Review Stop G GAS REVIEW
Rev No 1 Status F Date 2015-04-01 Cont ID  
Sent By tklarge Date 2015-04-01 Time 05:48 Rev Time 0.00
Received By tklarge Date 2015-04-01 Time 04:44 Sent To  
Notes
2015-04-01 05:47:081) SUBMIT MANUF. SPECIFICATIONS FOR THE TANKLESS WATER
 HEATERS AND THE DRYERS. APPLIANCES SHALL BE LISTED AND
 LABELED PER THE 2010 FL. FUEL GAS CODE SEC. 301.3.
 2) SHOW THE LOCATION AND DISTANCE OF THE TANKLESS WATER
 HEATER'S EXHAUST IN RELATION TO ALL BUILDING OPENINGS
 INCLUDING ANY SOFFIT VENTS. SUBMIT 2 COPIES OF THE PAGE
 FROM THE MANUF. INSTALLATION MANUAL THAT SHOWS THE
 REQUIRED CLEARANCES. WPB AMEND. TO 2010 FBC SEC.
 107.2.1, 2010 FGC SEC.303.1.
 3) THE TANKLESS WATER HEATERS SHALL BE LISTED FOR
 OUTDOOR LOCATIONS. FGC SEC.303.6.SUBMIT DOCUMENTATION.
 4) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE DRYERS IN
 ACCORDANCE WITH THE 2010 FGC SEC.304.
 5) SUBMIT DETAILS FOR THE DRYER EXHAUSTS PER THE 2010
 SEC.614. SHOW TYPE OF VENT, SIZES, LOCATIONS, ETC.
 6) SIZE THE PIPE SECTION ON THE GAS RISER FROM THE
 METER TO THE FIRST BRANCH TO THE WATER HEATERS, WPB
 AMEND. TO 2010 FBC SEC. 107.2.1.
 7) INSTALLATIONS EXHAUSTING MORE THAN 200 CFM SHALL BE
 PROVIDED WITH MAKEUP AIR PER 2010 FGC SEC.614.5.
 8) SUBMIT A COPY OF THE MANUFACTURER'S INSTALLATION
 INSTRUCTIONS FOR THE DRYER'S PER THE 2010 FGC
 SEC.614.6.5.2. ARE THESE RESIDENTIAL TYPE DRYERS OR
 COMMERCIAL TYPE? INDICATE ON PLAN.
 9) EXHAUST DUCTS SHALL BE EQUIPPED WITH A BACKDRAFT
 DAMPER PER THE 2010 FGC SEC.614.4.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-04-24 Cont ID  
Sent By tklarge Date 2015-04-24 Time 12:18 Rev Time 0.00
Received By tklarge Date 2015-04-23 Time 16:49 Sent To  
Notes
2015-04-23 16:49:56TO TL DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-04-01 Cont ID  
Sent By tklarge Date 2015-04-01 Time 05:47 Rev Time 0.00
Received By tklarge Date 2015-03-30 Time   Sent To  
Notes
2015-03-31 11:10:25INCOMING SENT TO PLUMBING BOX<$5K.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved