Plan Review Details - Permit 15030955
Plan Review Stops For Permit 15030955
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-05-22 Cont ID  
Sent By jwitmer Date 2015-05-22 Time 11:45 Rev Time 0.00
Received By jwitmer Date 2015-05-22 Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-04-30 Cont ID  
Sent By jwitmer Date 2015-04-30 Time 15:46 Rev Time 0.00
Received By jwitmer Date 2015-04-30 Time 15:15 Sent To  
Notes
2015-04-30 15:46:35BUILDING PLAN REVIEW
 W. P. B. PERMIT:15030955
 ADD: 400 N. FLAGLER SUITE: 803
 CONT: MARYJULI
 TEL: (561)386-6032
 E-MAIL:
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 NOTICE!!!!!!!!!!! NOTICE!!!!!!!!!!!!!: CHAPTER
 553.80(2)(B) FLORIDA STATUTES STATES THAT A LOCAL
 GOVERNMENT SHALL IMPOSE A FEE OF FOUR TIMES THE FEE FOR
 PLAN REVIEW, IF PLANS ARE REJECTED (3) OR MORE TIMES
 FOR REPEATED FAILURE TO CORRECT A CODE VIOLATION.
  
  
 2ND REVIEW
 DATE: THURS. APRIL 30/ 2015
 ACTION: DENIED
  
 1) 2ND REQUEST, THE DESIGNER OF RECORD HAS NOT REVIEWED
 THE PRODUCT APPROVAL AND PUT THEIR SHOP DRAWING STAMP
 OF APPROVAL.
 SHEET 1 INDICATES NEW SLIDING GLASS DOORS:2010 FBC-B
 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41 COMPONENTS
 & CLADDING, NO APPROVALS SUBMITTED.
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
  
  
 2) 2ND REQUEST. 2010 FBC 107.3.4.1 PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE
 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 3) SHEET A1 INDICATES THE WIND DESIGN, NOTE THIS IS A
 225 FT HIGHRISE BUILDING WITH A D EXPOSURE, THE
 PRESSURES STATED ON THE PLANS APPEAR TO BE FOR 60 FT.
 ABOVE GRADE, D EXPOSURE. NEGATIVE PRESSURES ARE TAKEN
 FROM THE ROOF, PLEAS PROVIDE CALCULATIONS ON HOW THESE
 PRESSURES WERE DERIVED. THE UNIT FLOOR PLAN IN RELATION
 TO THE BUILDING CAN NOT IDENTIFY IF THIS IS IN A END
 ZONE(ZONE # 5) OR INTERIOR ZONE (ZONE # 4).
  
 4) 2ND REQUEST. SUBMITTED IN WITH THE PLANS IS
 DOCUMENTS FOR FLOOR INSULATION PROFLEX 90 FLOOR
 INSULATION, PLEASE NOTE THERE WERE A FEW PERMITS ISSUED
 WITH THIS PRODUCT BUT IT HAS BEEN BROUGHT TO OUR
 ATTENTION THIS REPORT WITH A INSULATION CLASS OF IIC 72
 IS WITH A DROPPED CEILING. THE PRODUCT IS TO BE TESTED
 WITH FLOOR TILE, THIN-SET, INSULATION MATERIAL AND 6
 INCH THICK CONCRETE SLAB. SEE THE FOLLOWING CODE
 REQUIREMENTS, THE FULL TEST DOCUMENTS REQUIRED.
  
 4A)PLEASE NOTE THE PROFLEX TEST SUBMITTED FOR THE ASTM
 E 492 FOR THE IIC RATING OF 68 BD IS WITH A DROP
 CEILING AND 3 1/2 INCHES OF INSULATION. THE TEST
 SUBMITTED ASTM E-90 FOR THE STC RATING OF 72 DB ALSO
 HAS A DROPPED CEILING, 10 PLENUM, 3 1/2 INCHES OF
 INSULATION. THE TEST HAVE TO BE WITH A 6 INCH SLAB AND
 NO DROPPED CEILING.
  
 4A) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 4B) FBC-B 2010 1207.2 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 4C) FLAME SPREAD- FBC-B 2010 603.1.2 EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 4D) FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 703.4 NONCOMBUSTIBILITY TESTS.
 THE TESTS INDICATED IN SECTIONS 703.4.1 AND 703.4.2
 SHALL SERVE AS CRITERIA FOR ACCEPTANCE OF BUILDING
 MATERIALS AS SET FORTH IN SECTIONS 602.2, 602.3 AND
 602.4 IN TYPE I, II, III AND IV CONSTRUCTION. THE TERM
 ?NONCOMBUSTIBLE? DOES NOT APPLY TO THE FLAME SPREAD
 CHARACTERISTICS OF INTERIOR FINISH OR TRIM MATERIALS. A
 MATERIAL SHALL NOT BE CLASSIFIED AS A NONCOMBUSTIBLE
 BUILDING CONSTRUCTION MATERIAL IF IT IS SUBJECT TO AN
 INCREASE IN COMBUSTIBILITY OR FLAME SPREAD BEYOND THE
 LIMITATIONS HEREIN ESTABLISHED THROUGH THE EFFECTS OF
 AGE, MOISTURE OR OTHER ATMOSPHERIC CONDITIONS.
  
 703.4.1 ELEMENTARY MATERIALS.
 MATERIALS REQUIRED TO BE NONCOMBUSTIBLE SHALL BE TESTED
 IN ACCORDANCE WITH ASTM E 136.
  
 703.4.2 COMPOSITE MATERIALS.
 MATERIALS HAVING A STRUCTURAL BASE OF NONCOMBUSTIBLE
 MATERIAL AS DETERMINED IN ACCORDANCE WITH SECTION
 703.4.1 WITH A SURFACING NOT MORE THAN 0.125 INCH (3.18
 MM) THICK THAT HAS A FLAME SPREAD INDEX NOT GREATER
 THAN 50 WHEN TESTED IN ACCORDANCE WITH ASTM E 84 OR UL
 723 SHALL BE ACCEPTABLE AS NONCOMBUSTIBLE MATERIALS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-03-26 Cont ID  
Sent By   Date 2015-03-26 Time 06;58 Rev Time 0.00
Received By jwitmer Date 2015-03-26 Time 06:33 Sent To  
Notes
2015-03-26 06:38:18BUILDING PLAN REVIEW
 W. P. B. PERMIT:15030955
 ADD: 400 N. FLAGLER SUITE: 803
 CONT: MARYJULI
 TEL: (561)386-6032
 E-MAIL:
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 IMPORTANT NOTICE: EFFECTIVE MARCH 30, 2015
 ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED
 ELECTRONICALLY
 UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS
 SUBMISSION OPTIONS ARE AS FOLLOWS:
 1 UPLOAD VIA THE PROJECT DOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL
 SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED
 NAMING CONVENTION FOR EACH DOCUMENT
 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER
 DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE
 REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT
 TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS
 ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES
 AVAILABLE
  
 1ST REVIEW
 DATE: THURS. MARCH 26/ 2015
 ACTION: DENIED
  
 1) SHEET 1 INDICATES NEW SLIDING GLASS DOORS:2010 FBC-B
 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41 COMPONENTS
 & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
  
  
 2) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 3) WITH THE NEW WINDOWS AND SLIDDING GLASS DOORS THE
 PLANS DO NOT PROVIDE THE WIND DESIGN CRITERIA;
 WIND DESIGN CRITERIA
 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
  
  
 3.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 3.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 3.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 3.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 3.5) COMPONENTS & CLADDING PRESSURES POSITIVE &
 NEGATIVE TABLE 1609.2(2) .
  
 4) SUBMITTED IN WITH THE PLANS IS DOCUMENTS FOR FLOOR
 INSULATION PROFLEX 90 FLOOR INSULATION, PLEASE NOTE
 THERE WERE A FEW PERMITS ISSUED WITH THIS PRODUCT BUT
 IT HAS BEEN BROUGHT TO OUR ATTENTION THIS REPORT WITH A
 INSULATION CLASS OF IIC 72 IS WITH A DROPPED CEILING.
 THE PRODUCT IS TO BE TESTED WITH FLOOR TILE, THIN-SET,
 INSULATION MATERIAL AND 6 INCH THICK CONCRETE SLAB. SEE
 THE FOLLOWING CODE REQUIREMENTS, THE FULL TEST
 DOCUMENTS REQUIRED.
  
 4A) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 4B) FBC-B 2010 1207.2 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 4C) FLAME SPREAD- FBC-B 2010 603.1.2 EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 703.4 NONCOMBUSTIBILITY TESTS.
 THE TESTS INDICATED IN SECTIONS 703.4.1 AND 703.4.2
 SHALL SERVE AS CRITERIA FOR ACCEPTANCE OF BUILDING
 MATERIALS AS SET FORTH IN SECTIONS 602.2, 602.3 AND
 602.4 IN TYPE I, II, III AND IV CONSTRUCTION. THE TERM
 ?NONCOMBUSTIBLE? DOES NOT APPLY TO THE FLAME SPREAD
 CHARACTERISTICS OF INTERIOR FINISH OR TRIM MATERIALS. A
 MATERIAL SHALL NOT BE CLASSIFIED AS A NONCOMBUSTIBLE
 BUILDING CONSTRUCTION MATERIAL IF IT IS SUBJECT TO AN
 INCREASE IN COMBUSTIBILITY OR FLAME SPREAD BEYOND THE
 LIMITATIONS HEREIN ESTABLISHED THROUGH THE EFFECTS OF
 AGE, MOISTURE OR OTHER ATMOSPHERIC CONDITIONS.
  
 703.4.1 ELEMENTARY MATERIALS.
 MATERIALS REQUIRED TO BE NONCOMBUSTIBLE SHALL BE TESTED
 IN ACCORDANCE WITH ASTM E 136.
  
 703.4.2 COMPOSITE MATERIALS.
 MATERIALS HAVING A STRUCTURAL BASE OF NONCOMBUSTIBLE
 MATERIAL AS DETERMINED IN ACCORDANCE WITH SECTION
 703.4.1 WITH A SURFACING NOT MORE THAN 0.125 INCH (3.18
 MM) THICK THAT HAS A FLAME SPREAD INDEX NOT GREATER
 THAN 50 WHEN TESTED IN ACCORDANCE WITH ASTM E 84 OR UL
 723 SHALL BE ACCEPTABLE AS NONCOMBUSTIBLE MATERIALS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-04-09 Cont ID  
Sent By rlecky Date 2015-04-09 Time 12:51 Rev Time 0.00
Received By rlecky Date 2015-04-09 Time 12:29 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-03-25 Cont ID  
Sent By pleduc Date 2015-03-25 Time   Rev Time 0.00
Received By pleduc Date 2015-03-25 Time 14:51 Sent To  
Notes
2015-03-25 15:01:50THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PROVISO:
  
 THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF THE
 FIRE ALARM AND SPRINKLER SYSTEM FOR CODE COVERAGE AND
 COMPLIANCE.
  
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-05-22 Cont ID  
Sent By jwitmer Date 2015-05-22 Time 11:45 Rev Time 0.00
Received By jwitmer Date 2015-05-22 Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-04-30 Cont ID  
Sent By jwitmer Date 2015-04-30 Time 15:47 Rev Time 0.00
Received By jwitmer Date 2015-04-23 Time 10:53 Sent To  
Notes
2015-04-30 15:19:04BUILDING PLAN REVIEW
 W. P. B. PERMIT:15030955
 ADD: 400 N. FLAGLER SUITE: 803
 CONT: MARYJULI
 TEL: (561)386-6032
 E-MAIL:
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: THURS. APRIL 30/ 2015
 ACTION: DENIED
  
 1) 2ND REVIEW, THE SUBMITTED PRODUCT APPROVAL HAS NOT
 BEEN REVIEWED BY THE DESIGNER OF RECORD. NOTSHEET 1
 INDICATES NEW SLIDING GLASS DOORS:2010 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.41 COMPONENTS &
 CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
  
  
 2) 2ND REVIEW. THE DESIGNER OF RECORD HAS NOT STAMP
 PLANS WITH SHOP DRAWING OF APPROVAL. 2010 FBC 107.3.4.1
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED
 BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 3) SHEET A-1 PLEASE PROVIDE THE CALCULATION FOR WIND
 PRESSURES, IT APPEARS THESE PRESSURES WERE TAKEN FOR A
 HEIGHT OF 60 FT. NOTE THE NEGATIVE PRESSURES ARE TAKEN
 FROM THE ROOF HEIGHT, POSITIVE PRESSURES BUILD UP FROM
 GRADE.
  
