Plan Review Details - Permit 15030974
Plan Review Stops For Permit 15030974
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2015-05-04 Cont ID  
Sent By spalmer Date 2015-05-04 Time 08:04 Rev Time 0.00
Received By spalmer Date 2015-05-04 Time 08:04 Sent To  
Notes
2015-05-04 08:04:55OKAY PER MIKE

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-07-13 Cont ID  
Sent By jgomez Date 2015-07-13 Time 07:56 Rev Time 0.00
Received By jgomez Date 2015-07-13 Time 07:56 Sent To  
Notes
2015-07-13 07:56:42BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGN AND SEAL) ALL PRODUCT APPROVALS AS REQUIRED
 BY SEC. 107.3.4.1 CITY AMENDMENTS. NOTE: PRODUCT
 APPROVALS SUBMITTED ARE APPROVED BY H. JOHN GRIFFIN II,
 P.E. THIS IS NOT THE DESIGNER OF RECORD FOR THIS
 PROJECT.
  
 NOTE:
 THERE WAS ANOTHER SET OF PLANS SUBMITTED FOR THE
 REMODELING OF THE 2 STORY FRONT STRUCTURE. THIS
 STRUCTURE WAS NOT PART OF THE FIRST SUBMITTAL. EACH
 STRUCTURE NEEDS A SEPARATE PERMIT NUMBER. THIS PLANS
 WERE ASSIGNED A DIFFERENT PERMIT NUMBER (15070501) AND
 ROUTED FOR REVIEW BY ALL TRADES.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2015-05-05 Cont ID  
Sent By jgomez Date 2015-05-01 Time 15:01 Rev Time 0.00
Received By jgomez Date 2015-05-01 Time 14:15 Sent To  
Notes
2015-05-01 15:13:12BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGN AND SEAL) ALL PRODUCT APPROVALS AS REQUIRED
 BY SEC. 107.3.4.1 CITY AMENDMENTS. NOTE: PRODUCT
 APPROVALS SUBMITTED ARE APPROVED BY H. JOHN GRIFFIN II,
 P.E. THIS IS NOT THE DESIGNER OF RECORD FOR THIS
 PROJECT.
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-04-28 Cont ID  
Sent By dhayes Date 2015-04-28 Time 09:50 Rev Time 0.00
Received By dhayes Date 2015-04-28 Time 09:50 Sent To  
Notes
2015-04-28 09:53:301) VERIFY ALL NEW GENERAL PURPOSE OUTLETS MUST BE
 TAMPER RESISTANT AND AFCI PROTECTED. NEC 210.12, 406.11
  
 2) PROVIDE A PANELSCHEDULE FOR THE INSPECTOR IN THE
 FIELD PRIOR TO FINAL. EVERY CIRCUIT AND CIRCUIT
 MODIFICATION SHALL BE LEGIBLY IDENTIFIED AS TO ITS
 CLEAR, EVIDENT, AND SPECIFIC PURPOSE OR USE. NEC 408.4
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2015-04-06 Cont ID  
Sent By fmittner Date 2015-04-06 Time 16:48 Rev Time 0.00
Received By fmittner Date 2015-03-31 Time 15:23 Sent To  
Notes
2015-04-06 16:49:46ELEVATIONS SHOW EXISTING LAP SIDING. INTACT HORIZONTAL
 SIDING SHALL BE REPAIRED NOT REPLACED. IF REPLACEMENT
 IS NECESSARY (NOT CURRENTLY SHOWN ON PLANS) CONTACT
 FRIEDERIKE MITTNER TO DETERMINE LEAST AMOUNT NECESSARY
 FOR REPLACEMENT WITH CEDAR OR CYPRESS IN SAME WIDTH AND
 PROFILE.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-07-13 Cont ID  
Sent By jgomez Date 2015-07-13 Time 13:49 Rev Time 0.00
Received By jgomez Date 2015-06-29 Time 13:25 Sent To  
Notes
2015-07-13 18:04:39NOTE:
 THERE WAS ANOTHER SET OF PLANS SUBMITTED FOR THE
 REMODELING OF THE 2 STORY FRONT STRUCTURE. THIS
 STRUCTURE WAS NOT PART OF THE FIRST SUBMITTAL. EACH
 STRUCTURE NEEDS A SEPARATE PERMIT NUMBER. THIS PLANS
 WERE ASSIGNED A DIFFERENT PERMIT NUMBER (15070501) AND
 ROUTED FOR REVIEW BY ALL TRADES. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-05-01 Cont ID  
Sent By jgomez Date 2015-05-01 Time 18:31 Rev Time  
Received By jgomez Date 2015-03-23 Time   Sent To  
Notes
2015-04-17 15:35:05R05
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
2015-03-24 09:48:17R-31

