Plan Review Details - Permit 15031053
Plan Review Stops For Permit 15031053
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-04-23 Cont ID  
Sent By jwitmer Date 2015-04-23 Time 17:11 Rev Time  
Received By jwitmer Date 2015-04-23 Time   Sent To  
Notes
2015-04-23 17:13:30PLEASE SEE FIRES COMMENT ABOUT CARD READERS IN
 STAIRWELLS. 2010 FBC-B 1022.4 PENETRATIONS.
 PENETRATIONS INTO AND OPENINGS THROUGH AN EXIT
 ENCLOSURE ARE PROHIBITED EXCEPT FOR REQUIRED EXIT
 DOORS, EQUIPMENT AND DUCTWORK NECESSARY FOR INDEPENDENT
 VENTILATION OR PRESSURIZATION, SPRINKLER PIPING,
 STANDPIPES, ELECTRICAL RACEWAY FOR FIRE DEPARTMENT
 COMMUNICATION SYSTEMS AND ELECTRICAL RACEWAY SERVING
 THE EXIT ENCLOSURE AND TERMINATING AT A STEEL BOX NOT
 EXCEEDING 16 SQUARE INCHES (0.010 M2). SUCH
 PENETRATIONS SHALL BE PROTECTED IN ACCORDANCE WITH
 SECTION 713. THERE SHALL BE NO PENETRATIONS OR
 COMMUNICATION OPENINGS, WHETHER PROTECTED OR NOT,
 BETWEEN ADJACENT EXIT ENCLOSURES.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-04-23 Cont ID  
Sent By rlecky Date 2015-04-23 Time 13:02 Rev Time 0.00
Received By rlecky Date 2015-04-23 Time 12:35 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-04-17 Cont ID  
Sent By wjolin Date 2015-04-17 Time 13:38 Rev Time 0.00
Received By wjolin Date 2015-04-17 Time 11:32 Sent To  
Notes
2015-04-17 13:38:184847 FRED GLADSTONE DRIVE
 PERMIT #15031053
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET E-E501: SEVERAL STAIRS ON SEVERAL LEVELS INDICATE
 THE USE OF CARD READERS AND OCCUPANT SENSORS LOCATED
 WITHIN THE FIRE RATED EXIT ENCLOSURE. PER NFPA 101
 SECTION 7.1.3.2.1, PENETRATIONS INTO, AND OPENINGS
 THROUGH, AN EXIT ENCLOSURE ASSEMBLY SHALL BE LIMITED TO
 DOOR ASSEMBLIES FROM NORMALLY OCCUPIED SPACES AND
 CORRIDORS, REQUIRED EXIT DOOR OPENINGS, ELECTRICAL
 CONDUIT SERVING THE EXIT ENCLOSURE, DUCTWORK AND
 EQUIPMENT NECESSARY FOR INDEPENDENT STAIR
 PRESSURIZATION, WATER OR STEAM PIPING NECESSARY FOR THE
 HEATING OR COOLING OF THE EXIT ENCLOSURE, SPRINKLER
 PIPING, STANDPIPES, AND PENETRATIONS FOR FIRE ALARM
 CIRCUITS, WHERE THE CIRCUITS ARE INSTALLED IN METAL
 CONDUIT AND THE PENETRATIONS ARE PROTECTED.
  
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-05-02 Cont ID  
Sent By tklarge Date 2015-05-02 Time 10:15 Rev Time 0.00
Received By tklarge Date 2015-03-25 Time 08:43 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2015-05-02 Cont ID  
Sent By hmoser Date 2015-05-02 Time 10:06 Rev Time 0.00
Received By hmoser Date 2015-05-02 Time 09:36 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-05-02 Cont ID  
Sent By tklarge Date 2015-04-20 Time 06:03 Rev Time 0.00
Received By tklarge Date 2015-04-19 Time 10:39 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2015-04-20 Cont ID  
Sent By eschneid Date 2015-04-20 Time 12:16 Rev Time 1.00
Received By eschneid Date 2015-04-20 Time 12:16 Sent To  
Notes
2015-04-20 12:17:24THE LANDSCAPE AND FENCE/GATE REQUIRE SEPARATE PERMITS
 WITH PLANS AND ARE NOT APPROVED AS PART OF THIS PERMIT
 REVISION.
  