Plan Review Details - Permit 15031260
Plan Review Stops For Permit 15031260
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-06-27 Cont ID  
Sent By jgomez Date 2015-06-27 Time 14:36 Rev Time 0.00
Received By jgomez Date 2015-06-27 Time 14:35 Sent To  
Notes
2015-06-27 14:37:00BUILDING REVIEW APPROVED WITH PROVISO:
 1- REVISE BUILDING EXPOSURE AND ALL DESIGN PRESSURES.
 2- PROVIDE COMPLETE DETAILS & SPECIFICATIONS FOR THE
 OPENING PROTECTION OF WINDOW LOCATED BETWEEN GARAGE AND
 OFFICE. SEC. R302.5.
 3- PROVIDE PRODUCT APPROVAL (2 COPIES) FOR (NOTE: ALL
 PRODUCT APPROVALS WILL BE RE-REVIEWED WHEN ALL DESIGN
 PRESSURES ARE REVISED).
 A) CUSTOM MADE ENTRY DOOR ASSEMBLY. NEED TO PROVIDE
 COMPLETE ENGINEER PACKAGE FOR BUILDING OFFICIAL
 REVIEW/APPROVAL. CONTACT ROBERT BROWN (BUILDING
 OFFICIAL) AT [email protected].
 B) FIXED WINDOW SIZE SPECIFIED FOR WINDOW "F" ON THE
 WINDOW SCHEDULE. NOA 11-1031.06 SUBMITTED DOESN'T COVER
 THAT SIZE.
 NOTE: WINDOW SCHEDULE CALLS FOR PGT WINDOWS. PRODUCT
 APPROVALS SUBMITTED ARE FOR DIFFERENT MANUFACTURER.
 REVISE AS REQUIRED.
 C) OUTSWING GLAZED DOOR WITH SIDELITES: NEED TO PROVIDE
 PRODUCT APPROVAL THAT COVERS SIZE FOR DOOR #4.
 D) SLIDING GLASS DOORS WITH 3 PANELS SIZE AS SPECIFIED
 FOR DOOR #3.
 E) PRECAST LINTELS AS SPECIFIED ON PLANS. NOA
 13-0321.07 SUBMITTED IS FOR 4", 6" & 12" LINTELS.
 4- DESIGNER OF RECORD TO APPROVE ALL PRODUCT APPROVALS.
 5- GEO-TECHNICAL ENGINEERING REPORT SUBMITTED NEED THE
 ENGINEER'S ORIGINAL SEAL AND SIGNATURE AS REQUIRED BY
 CHAPTER 471 F.S.
  
 NOTE: FLOOD ZONE A5. ELEVATION CERTIFICATES WILL BE
 REQUIRED DURING CONSTRUCTION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-06-20 Cont ID  
Sent By jgomez Date 2015-06-19 Time 16:58 Rev Time 0.00
Received By jgomez Date 2015-06-19 Time 16:55 Sent To  
Notes
2015-06-19 17:01:42NOTE: BUILDING REVIEW MAY BE APPROVED WITH PROVISO.
 BELOW COMMENTS MAY BE ADDRESSED AFTER PERMIT IS ISSUED.
 REVISION FEES WILL APPLY.
  
  
  
 ORIGINAL COMMENT:
 1- WINDOWS AND DOORS DESIGN PRESSURES SHOWN ON SHEET
 SP-1 DON'T CORRESPOND TO THE WORST CASE SCENARIO FOR
 EXPOSURE "D". REVISE AS REQUIRED. SEC. R301.1 OF 2010
 FBC-RESIDENTIAL.
  
 RESPONSE:
 THE BUILDING EXPOSURE WAS CHANGED TO "C". THE BUILDING
 EXPOSURE FOR THIS BUILDING IS "D". ORIGINAL PLANS HAD
 THE CORRECT BUILDING EXPOSURE "D". IT WAS THE DESIGN
 PRESSURES THAT WERE INCORRECT. THAT'S WHY I DIDN'T ASK
 TO CHANGE THE BUILDING EXPOSURE. ONLY THE DESIGN
 PRESSURES. RESPONSE LETTER FROM THE ARCHITECT ONLY
 TAKES INTO CONSIDERATION A WIND EXPOSURE FROM THE EAST
 SIDE. NEED TO TAKE INTO CONSIDERATION EACH WIND
 DIRECTION. SEE SEC. R301.2.1.4. (I MET WITH ROBERT
 BROWN, BUILDING OFFICIAL, FOR SECOND OPINION ON
 BUILDING EXPOSURE FOR THIS BUILDING. HE AGREES ON
 EXPOSURE "D". PROPERTY APPRAISAL AERIAL VIEWS WILL BE
 E-MAILED TO ARCHITECT TO ILLUSTRATE BUILDING EXPOSURE).
  
