Plan Review Details - Permit 15030968
Plan Review Stops For Permit 15030968
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2015-12-28 Cont ID  
Sent By skennedy Date 2015-12-28 Time 11:32 Rev Time 0.00
Received By skennedy Date 2015-12-28 Time 11:32 Sent To  
Notes
2015-12-28 11:32:50INCREASED VALUE TO $15,000.00

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2015-10-28 Cont ID  
Sent By skennedy Date 2015-10-28 Time 07:10 Rev Time 0.00
Received By skennedy Date 2015-10-28 Time 07:10 Sent To  
Notes
2015-10-28 07:12:343RD REVIEW: FBC 2010
  
 THE SUBMITTAL IS THROUGHLY CONFUSING. THE APPLICATION
 DESCRIPTION AND NEWEST PLAN DO NOT MATCH, THE SUBMITTAL
 CONSIST OF PLANS FROM MORE THAN ONE DESIGN
 PROFESSIONAL. ONE HAS A SITE PLAN, THE NEW ONE DOES
 NOT. THERE IS ENGINEERING FROM A THIRD DESIGN
 PROFESSIONAL SUPPLIED FOR WINDOW AND DOOR DESIGN
 PRESSURES YET THE BUILDING SHOWING THE AREA OF
 INSTALLATION IS SIGNED AND SEAL BY SOMEONE ELSE. A
 SHUTTER INSTALLATION SCHEDULE HAS BEEN PROVIDE BUT LIST
 THE DOOR AND WINDOW PRODUCT ON IT. WHY IS THAT
 SUPPLIED. ARE WINDOWS ON THE PRIMARY STRUCTURE PROPOSED
 TO BE REPLACED? ALTHOUGH THE NEW PLAN FOR THE ACCESSORY
 BUILDING IS LABLED "STORAGE" IT PRESENTS AS LIVING AREA
 AND ACCORDINGLY IS A CHANGE OF OCCUPANCY AND THE
 PREVIOUS COMMENTS AS FOLLOWS STILL APPLY.
  
 THE VALUATION FOR THE PROPOSED WORK IS LOW AND THE
 SCOPE OF WORK IS UNCLEAR. PROVIDE JUSTIFICATION FOR THE
 CLAIMED VALUE OR REVISE VALUE AND PROVIDE A FULL SCOPE
 OF WORK.
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 FBC 107 - PROVIDE A SURVEY WITH FLOOD DESIGNATION.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BYFAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE WINDOW, WINDOW MULLION, AND DOOR
 SUBMITTALS. PROVIDE DESIGN PRESSURES FOR THE APPLICABLE
 OPENINGS.
  
 THE FOLLOWING APPLIES TO THE GARAGE CONVERSION TO
 LIVING SPACE:
  
 PER TABLE 101.4.1 NONEXEMPT EXISTING BUILDINGS, NOT
 PREVIOUSLY CONDITIONED PERMITTED BEFORE MARCH 1979 AND
 OCCUPANCY TYPE CHANGE MINIMUM EFFICIENCY LEVELS SHALL
 BE MET FOR COMPONENTS BEING CHANGED ENVELOPE: SECTION
 402, WQUIPMENT: SECTION 403, LIGHTING: SECTION 404.
 FBC 107.3.5.1.6 ENERGY CALCULATIONS - PROVIDE AN ENERGY
 SUBMITTAL COMPLIANT WITH FBC-E 103
  
 FBCR TABLE R302.1 EXTERIOR WALLS; MINIMUM
 FIRE-RESISTANCE RATING WITHIN 3 FEET OF PROPERTY LINE
 IS: 1 HOUR-TESTED IN ACCORDANCE WITH ASTM E 119 OR UL
 263 WITH EXPOSURE FROM BOTH SIDES. PROVIDE DETAILS TO
 DEMONSTRATE COMPLIANCE WITH THE FORGOING. FOR THE REAR
 AND WEST WALLS.
  
 FBC 107. PROVIDE FRAMING DETAILS FOR THE INSTALLATION
 OF THE NEW WINDOW AND NEW DOOR.
  
 A NEW WALL SECTION IS PROVIDED, BUT THE PREVIOUS
 COMMENT STILL APPLIES AS FOLLOWS:
 A TYPICAL BEARING WALL DETAIL IS PROVIDED. PLEASE
 CLARIFY WHY THE DETAIL IS PROVIDED AND WHAT WORK
 DEPICTED THERE IS PROPOSED AS NEW.
  