 4) 2ND REQUEST. SUBMITTED IN WITH THE PLANS IS
 DOCUMENTS FOR FLOOR INSULATION PROFLEX 90 FLOOR
 INSULATION, PLEASE NOTE THERE WERE A FEW PERMITS ISSUED
 WITH THIS PRODUCT BUT IT HAS BEEN BROUGHT TO OUR
 ATTENTION THIS REPORT WITH A INSULATION CLASS OF IIC 72
 IS WITH A DROPPED CEILING. THE PRODUCT IS TO BE TESTED
 WITH FLOOR TILE, THIN-SET, INSULATION MATERIAL AND 6
 INCH THICK CONCRETE SLAB. SEE THE FOLLOWING CODE
 REQUIREMENTS, THE FULL TEST DOCUMENTS REQUIRED.
  
 4A) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 4B) FBC-B 2010 1207.2 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 4C) FLAME SPREAD- FBC-B 2010 603.1.2 EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 703.4 NONCOMBUSTIBILITY TESTS.
 THE TESTS INDICATED IN SECTIONS 703.4.1 AND 703.4.2
 SHALL SERVE AS CRITERIA FOR ACCEPTANCE OF BUILDING
 MATERIALS AS SET FORTH IN SECTIONS 602.2, 602.3 AND
 602.4 IN TYPE I, II, III AND IV CONSTRUCTION. THE TERM
 ?NONCOMBUSTIBLE? DOES NOT APPLY TO THE FLAME SPREAD
 CHARACTERISTICS OF INTERIOR FINISH OR TRIM MATERIALS. A
 MATERIAL SHALL NOT BE CLASSIFIED AS A NONCOMBUSTIBLE
 BUILDING CONSTRUCTION MATERIAL IF IT IS SUBJECT TO AN
 INCREASE IN COMBUSTIBILITY OR FLAME SPREAD BEYOND THE
 LIMITATIONS HEREIN ESTABLISHED THROUGH THE EFFECTS OF
 AGE, MOISTURE OR OTHER ATMOSPHERIC CONDITIONS.
  
 703.4.1 ELEMENTARY MATERIALS.
 MATERIALS REQUIRED TO BE NONCOMBUSTIBLE SHALL BE TESTED
 IN ACCORDANCE WITH ASTM E 136.
  
 703.4.2 COMPOSITE MATERIALS.
 MATERIALS HAVING A STRUCTURAL BASE OF NONCOMBUSTIBLE
 MATERIAL AS DETERMINED IN ACCORDANCE WITH SECTION
 703.4.1 WITH A SURFACING NOT MORE THAN 0.125 INCH (3.18
 MM) THICK THAT HAS A FLAME SPREAD INDEX NOT GREATER
 THAN 50 WHEN TESTED IN ACCORDANCE WITH ASTM E 84 OR UL
 723 SHALL BE ACCEPTABLE AS NONCOMBUSTIBLE MATERIALS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-04-28 Cont ID  
Sent By jwitmer Date 2015-04-28 Time 10:52 Rev Time  
Received By jwitmer Date 2015-03-23 Time   Sent To  
Notes
2015-03-23 13:36:28INCOMING SENT TO B11.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2015-04-28 Cont ID  
Sent By hmoser Date 2015-04-28 Time 10:35 Rev Time 0.00
Received By hmoser Date 2015-04-28 Time 10:35 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-04-21 Cont ID  
Sent By tklarge Date 2015-04-21 Time 05:30 Rev Time 0.00
Received By tklarge Date 2015-04-12 Time 07:06 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2015-03-27 Cont ID  
Sent By ajones Date 2015-03-27 Time 10:34 Rev Time 0.00
Received By ajones Date 2015-03-27 Time 10:34 Sent To  
Notes
***NONE***