 2- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 OPENING PROTECTION OF WINDOW LOCATED BETWEEN GARAGE AND
 OFFICE. SEC. R302.5 OF 2010 FBC-RESIDENTIAL. (COMPLETE
 ASSEMBLY MAY BE SUBMITTED LATER FOR BUILDING OFFICIAL
 REVIEW AND APPROVAL)
  
 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR (NOTE: ALL PRODUCT APPROVALS WILL BE
 RE-REVIEWED WHEN DESIGN PRESSURES ARE CHANGED FOR
 EXPOSURE "D"):
 A) CUSTOM MADE ENTRY DOOR ASSEMBLY. NEED TO PROVIDE
 COMPLETE ENGINEER PACKAGE FOR SITE SPECIFIC APPROVAL.
 MANUFACTURER TO CONTACT ROBERT BROWN (BUILDING
 OFFICIAL) AT (561)805-6652 OR AT [email protected] TO
 COORDINATE REQUIRED SUBMITTAL PACKAGE TO AVOID DELAYS
 OR CONFLICTS.
  
 B) FIXED WINDOW SIZE SPECIFIED FOR WINDOW "F" ON THE
 WINDOW SCHEDULE. NOA 11-1031.06 SUBMITTED DOESN'T COVER
 THAT SIZE.
 NOTE: WINDOW SCHEDULE CALLS FOR PGT WINDOWS. PRODUCT
 APPROVALS SUBMITTED ARE FOR DIFFERENT MANUFACTURER.
 REVISE AS REQUIRED.
  
 C) OUTSWING GLAZED DOOR WITH SIDELITES: NEED TO PROVIDE
 PRODUCT APPROVAL THAT COVERS SIZE FOR DOOR #4.
  
 D) SLIDING GLASS DOORS WITH 3 PANELS SIZE AS SPECIFIED
 FOR DOOR #3.
  
 E) PRECAST LINTELS AS SPECIFIED ON PLANS. NOA
 13-0321.07 SUBMITTED IS FOR 4", 6" & 12" LINTELS. THIS
 IS NOT WHAT'S SPECIFIED ON PLANS.
  
 4- DESIGNER OF RECORD TO REVIEW AND APPROVE ABOVE
 PRODUCT APPROVALS. SEC. 107.3.4.1 CITY AMENDMENTS.
  
 5- GEO-TECHNICAL ENGINEERING REPORT SUBMITTED NEED THE
 ENGINEER'S ORIGINAL SEAL AND SIGNATURE AS REQUIRED BY
 CHAPTER 471 F.S.
  
 NOTE: FLOOD ZONE A5. ELEVATION CERTIFICATES WILL BE
 REQUIRED DURING CONSTRUCTION.
  
 ***PLEASE PROVIDE A RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE REPLACE AND REMOVE ANY REVISED DRAWING.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-05-05 Cont ID  
Sent By jgomez Date 2015-05-04 Time 18:20 Rev Time 0.00
Received By jgomez Date 2015-05-04 Time 18:20 Sent To  
Notes
2015-05-04 18:28:51NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.
  
 2- PROPERTY IS LOCATED IN FLOOD ZONE A5. PROVIDE
 COMPLETE DETAILS AND SPECIFICATIONS SHOWING COMPLIANCE
 WITH THE REQUIREMENTS OF SEC. R322 OF 2010
 FBC-RESIDENTIAL. SPECIFY FINISH FLOOR ELEVATION FOR
 MAIN HOUSE, GARAGE, CABANA AND ALL EQUIPMENT. NOTE:
 ELEVATIONS CERTIFICATES WILL BE REQUIRED DURING
 CONSTRUCTION.
  
 3- WINDOWS AND DOORS DESIGN PRESSURES SHOWN ON SHEET
 SP-1 DON'T CORRESPOND TO THE WORST CASE SCENARIO FOR
 EXPOSURE "D". REVISE AS REQUIRED. SEC. R301.1 OF 2010
 FBC-RESIDENTIAL.
  
 4- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 OPENING PROTECTION OF WINDOW LOCATED BETWEEN GARAGE AND
 OFFICE SHOWING COMPLIANCE WITH SEC. R302.5 OF 2010
 FBC-RESIDENTIAL.
  
 5- GARAGE WALL SECTION ON SHEET A-3 AND WALL SECTION ON
 SHEET A-6 CALL FOR ROOF FLAT TILE TO BE FOAMED AND
 NAILED. SPECIFY TYPE AND NUMBER OF NAILS. SEC.
 107.2.1.2 CITY AMENDMENTS.
  
 6- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 SECOND FLOOR DRAFSTOPPING SHOWING COMPLIANCE WITH SEC.,
 R302.12 OF 2010 FBC-RESIDENTIAL.
  
 7- GARAGE WALL SECTION ON SHEET A-3:
 A) PROVIDE FIREBLOCKING SPECS BETWEEN GARAGE AND SECOND
 FLOOR. SEC. R302.11 OF 2010 FBC-RESIDENTIAL.
  
 B) PROVIDE SPECIFICATIONS FOR CEILING MATERIALS AS
 REQUIRED BY TABLE R302.6 OF 2010 FBC-RESIDENTIAL.
  
 C) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 SOFFIT CONSTRUCTION AT SECOND FLOOR AND AT THE BALCONY
 SHOWING COMPLIANCE WITH SEC. R703.1.3 OF 2010
 FBC-RESIDENTIAL. SPECIFY ALL FRAMING MEMBERS AND
 FASTENERS, WATER BARRIER, ETC.
  
 D) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION OF BALCONY CONCRETE PIERS. TABLE R301.5 OF
 2010 FBC-RESIDENTIAL.
  
 E) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 GUARDRAIL CONSTRUCTION SHOWING COMPLIANCE WITH THE LIVE
 LOAD OF TABLE R301.5 AND THE REQUIREMENTS OF SEC. R312
 OF 2010 FBC-RESIDENTIAL.
  
 F) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 SECOND FLOOR ASSEMBLY. SPECIFY FLOOR SHEATHING AND
 FINISH, ETC. SEC. 107.2.1 CITY AMENDMENTS.
  
 G) SHOW CORRECT LOCATION OF ICYNENE. WALL SECTION SHOWS
 SOFFIT WITHOUT INSULATION. NEED TO SHOW THAT THERMAL
 ENVELOPE IS COVERED WITH ICYNENE FOR AN UNVENTED ATTIC.
 SEC. R806 OF 2010 FBC-RESIDENTIAL.
  
 H) SPECIFY INSULATION BETWEEN GARAGE AND SECOND FLOOR.
 COORDINATE WITH THE ENERGY CALCULATIONS. SEC. 103.2.2
 OF 2010 FBC-ENERGY CONSERVATION.
  
 8- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 INSTALLATION OF STUCCO OVER FRAME CONSTRUCTION SHOWING
 THICKNESS COMPLIANCE WITH TABLE R702.1(1) AND WATER
 RESISTANT BARRIER SEC. R703.6.3 OF 2010
 FBC-RESIDENTIAL.
  
 9- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION AND INSTALLATION OF DECORATIVE ALUMINUM
 LOUVERS ON COVERED PORCH.
  
 10- ENTRY WALL SECTION ON SHEET A-4: SEE GARAGE WALL
 SECTION COMMENTS AND ADDRESS ITEMS THAT APPLY TO THIS
 SECTION. NOTE: SAME THING APPLIES TO WALL SECTION ON
 SHEET A-6.
  
 11- SHEET A-5:
 A) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 FIREBLOCKING AS REQUIRED BY SEC. R302.11 AT STAIRS AND
 DROPPED CEILING SHOWN ON STAIR SECTION-1.
  
 B) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 FABRICATION AND INSTALLATION OF HANDRAILS AND
 GUARDRAILS SHOWING COMPLIANCE WITH THE LIVE LOAD OF
 TABLE R301.5 AND ALL THE REQUIREMENTS OF SEC. R311.7.7
 AND R312 OF 2010 FBC-RESIDENTIAL. SPECIFY MATERIALS AND
 FASTENERS.
  
 C) SCHEMATIC GUARDRAIL DETAIL. REVISE OPENING
 SPECIFICATIONS. IT'S NOT 4" SPHERE MIN. IT'S AN OPENING
 THAT DOESN'T ALLOW THE PASSAGE OF A 4" SPHERE. SEC.
 R312.3 OF 2010 FBC-RESIDENTIAL.
  
 D) WINDOW SAFEGUARD NOTE IS INCORRECT. SEE SEC. R612.2
 OF 2010 FBC-RESIDENTIAL AND REVISE AS REQUIRED.
  
 E) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING
 COMPLIANCE WITH THE FLASHING REQUIREMENTS OF SEC.
 R703.8 OF 2010 FBC-RESIDENTIAL.
  
 12- SHEET A-6:
 A) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 CABANA STEEL ALUMINUM COLUMNS. SPECIFY BOTTOM PLATE
 SIZE AND FASTENERS. SEC. R601.2 OF 2010
 FBC-RESIDENTIAL..
  
 B) PROVIDE WALL SECTION THRU THE SUMMER KITCHEN.
 PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 CEILING CONSTRUCTION. SEC. R301.1 OF 2010
 FBC-RESIDENTIAL.
  
 C) SPECIFICATIONS FOR THE ROOF SHEATHING SHOWN ON THE
 ROOF FRAMING PLAN DON'T MATCH THE SPECIFICATIONS SHOWN
 ON THE WALL SECTION . REVISE AS REQUIRED. SEC. 107.2.1
 CITY AMENDMENTS.
  
 13- SHEET S-2:
 A) PROVIDE WALL SECTION THRU REAR COVERED PORCH.
 SPECIFY CEILING CONSTRUCTION MATERIALS AND FASTENERS.
 SPECIFY CONNECTORS FOR TRUSSES THAT ARE RESTING ON THE
 WALL BETWEEN THE GARAGE AND COVERED PORCH. SEC. R301.1
 OF 2010 FBC-RESIDENTIAL.
  
 B) GIRDER TRUSS LOCATED BY THE STAIRS AND LIVING ROOM
 AREA: GIRDER TRUSS IS RESTING ON A WOOD COLUMN ON THE
 LEFT HAND SIDE, BUT THERE IS NOT INFORMATION FOR THE
 BEARING ON THE RIGHT HAND SIDE. PROVIDE COMPLETE
 DETAILS AND SPECIFICATIONS, INCLUDING FOOTING IF
 REQUIRED. SEC. R301.1 OF 2010 FBC-RESIDENTIAL.
  
 C) SPECIFY ALL CONNECTORS FOR THE FLOOR TRUSSES,
 INCLUDING THE GIRDER TRUSSES. SEC. R301.1 OF 2010
 FBC-RESIDENTIAL.
  
 D) TYPICAL INTERMEDIATE SECTION. SHOW COMPLIANCE WITH
 FIREBLOCKING AS REQUIRED BY SEC. R302.11 OF 2010
 FBC-RESIDENTIAL.
  
 E) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 COLUMNS BETWEEN WINDOWS "F". SEC. R301.1 OF 2010
 FBC-RESIDENTIAL.
  
 14- SHEET S-3: THERE ARE DIFFERENT SPECS FOR THE ROOF
 SHEATHING FASTENING. SEE SPECS ON TYPICAL ROOF SECTION,
 NAILING ZONE PLAN AND ROOF FRAMING PLAN. REVISE AS
 REQUIRED TO MATCH. SEC. 107.2.1 CITY AMENDMENTS.
  
 15- PROVIDE SEPARATE ENERGY CALCULATIONS FOR THE
 DETACHED CABANA. SEC. 103.2.1 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 16- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) CUSTOM MADE ENTRY DOOR ASSEMBLY. NEED TO PROVIDE
 COMPLETE ENGINEER PACKAGE FOR SITE SPECIFIC APPROVAL.
 MANUFACTURER TO CONTACT ROBERT BROWN (BUILDING
 OFFICIAL) AT (561)805-6652 OR AT [email protected] TO
 COORDINATE REQUIRED SUBMITTAL PACKAGE TO AVOID DELAYS
 OR CONFLICTS.
  
 B) ROOF TILE. NOA 12-0222.03 SUBMITTED DOESN'T
 CORRESPOND TO THE FLORIDA PRODUCT APPROVAL FL601-R9
 SUBMITTED. PROVIDE CORRECT NOA.
  
 C) ROOF TILE ADHESIVE THAT MEETS THE MINIMUM ROOF TILE
 ATTACHMENT RESISTANCE. TILE BOND ADHESIVE SUBMITTED
 DOESN'T MEET THE ROOF TILE ATTACHMENT RESISTANCE.
  
 D) FIXED WINDOW SIZE SPECIFIED FOR WINDOW "F". NOA
 11-1031.06 SUBMITTED DOESN'T COVER THAT SIZE.
  
 E) OUTSWING GLAZED DOORS WITH/WITHOUT SIDE-LITES. NOA
 13-0226.06 SUBMITTED DOESN'T CORRESPOND TO FLORIDA
 PRODUCT APPROVAL FL16217 SUBMITTED. PROVIDE EITHER THE
 MIAMI-DADE NOA OR COMPLETE FLORIDA PRODUCT APPROVAL
 PACKAGE. NOTE: BEFORE SUBMITTAL VERIFY THAT PRODUCT
 APPROVAL COVER SIZE OF DOOR ASSEMBLY SPECIFIED FOR DOOR
 #4.
  
 F) GARAGE DOOR. NEED PRODUCT APPROVAL THAT MEETS THE
 DESIGN PRESSURES CALCULATED BY THE ARCHITECT OF RECORD.
 AND PROVIDE LEGIBLE DRAWINGS.
  
 G) SLIDING GLASS DOORS SIZE AS SPECIFIED FOR DOOR #3.
 NOTE: SEE SIZE OF PANELS (3).
  
 H) PRECAST LINTELS AS SPECIFIED ON PLANS.
  
 I) ALUMINUM BAHAMA SHUTTERS AS SPECIFIED ON PLANS. AND
 PROVIDE COMPLETE INSTALLATION SCHEDULE.
  
 J) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 FRAMING PLANS AND DETAILS. PROVIDE ONLY THE FLORIDA
 PRODUCT APPROVAL COVER PAGE AND PAGE SHOWING THE
 SPECIFIED CONNECTOR OR LIST FLORIDA PRODUCT APPROVAL
 NUMBER NEXT TO THE SPECIFIED CONNECTOR.
  
 17- DESIGNER OF RECORD TO REVIEW AND APPROVE ABOVE
 PRODUCT APPROVALS. SEC. 107.3.4.1 CITY AMENDMENTS.
  
 18- PROVIDE ICYNENE ICC CURRENT EVALUATION REPORT TO
 VERIFY COMPLIANCE WITH SEC. R316 OF 2010
 FBC-RESIDENTIAL. AND ARCHITECT OF RECORD TO REVIEW AND
 APPROVE IT PRIOR TO SUBMITTAL.
  
 19- SHEET S-1: FOOTING PROFILE SHOWN BETWEEN THE GARAGE
 AND OFFICE SIDE IS INCORRECT. THERE IS A 4" DROP ON THE
 FOOTING PROFILE. REVISE AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 20- REVISE THE DESCRIPTION OF THE GEO-TECHNICAL
 ENGINEERING REPORT SUBMITTED. THIS IS A TWO STORY
 SINGLE FAMILY HOME NOT ONE. ALSO, TAKE INTO
 CONSIDERATION THAT IT'S CONCRETE BLOCK CONSTRUCTION.
 SEC. R301.1 OF 2010 FBC-RESIDENTIAL.
  
 21- DESIGNER OF RECORD TO REVIEW THE GEO-TECHNICAL
 ENGINEERING REPORT FOR FOUNDATION AND CONCRETE SLAB
 RECOMMENDATIONS (SEE SEC. 4.3.1 AND 4.3.2 OF REPORT
 SUBMITTED). DESIGNER OF RECORD TO REVISE PLANS AS
 RECOMMENDED OR ACKNOWLEDGE IN WRITING THAT NO CHANGES
 WILL BE REQUIRED FOR HIS DESIGN. SEC. R301.1 OF 2010
 FBC-RESIDENTIAL.
  
 22- ATTIC ACCESS LOCATED IN SECOND FLOOR BY THE LIVING
 AREA DOESN'T COMPLY WITH SEC. R807 OF 2010
 FBC-RESIDENTIAL. CLOSET IS TOO SMALL. ACCESS WILL BE
 BLOCKED BY THE CONTENT OF THE CLOSET. REVISE LOCATION
 AS REQUIRED.
  
 ***PLEASE PROVIDE A RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE REPLACE AND REMOVE ANY REVISED DRAWING.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-06-25 Cont ID  
Sent By dhayes Date 2015-06-25 Time 11:39 Rev Time 0.00
Received By dhayes Date 2015-06-25 Time 11:39 Sent To  
Notes
2015-06-25 11:39:104/28/2015
 PROJECT: POTTER RESIDENCE
 PERMIT#: 15031260
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN
 APPROVED PROVISIONALLY. FAILURE TO CORRECT THE LISTED
 DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED
 INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION
 FEE(S).
  
 1) REVISE THE RISER DIAGRAM TO INDICATE THE
 INSTALLATION OF THE INTER-SYSTEM BONDING DEVICE. SEE
 NEC 250.94
  
 2) PERMANENT LADDERS OR STAIRWAYS SHALL BE PROVIDED AT
 THE SECOND FLOOR ACCESS TO THE ATTIC WHERE AHU2 AND
 AHU3 ARE INSTALLED TO GIVE SAFE ACCESS TO THE WORKING
 SPACE AROUND ELECTRICAL EQUIPMENT INSTALLED IN ATTIC.
 NEC 110.33(B)
  
 PLEASE PROVIDE A SEPARATE PERMIT APPLICATIONS
 ACCOMPANIED BY MANUFACTURERS EQUIPMENT SUBMITTALS, AND
 SHOP DRAWINGS FOR ALL LOW VOLTAGE SPECIALTY SYSTEMS
 SUCH AS BUT NOT LIMITED TO THE FOLLOWING:
 DATA/COMMUNICATION, SECURITY, AND AUDIO/VIDEO.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-04-28 Cont ID  
Sent By dhayes Date 2015-04-28 Time 12:29 Rev Time 0.00
Received By dhayes Date 2015-04-28 Time 10:59 Sent To  
Notes
2015-04-28 12:29:394/28/2015
 PROJECT: POTTER RESIDENCE
 PERMIT#: 15031260
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
 REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW
 COMMENTS:
  
 1) THE ELECTRICAL SERVICE LOAD SUMMARY INDICATES A
 TOTAL CONNECTED LOAD OF 320AMPS AND YET THE RISER
 DIAGRAM INDICATES ONLY A 2/0 FEEDER TO A 200AMP MAIN
 RATED PANEL "A". REVISE THE RISER TO ACCOMMODATE THE
 TOTAL CONNECTED LOAD PROPOSED.
  
 2) REVISE THE RISER DIAGRAM TO INDICATE THE BONDING OF
 THE GAS PIPING AND THE INSTALLATION OF THE INTER-SYSTEM
 BONDING DEVICE. SEE NEC 250.94 AND 250.104(2)
  
 3) INDICATE THE LOCATION FOR THE SAUNA AND PANEL "C" ON
 THE FLOOR PLAN.WPB AMENDMENTS TO THE FBC 107.2.1
  
 4) PERMANENT LADDERS OR STAIRWAYS SHALL BE PROVIDED TO
 GIVE SAFE ACCESS TO THE WORKING SPACE AROUND ELECTRICAL
 EQUIPMENT INSTALLED ON PLATFORMS, BALCONIES, OR
 MEZZANINE FLOORS OR IN ATTIC OR ROOF ROOMS OR SPACES.
 NEC 110.33(B)
  
 5) RECESSED LUMINARIES INSTALLED IN THE BUILDING
 THERMAL ENVELOPE SHALL BE SEALED TO LIMIT AIR LEAKAGE
 BETWEEN CONDITIONED AND UNCONDITIONED SPACES. ALL
 RECESSED LUMINARIES SHALL BE IC-RATED AND LABELED AS
 MEETING ASTM E 283 WHEN TESTED AT 1.57 PSF (75 PA)
 PRESSURE DIFFERENTIAL WITH NO MORE THAN 2.0 CFM (0.944
 L/S) OF AIR MOVEMENT FROM THE CONDITIONED SPACE TO THE
 CEILING CAVITY. ALL RECESSED LUMINARIES SHALL BE SEALED
 WITH A GASKET OR CAULK BETWEEN THE HOUSING AND INTERIOR
 WALL OR CEILING COVERING. FBC-E 502.3.8 RECESSED
 LIGHTING.
  
 6) VERIFY CARBON MONOXIDE DETECTORS ARE INSTALLED AS
 REQUIRED. EVERY SEPARATE BUILDING OR AN ADDITION TO AN
 EXISTING BUILDING FOR WHICH A PERMIT FOR NEW
 CONSTRUCTION IS ISSUED AND HAVING A FOSSIL FUEL BURNING
 HEATER OR APPLIANCE, A FIRE PLACE, AN ATTACHED GARAGE,
 OR OTHER FEATURE, FIXTURE OR ELEMENT THAT EMITS CARBON
 MONOXIDE AS A BYPRODUCT OF COMBUSTION SHALL HAVE AN
 OPERATIONAL CARBON MONOXIDE ALARM INSTALLED WITHIN 10'
 OF EACH ROOM USED FOR SLEEPING PURPOSES.
 FBC-RESIDENTIAL 315.1
  
 7) PROVIDE A 3WAY SWITCH AT THE BALCONY EGRESS DOORS
 FROM BATH 2 ON THE 2ND FL WPB AMENDMENTS TO THE FBC
 107.2.1
  
 8) VERIFY LUMINAIRES IN CLOTHES CLOSETS SHALL BE
 INSTALLED IN ACCORDANCE WITH THE PROVISIONS OF THE NEC
 410.16(A) AND (B).
  
 9) DOUBLE CHECK AND VERIFY GFI OUTLET SPACING AT THE
 KITCHEN COUNTERTOPS. THERE APPEARS TO BE A COUPLE OF
 OUTLETS MISSING BY THE REFRIGERATOR AND THE OVEN. NEC
 210.52(C)(1) WALL COUNTERTOP SPACES.
  
 10) VERIFY THE WATER HEATER HAS THE REQUIRED ELECTRIC
 DISCONNECT. NEC 422.31
  
 PLEASE PROVIDE A SEPARATE PERMIT APPLICATIONS
 ACCOMPANIED BY MANUFACTURERS EQUIPMENT SUBMITTALS, AND
 SHOP DRAWINGS FOR ALL LOW VOLTAGE SPECIALTY SYSTEMS
 SUCH AS BUT NOT LIMITED TO THE FOLLOWING:
 DATA/COMMUNICATION, SECURITY, AND AUDIO/VIDEO.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2015-06-16 Cont ID  
Sent By tklarge Date 2015-06-16 Time 14:28 Rev Time 0.00
Received By tklarge Date 2015-06-16 Time 14:28 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2015-04-30 Cont ID  
Sent By tklarge Date 2015-04-30 Time 09:19 Rev Time 0.00
Received By tklarge Date 2015-04-30 Time 08:17 Sent To  
Notes
2015-04-30 09:19:021) SPECIFICATIONS FOR ALL GAS EQUIPMENT SHALL BE
 SUBMITTED AT TIME OF GAS PERMIT APPLICATION. ALL GAS
 EQUIPMENT SHALL BE LISTED AND LABELED PER THE 2010 FBCR
 SEC.G2404.3.
 2) INDICATE THE TYPE OF GAS APPLIANCE ON THE GAS RISER
 THAT IS LOCATED AT THE CABANA. IT APPEARS TO BE A BBQ
 GRILL. WPB AMEND.TO 2010 FBC SEC. 107.2.1.
 3) SHOW THE LENGTH OF THE VERTICAL SECTION OF PIPE FROM
 THE GAS METER TO WHERE IT MEETS BOTH 1 1/4" LINES.
 4) BASED ON THE TOTAL BTU LOAD OF THE APPLIANCES AND
 THE TOTAL DEVELOPED LENGTH OF THE PIPING, THE MINIMUM
 SIZE LINE AT THE METER SHALL BE 2 INCHES PER TABLE
 G2413.4 (1).
 5) SIZE THE LINE TO THE COOKTOP.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-06-30 Cont ID  
Sent By jgomez Date 2015-06-30 Time 18:25 Rev Time 0.00
Received By jgomez Date 2015-06-30 Time 18:25 Sent To  
Notes
2015-06-30 18:25:35RE-SUBMITTAL PLANS WITH IMPACT FEES STAMP. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-06-25 Cont ID  
Sent By dhayes Date 2015-06-25 Time 11:39 Rev Time 0.00
Received By dhayes Date 2015-05-26 Time 15:34 Sent To  
Notes
2015-05-26 15:34:44R07

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-05-14 Cont ID  
Sent By jgomez Date 2015-05-14 Time 14:24 Rev Time 0.00
Received By jgomez Date 2015-03-27 Time 08:01 Sent To  
Notes
2015-03-28 08:03:59R32

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2015-06-30 Cont ID  
Sent By jgomez Date 2015-06-30 Time 18:24 Rev Time 0.00
Received By jgomez Date 2015-06-30 Time 18:18 Sent To  
Notes
2015-06-30 18:24:48NO FEES. MU-2015-16294. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2015-06-19 Cont ID  
Sent By jgomez Date 2015-06-19 Time 17:03 Rev Time 0.00
Received By jgomez Date 2015-06-19 Time 17:03 Sent To  
Notes
2015-06-19 17:03:521- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-05-04 Cont ID  
Sent By jgomez Date 2015-05-04 Time 18:29 Rev Time 0.00
Received By jgomez Date 2015-05-04 Time 18:28 Sent To  
Notes
2015-05-04 18:29:231- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2015-06-27 Cont ID  
Sent By jgomez Date 2015-06-27 Time 15:01 Rev Time 0.00
Received By jgomez Date 2015-06-27 Time 14:56 Sent To  
Notes
2015-06-27 15:02:25PROVIDE COMPLETE AND CORRECT INFORMATION (PLANS AND
 EQUIPMENT SIZING CALCULATIONS) UNDER A SEPARATE PERMIT.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2015-06-20 Cont ID  
Sent By jgomez Date 2015-06-20 Time 14:02 Rev Time 0.00
Received By jgomez Date 2015-06-20 Time 14:02 Sent To  
Notes
2015-06-20 14:20:31NOTE: THIS MAY BE A PROVISO TO PROVIDE COMPLETE REVISED
 INFORMATION (CALCULATIONS AND A/C PLANS) UNDER A
 SEPARATE PERMIT.
  
 1- SELECTED EQUIPMENT EXCEEDS THE CALCULATED TOTAL
 LOAD. NEED TO COMPLY WITH SEC. 403.6.1.1 OF 2010
 FBC-ENERGY CONSERVATION.
  
 2- NEED TO PROVIDE MECHANICAL VENTILATION FOR CABANA
 BATHROOM AND SAUNA ROOM. SEC. R303 AND M1507 OF 2010
 FBC-RESIDENTIAL.
  
 ***PLEASE PROVIDE A RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE REPLACE AND REMOVE ANY REVISED DRAWING.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-05-14 Cont ID  
Sent By jgomez Date 2015-05-14 Time 15:18 Rev Time 0.00
Received By jgomez Date 2015-05-14 Time 12:33 Sent To  
Notes
2015-05-14 15:24:05NEW SINGLE FAMILY RESIDENCE (R3) MECHANICAL REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- SELECTED EQUIPMENT EXCEEDS THE CALCULATED TOTAL
 LOAD. NEED TO COMPLY WITH SEC. 403.6.1.1 OF 2010
 FBC-ENERGY CONSERVATION.
  
 2- EQUIPMENT LISTED ON THE MECHANICAL PLAN DOESN'T
 MATCH EQUIPMENT LISTED ON THE EQUIPMENT SIZING
 CALCULATIONS. SEC. 103.2.2 OF 2010 FBC-ENERGY
 CONSERVATION. NOTE: COORDINATE WITH ITEM #1 ABOVE WHEN
 THE EQUIPMENT IS REVISED.
  
 ***PLEASE PROVIDE A RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE REPLACE AND REMOVE ANY REVISED DRAWING.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 3 Status N Date 2015-06-27 Cont ID  
Sent By jgomez Date 2015-06-27 Time 14:42 Rev Time 0.00
Received By jgomez Date 2015-06-27 Time 14:42 Sent To  
Notes
2015-06-27 14:42:19PLEASE E-MAIL SAMANTHA HILL WHEN THE PERMIT IS ISSUED.

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 2 Status F Date 2015-06-20 Cont ID  
Sent By jgomez Date 2015-06-20 Time 13:47 Rev Time 0.00
Received By jgomez Date 2015-06-20 Time 13:47 Sent To  
Notes
***NONE***

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2015-05-14 Cont ID  
Sent By jgomez Date 2015-05-14 Time 11:38 Rev Time 0.00
Received By jgomez Date 2015-05-14 Time 11:38 Sent To  
Notes
2015-05-14 11:39:36PLEASE E-MAIL SAMANTHA HILL WHEN THE PERMIT IS ISSUED.

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-06-16 Cont ID  
Sent By tklarge Date 2015-06-16 Time 13:58 Rev Time 0.00
Received By tklarge Date 2015-06-16 Time 06:42 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-05-05 Cont ID  
Sent By tklarge Date 2015-04-29 Time 09:42 Rev Time 0.00
Received By tklarge Date 2015-04-29 Time 11:13 Sent To  
Notes
2015-04-29 12:15:181) SHOW THE LOCATION OF THE WASHING MACHINE AND LAUNDRY
 TRAY ON THE FLOOR PLAN.WPB AMEND. TO 2010 FBC SEC.
 107.2.1.
 2)THE SANITARY RISER DOES NOT CORRELATE WITH THE FLOOR
 PLAN FOR THE LOCATION OF FIXTURES.WPB AMEND. TO 2010
 FBC SEC. 107.2.1.
 3) SHT. E-2 HAS A SECTION OF THE SANITARY RISER THAT
 INCLUDES A WATER CLOSET, LAVATORY, FLOOR DRAIN, A SINK
 AND A LAVATORY BUT THERE IS NO SUCH AREA ON THE FLOOR
 PLAN. CLARIFY.
 4) SHT. E-2 HAS A SANITARY RISER FOR A BATH #3 BUT
 THERE IS NO BATH #3. CLARIFY.WPB AMEND. TO 2010 FBC
 SEC. 107.2.1.
 5) THE SECOND FLOOR SHOWS A BATH #1 BUT THE RISERS DO
 NOT SHOW A BATH #1. CLARIFY.WPB AMEND. TO 2010 FBC SEC.
 107.2.1.
 6) IDENTIFY THE CONNECTION POINTS ON THE FIRST FLOOR
 RISER WHERE THE SECOND FLOOR RISERS CONNECT TO THE
 STACKS.WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 7) CLEANOUTS ARE REQUIRED IN THE BASE OF ALL STACKS PER
 THE 2010 FBCR SEC.P3005.2.6.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2015-06-20 Cont ID  
Sent By jgomez Date 2015-06-20 Time 13:58 Rev Time 0.00
Received By jgomez Date 2015-06-20 Time 13:58 Sent To  
Notes
2015-06-20 14:02:031- ROOF TILE NOA 12-0222.03.
  
 2- TILE ADHESIVE NOA 12-0228.18.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2015-05-14 Cont ID  
Sent By jgomez Date 2015-05-14 Time 12:40 Rev Time 0.00
Received By jgomez Date 2015-05-14 Time 12:40 Sent To  
Notes
2015-05-14 12:41:351- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) ROOF TILE. NOA 12-0222.03 SUBMITTED DOESN'T
 CORRESPOND TO THE FLORIDA PRODUCT APPROVAL FL601-R9
 SUBMITTED. PROVIDE CORRECT NOA.
  
 B) ROOF TILE ADHESIVE THAT MEETS THE MINIMUM ROOF TILE
 ATTACHMENT RESISTANCE. TILE BOND ADHESIVE SUBMITTED
 DOESN'T MEET THE ROOF TILE ATTACHMENT RESISTANCE.
  

Review Stop Z ZONING
Rev No 3 Status P Date 2015-06-24 Cont ID  
Sent By sgraham Date 2015-06-24 Time 11:07 Rev Time 0.00
Received By sgraham Date 2015-06-24 Time 11:07 Sent To  
Notes
2015-06-19 17:06:03NEW DRAWINGS SUBMITTED. JG.

Review Stop Z ZONING
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2015-04-14 Time   Rev Time 0.00
Received By   Date 2015-04-14 Time   Sent To  
Notes
2015-05-14 09:40:445/14/15 POOL EQUIPMENT MUST CLEAR THE EASEMENT IN THE
 REAR.

Review Stop Z ZONING
Rev No 1 Status F Date 2015-04-10 Cont ID  
Sent By sgraham Date 2015-04-10 Time 11:49 Rev Time 0.00
Received By sgraham Date 2015-04-10 Time 11:49 Sent To  
Notes
2015-04-10 11:52:564/10/15 ZONING FAILED
  
 1. ROOF HEIGHT IN RESIDENTIAL ZONE IS 30' FT, YOUR ROOF
 IS 33' FT, MEASURING FROM THE GRADE TO ROOF MEAN.


Account Summary | Usage Policy | Privacy Policy