 A COMPLETE REVIEW CANNOT BE COMPLETED DUE TO THE LACK
 OF CLARITY OF THE SUBMITTAL.
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS
 SHALL BE SUBMITTED WHEN APPROVED BY THE BUILDING
 OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION.
  
 PLEASE NOTE IF THESE COMMENTS ARE NOT ADDRES PROPERLY
 ON THE 4TH REVIEW, A PENALTY WILL BE CHARGED.
  
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  
  
  
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-08-25 Cont ID  
Sent By skennedy Date 2015-08-25 Time 07:33 Rev Time 0.00
Received By skennedy Date 2015-08-24 Time 10:06 Sent To  
Notes
2015-08-25 07:58:501ST REVIEW: FBC 2010
  
 THE VALUATION FOR THE PROPOSED WORK IS LOW AND THE
 SCOPE OF WORK IS UNCLEAR. PROVIDE JUSTIFICATION FOR THE
 CLAIMED VALUE OR REVISE VALUE AND PROVIDE A FULL SCOPE
 OF WORK.
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 FBC 107 - PROVIDE A SURVEY WITH FLOOD DESIGNATION.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BYFAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE WINDOW, WINDOW MULLION, AND DOOR
 SUBMITTALS. PROVIDE DESIGN PRESSURES FOR THE APPLICABLE
 OPENINGS.
  
 THE FOLLOWING APPLIES TO THE GARAGE CONVERSION TO
 LIVING SPACE:
  
 PER TABLE 101.4.1 NONEXEMPT EXISTING BUILDINGS, NOT
 PREVIOUSLY CONDITIONED PERMITTED BEFORE MARCH 1979 AND
 OCCUPANCY TYPE CHANGE MINIMUM EFFICIENCY LEVELS SHALL
 BE MET FOR COMPONENTS BEING CHANGED ENVELOPE: SECTION
 402, WQUIPMENT: SECTION 403, LIGHTING: SECTION 404.
 FBC 107.3.5.1.6 ENERGY CALCULATIONS - PROVIDE AN ENERGY
 SUBMITTAL COMPLIANT WITH FBC-E 103
  
 FBCR TABLE R302.1 EXTERIOR WALLS; MINIMUM
 FIRE-RESISTANCE RATING WITHIN 3 FEET OF PROPERTY LINE
 IS: 1 HOUR-TESTED IN ACCORDANCE WITH ASTM E 119 OR UL
 263 WITH EXPOSURE FROM BOTH SIDES. PROVIDE DETAILS TO
 DEMONSTRATE COMPLIANCE WITH THE FORGOING. FOR THE REAR
 AND WEST WALLS.
  
 FBC 107. PROVIDE FRAMING DETAILS FOR THE INSTALLATION
 OF THE NEW WINDOW AND NEW DOOR.
  
 A TYPICAL BEARING WALL DETAIL IS PROVIDED. PLEASE
 CLARIFY WHY THE DETAIL IS PROVIDED AND WHAT WORK
 DEPICTED THERRE IS PROPOSED AS NEW.
  
 A COMPLETE REVIEW CANNOT BE COMPLETED DUE TO THE LACK
 OF CLARITY OF THE SUBMITTAL.
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS
 SHALL BE SUBMITTED WHEN APPROVED BY THE BUILDING
 OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION.
  
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-05-01 Cont ID  
Sent By skennedy Date 2015-05-01 Time 11:13 Rev Time 0.00
Received By skennedy Date 2015-04-28 Time 15:20 Sent To  
Notes
2015-05-01 11:32:561ST REVIEW: FBC 2010
  
 THE REVIEW IS SUSPENDED AS THE SUBMITTAL DOCUMENTS ARE
 PREPARED AND SIGNED AND SEAL BY FERNANDO R, GOMEZ-PINA
 DATED 12/18/14. MR. GOMEZ-PINA VOLUNTARILY RELINQUISHED
 HIS LICENSE NUMBER 14710 ON 12/15/14 ACCORDING TO THE
 DBPR PUBLIC RECORDS.. ACCORDINGLY, THE DOCUMENTS ARE
 NOT IN COMPLIANCE WITH FLORDIA BUILDING CODE SECTION
 107, CHAPTER 471, FLORIDA STATUTES, AND 61G15 FLORIDA
 ADMINISTRATIVE CODE. THE MATTER IS FORWARDED THE
 FLORIDA BOARD OF PROFESSIONAL ENGINEERS.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  
  
2015-04-29 06:51:384/28/15 NOTE: BUILDING TO BE USED AS AN OFFICE ONLY, NO
 SLEEPING OR LIVING SPACE.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2015-12-28 Cont ID  
Sent By skennedy Date 2015-12-28 Time 11:32 Rev Time 0.00
Received By skennedy Date 2015-12-28 Time 11:32 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2015-10-28 Cont ID  
Sent By skennedy Date 2015-10-28 Time 07:42 Rev Time 0.00
Received By skennedy Date 2015-10-28 Time 07:40 Sent To  
Notes
2015-10-28 07:43:272ND REVIEW: FBC 2010 NEC 2008
  
 THE PLAN INDICATES THE DESIGN IS TO COMPLY WITH THE
 2014 NFPA 70 NEC, WHICH IS NOT THE ADOPTED CODE IN
 EFFECT. THE CODE IN EFFECT AT THE TIME OF APPLICATION
 IS THE NEC 2008, BUT YOU MAY CHOOSE THE FBC 5TH EDITION
 RESIDENTIAL IF YOU WISH.
  
 THE ELECTRICAL DESIGN IS UNCLEAR. IS A NEW SERVICE
 PROPOSED? A RISER DIAGRAM IS PROVIDED THAT APPEARS TO
 BE NEW WORK. THERE ARE ALSO MANY NOTES REFERING TO AREA
 NOT ON THE PLAN SUCH AS BATHROOMS AND KITCHENS. ARE YOU
 DOING WORK IN THE PRIMARY BUILDING. ADDITIONALLY, THE
 PANEL SCHEDULE IS TOO SMALL AND NOT LEGIBLE. PROVIDE A
 MORE CLEAR PLAN.
  
 107.2.1 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE. AND RELEVANT
 LAWS,
  
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-08-25 Cont ID  
Sent By skennedy Date 2015-08-25 Time 08:07 Rev Time 0.00
Received By skennedy Date 2015-08-25 Time 08:07 Sent To  
Notes
2015-08-25 08:12:151ST REVIEW: FBC 2010 NEC 2008
  
 NEC 210.52(A)(1)&(2) OUTLET SPACING, IT APPEARS SOME
 POINTS ALONG THE WALL EXCEED 6? FROM AN OUTLET
  
 NEC 210.12B - OUTLETS TO BE AFCI PROTECTED.
  
 NEC 406.11- PROVIDE TAMPER RESISTANT RECEPTACLES.
  
 FBC 1006.1 MEANS OF EGRESS ILLUMINATION. PROVIDE
 ILLUMINATION.
  
 SHOW HOW THE AREA IS FED, PANEL, SUB PANEL, MEANS OF
 DICCONNECT, WIRING METHOD?????
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2015-05-01 Cont ID  
Sent By skennedy Date 2015-05-01 Time 11:13 Rev Time  
Received By skennedy Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2016-02-03 Cont ID  
Sent By skennedy Date 2016-02-03 Time 08:08 Rev Time 0.00
Received By skennedy Date 2016-01-27 Time 13:50 Sent To  
Notes
2016-01-27 13:50:53RESUB ROUTED TO IMPACT FEES

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-01-07 Cont ID  
Sent By shill Date 2016-01-07 Time 17:36 Rev Time 0.00
Received By shill Date 2015-12-02 Time 12:53 Sent To  
Notes
2015-12-02 12:53:33RESUB ROUTED TO SKENNEDY

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-10-28 Cont ID  
Sent By skennedy Date 2015-10-28 Time 16:15 Rev Time 0.00
Received By skennedy Date 2015-10-14 Time 14:44 Sent To  
Notes
2015-10-14 14:45:50SKENNEDY'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-08-25 Cont ID  
Sent By skennedy Date 2015-08-25 Time 08:12 Rev Time 0.00
Received By skennedy Date 2015-05-06 Time 10:49 Sent To Z
Notes
2015-05-07 11:43:11SENT TO SGRAHAM
2015-05-07 10:49:29ROUTE TO S.KENNEDY'S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-05-01 Cont ID  
Sent By skennedy Date 2015-05-01 Time 11:13 Rev Time 0.00
Received By skennedy Date 2015-03-23 Time 14:11 Sent To  
Notes
2015-04-08 14:11:30R33
  
  
2015-03-23 14:41:13ROUTED TO MISC 1

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2016-02-03 Cont ID  
Sent By skennedy Date 2016-02-03 Time 08:08 Rev Time 0.00
Received By skennedy Date 2016-02-03 Time 08:08 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2015-10-28 Cont ID  
Sent By skennedy Date 2015-10-28 Time 07:01 Rev Time 0.00
Received By skennedy Date 2015-10-28 Time 07:01 Sent To  
Notes
2015-10-28 07:02:412ND REVIEW: FBC 2010 RESIDENTIAL
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE PLAN AND
 TAKE TO THAT OFFICE FOR REVIEW. PLEASE RETURNED STAMPED
 WITH A COPY OF RECEIPT AS APPLICABLE.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-08-25 Cont ID  
Sent By skennedy Date 2015-08-25 Time 07:58 Rev Time 0.00
Received By skennedy Date 2015-08-25 Time 07:58 Sent To  
Notes
2015-08-25 08:00:471ST REVIEW: FBC 2010
  
 THE FOLLOWING APPLIES TO THE PLANNED CONVERSION OF THE
 GARAGE TO LIVING SPACE.
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE PLAN AND
 TAKE TO THAT OFFICE FOR REVIEW. PLEASE RETURNED STAMPED
 WITH A COPY OF RECEIPT AS APPLICABLE.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2015-12-28 Cont ID  
Sent By skennedy Date 2015-12-28 Time 11:32 Rev Time 0.00
Received By skennedy Date 2015-12-28 Time 11:32 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2015-10-28 Cont ID  
Sent By skennedy Date 2015-10-28 Time 07:35 Rev Time 0.00
Received By skennedy Date 2015-10-28 Time 07:35 Sent To  
Notes
2015-10-28 07:40:372ND REVIEW: FBC 2010
  
 THESE ARE REPEAT COMMENTS FROM THE PREVIUOS REVIEW.
  
 THE FOLLOWING APPLIES TO THE PLANNED CONVERSION OF THE
 GARAGE TO LIVING SPACE.
  
 FBCE-103.2.1.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM 402
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO
 DEMONSTRATE CODE COMPLIANCE BY THIS METHOD.
  
 FBCE-103.2.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM 405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 FBC-EC 403.2.5 PROVIDE A SIZING CALCULATION
  
 FBC- 107.3.5.3 PROVIDE A MECHANICAL PLAN/SPECIFY
 EQUIPMENT PER FBC-R M16. IT APPEARS YOU PLAN TO PUT A
 MECHANICAL UNIT IN THE REAR WALL, BUT THE WALL IS
 REQUIRED TO BE FIRE RATED THEREFORE YOU MAY NOT CHOOSE
 THIS LOCATION FOR THE UNIT.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2015-08-25 Cont ID  
Sent By skennedy Date 2015-08-25 Time 08:01 Rev Time 0.00
Received By skennedy Date 2015-08-25 Time 08:01 Sent To  
Notes
2015-08-25 08:04:001ST REVIEW: FBC 2010
  
 THE FOLLOWING APPLIES TO THE PLANNED CONVERSION OF THE
 GARAGE TO LIVING SPACE.
  
 FBCE-103.2.1.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM 402
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO
 DEMONSTRATE CODE COMPLIANCE BY THIS METHOD.
  
 FBCE-103.2.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM 405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 FBC-EC 403.2.5 PROVIDE A SIZING CALCULATION
  
 FBC- 107.3.5.3 ? PROVIDE A MECHANICAL PLAN TO SHOW
 SUPPLY DUCTS PER FBC-R M16.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2015-05-01 Cont ID  
Sent By skennedy Date 2015-05-01 Time 11:13 Rev Time  
Received By skennedy Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status P Date 2015-10-28 Cont ID  
Sent By sgraham Date 2015-10-28 Time 16:01 Rev Time 0.00
Received By sgraham Date 2016-01-04 Time 08:29 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2015-10-28 Cont ID  
Sent By   Date 2015-10-28 Time   Rev Time 0.00
Received By   Date 2015-10-28 Time   Sent To B
Notes
2015-10-28 12:08:2910/28/15 SUBMIT NEW SURVEYS

Review Stop Z ZONING
Rev No 2 Status P Date 2015-05-13 Cont ID  
Sent By skennedy Date 2015-08-25 Time 08:12 Rev Time 0.00
Received By sgraham Date 2015-05-13 Time 12:06 Sent To B
Notes
2015-05-13 12:07:495/13/15 PROVISO: BUILDING CAN NOT BE USED AS A SLEEPING
 ROOM, ONLY AN OFFICE

Review Stop Z ZONING
Rev No 1 Status P Date 2015-04-28 Cont ID  
Sent By sgraham Date 2015-04-28 Time 15:11 Rev Time 0.00
Received By sgraham Date 2015-04-28 Time 15:11 Sent To  
Notes
***NONE***