 Time 09:44 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2015-04-06 Cont ID  
Sent By ajones Date 2015-04-06 Time 14:51 Rev Time 0.00
Received By ajones Date 2015-04-06 Time 14:51 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved