Plan Review Details - Permit 15030931
Plan Review Stops For Permit 15030931
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-04-29 Cont ID  
Sent By shill Date 2015-04-29 Time 07:25 Rev Time 0.00
Received By shill Date 2015-04-29 Time 07:25 Sent To  
Notes
2015-04-29 07:26:11OK PER A LANGE
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-04-10 Cont ID  
Sent By shill Date 2015-04-10 Time 17:25 Rev Time 0.00
Received By shill Date 2015-04-10 Time 17:25 Sent To  
Notes
2015-04-10 17:25:10****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. THE CERTIFICATE OF AUTHORIZATION FOR THE ENGINEERING
 FIRM TO BE ON THE TITLE BLOCK, FS 471, FAC61G15-23.002.
  
 2. PROVIDE A VERIFIABLE COPY OF THE CONTRACT FOR THIS
 JOB, FBC 109. VALAUE TO INCLUDE LABOR AND MATERIALS,
 EVEN IF MATERIALS IS PROVIDED BY OTHERS.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-04-21 Cont ID  
Sent By shill Date 2015-04-21 Time 09:08 Rev Time 0.00
Received By dhayes Date 2015-04-21 Time 09:08 Sent To B
Notes
2015-04-21 09:09:06APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN APPROVED
 PROVISIONALLY. FAILURE TO CORRECT THE LISTED
 DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED
 INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION
 FEE(S).
  
 505.2.4 EXTERIOR LIGHTING CONTROLS.
 LIGHTING FOR ALL EXTERIOR APPLICATIONS NOT EXEMPTED IN
 SECTION 505.1 SHALL HAVE AUTOMATIC CONTROLS CAPABLE OF
 TURNING OFF EXTERIOR LIGHTING WHEN SUFFICIENT DAYLIGHT
 IS AVAILABLE OR WHEN THE LIGHTING IS NOT REQUIRED
 DURING NIGHTTIME HOURS. LIGHTING NOT DESIGNATED FOR
 DUSK-TO-DAWN OPERATION SHALL BE CONTROLLED BY EITHER A
 COMBINATION OF A PHOTOSENSOR AND A TIME SWITCH, OR AN
 ASTRONOMICAL TIME SWITCH.
  
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-03-30 Cont ID  
Sent By misc2 Date 2015-03-30 Time 16:12 Rev Time 0.00
Received By dhayes Date 2015-03-30 Time 16:07 Sent To B
Notes
2015-03-30 16:11:523/30/2015
 PROJECT: AUTOZONE
 PERMIT#: 15030931
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) NEC 600.3, AND 110(3)(B)
 ELECTRIC SIGNS, SECTION SIGNS, AND OUTLINE LIGHTING
 FIXED, MOBILE, OR PORTABLE, SHALL BE LISTED AND
 INSTALLED IN CONFORMANCE WITH THAT LISTING, UNLESS
 OTHERWISE APPROVED BY SPECIAL PERMISSION. NEC 600.3
 LISTING.
  
 2) NEC 600.6(A)(1)
 EACH SIGN AND OUTLINE LIGHTING SYSTEM, OR FEEDER
 CIRCUIT OR BRANCH CIRCUIT SUPPLYING A SIGN OR OUT-LINE
 LIGHTING SYSTEM, SHALL BE CONTROLLED BY AN EXTERNALLY
 OPERABLE SWITCH OR CIRCUIT BREAKER THAT WILL OPEN ALL
 UNGROUNDED CONDUCTORS WITHIN SIGHT OF THE SIGN NEC
 600.6(A)(1)
  
 3) FBC-E 505.2.4
 ALL EXTERIOR LIGHTING NOT EXEMPTED BY FBC 505.1 SHALL
 HAVE AUTOMATIC CONTROLS TO TURN OFF AT DAYLIGHT OR WHEN
 NOT REQUIRED. CONTROLS SHALL BE PHOTOSENSOR & TIME
 CLOCK OR ASTRONOMICAL TIME SWITCH. ALL TIME SWITCHES
 SHALL BE CAPABLE OF RETAINING PROGRAMING DURING A LOSS
 OF POWER FOR A MINIMUM OF 10 HOURS. FBC-E 505.2.4
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-04-29 Cont ID  
Sent By shill Date 2015-04-29 Time 07:26 Rev Time 0.00
Received By shill Date 2015-04-20 Time   Sent To  
Notes
2015-04-20 16:20:43INCOMING SENT TO D. HAYES' DESK.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-04-10 Cont ID  
Sent By shill Date 2015-04-10 Time 17:25 Rev Time 0.00
Received By shill Date 2015-04-10 Time 17:25 Sent To  
Notes
2015-03-23 10:25:13ZONING

Review Stop Z ZONING
Rev No 1 Status P Date 2015-03-25 Cont ID  
Sent By jroach Date 2015-03-25 Time 16:40 Rev Time 0.00
Received By jroach Date 2015-03-25 Time 16:40 Sent To E
Notes
***NONE***