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2015-07-13 Cont ID  
Sent By jgomez Date 2015-07-13 Time 13:50 Rev Time 0.00
Received By jgomez Date 2015-07-13 Time 13:49 Sent To  
Notes
2015-07-13 13:51:22 
  
 ***NOTE: CONTRACTOR MAY SUBMIT COMPLETE AND CORRECT
 MECHANICAL INFORMATION NOW OR COMPLETE INFORMATION MAY
 BE SUBMITTED BY THE A/C CONTRACTOR UNDER A SEPARATE
 PERMIT.
  
  
  
 RESIDENTIAL (R3) ALTERATION, SECOND MECHANICAL REVIEW
 COMMENTS.
 CODE: 2010 FBC
  
 *** THERE WAS NOT INFORMATION SUBMITTED. THE COMMENTS
 BELOW ARE THE ORIGINAL COMMENTS.
  
 1- PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS (2
 COPIES). SEC. M1401.3 OF 2010 FBC-RESIDENTIAL.
  
 2- MECHANICAL PLANS SUBMITTED:
 A) ARCHITECT TO REVISE THE TRANSFER DUCTS INFORMATION
 FOR THE BALANCED RETURN AIR. 14" DUCT DOESN'T FIT ON A
 12"X12" GRILL. SEC. M1602.4 OF 2010 FBC-RESIDENTIAL.
  
 B) LIST ON THE PLAN THE EQUIPMENT MANUFACTURER AND
 MODEL NUMBER THAT WAS USED FOR THE EQUIPMENT SIZING
 CALCULATIONS. SEC. 107.3.5.3(10) CITY AMENDMENTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-05-01 Cont ID  
Sent By jgomez Date 2015-05-01 Time 18:31 Rev Time 0.00
Received By jgomez Date 2015-05-01 Time 18:30 Sent To  
Notes
2015-05-01 18:31:33RESIDENTIAL (R3) ALTERATION, MECHANICAL REVIEW
 COMMENTS.
 CODE: 2010 FBC
  
 1- PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS (2
 COPIES). SEC. M1401.3 OF 2010 FBC-RESIDENTIAL.
  
 2- MECHANICAL PLANS SUBMITTED:
 A) ARCHITECT TO REVISE THE TRANSFER DUCTS INFORMATION
 FOR THE BALANCED RETURN AIR. 14" DUCT DOESN'T FIT ON A
 12"X12" GRILL. SEC. M1602.4 OF 2010 FBC-RESIDENTIAL.
  
 B) LIST ON THE PLAN THE EQUIPMENT MANUFACTURER AND
 MODEL NUMBER THAT WAS USED FOR THE EQUIPMENT SIZING
 CALCULATIONS. SEC. 107.3.5.3(10) CITY AMENDMENTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-04-18 Cont ID  
Sent By tklarge Date 2015-04-18 Time 09:59 Rev Time 0.00
Received By tklarge Date 2015-04-18 Time 09:41 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2015-04-06 Cont ID  
Sent By fmittner Date 2015-04-06 Time 16:49 Rev Time 0.00
Received By fmittner Date 2015-04-06 Time 16:49 Sent To  
Notes
***NONE***