Plan Review Details - Permit 15030795
Plan Review Stops For Permit 15030795
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2016-02-09 Cont ID  
Sent By shill Date 2016-02-09 Time 17:00 Rev Time 0.00
Received By shill Date 2016-02-09 Time 14:55 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2016-01-25 Cont ID  
Sent By shill Date 2016-01-25 Time 16:53 Rev Time 0.00
Received By shill Date 2016-01-25 Time 09:33 Sent To  
Notes
2016-01-25 16:55:53****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. THE SQUARE FOOT AREA ON THE PLANS STAMPED BY PALM
 BEACH COUNTY HAS CHANGED. PLEASE HAVE THE PLANS
 STAMPED, AND PROVIDE (NEW) RECEIPT SHOWING THAT FEES
 WERE PAID, IF APPLICABLE.
  
 2. PLAN SPECIFIES BOTH CONCRETE ROOF TILE (OFFICE AREA)
 AND A HOT MOP SYSTEM OVER THE FLAT ROOF. PRODUCT
 APPROVALS WERE NOT SUBMITTED FOR EITHER OF THOSE
 PRODUCTS. SEALOFLEX PRODUCT APPROVAL WAS SUBMITTED,
 CLARIFY LOCATION OF INSTALLATION, FBC 107. THIS MAY BE
 DONE VIA LETTER OR BY REVISING THE PLAN.
  
 THE ROOF PRODUCT APPROVALS CAN BE A PROVISO ITEM
 (PROVIDE WITH ROOF PERMIT APPLICATION, PRIOR TO
 INSTALLATION). WILL THE EXISTING ROOF HAVE THE
 SEALOFLEX SYSTEM INSTALLED? A MOISTURE SURVEY IS
 REQUIRED FOR A ROOF RECOVERY (INCLUDING COATINGS); THIS
 CAN ALSO BE A PROVISO ITEM.
  
 3. REGARDING DOOR #1, THE MAIN ENTRY DOOR, THIS IS A
 PART OF AN ACCESSIBLE ROUTE, FBC 2010 ACCESSIBILITY
 404.2.5, PROVIDE INFORMATION WHICH DEMONSTRATES
 COMPLIANCE WITH THE THRESHOLD HEIGHT (1/2" MAX)
 LIMITATION (PGT "FD-750 OUTSWING ALUMINUM FRENCH DOOR"
 NOA 14-1117.05.
  
 4. THE FLORIDA STATE PRODUCT APPROVAL APROVIDED IS FOR
 2014 CODE; GOVERNING CODE FOR THIS PROJECT IS FBC 2010.
 EITHER PROVIDE A PRODUCT APPROVAL FOR FBC 2010 OR
 REQUEST ALTERNATIVE MATERIALS AND METHODS FOR
 CONSIDERATION (FBC 104.11).
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2015-12-16 Cont ID  
Sent By jwitmer Date 2015-12-16 Time 15:11 Rev Time 0.00
Received By jwitmer Date 2015-12-16 Time 13:19 Sent To  
Notes
2015-12-16 15:06:55BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15030795
 ADD: 5390 GEORGIA AVE.
 CONT: TIM GIVENS BUILDING
 TEL: (561)533-5825
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: WED. DEC. 16I/2015
 ACTION: DENIED
  
 1-3) COMPLIED.
  
 4A)(1) SEMI- COMPLIED. THE PLANS DO NOT PROVIDE
 OCCUPANCY SEPARATION WALLS. PLEASE IDENTIFY THE
 OCCUPANCY SEPARATION WALLS BETWEEN THE F1 & S1
 OCCUPANCIES AND HOUR RATING OF WALL AND OPENING
 PROTECTIVE.
 2010 FBC-B TABLE 508.4
 2010 FBC-B TABLE 715.4.
  
 4A)(2) COMPLIED. 1 ? HR. OPENING PROTECTION. DOOR # 4
 IS SHOWN TO BE IN A 2 HOUR FIRE RATED WALL, THE DOOR
 SCHEDULE INDICATES THIS DOOR IS TO HAVE GLAZING IN THE
 DOOR, PLEASE PROVIDE THE AMOUNT OF SQ. INCHES IN THIS
 DOOR. 2010 FBC-B TABLE 715.5.4.
  
 4B)NEW ISSUE: THE CARPENTRY WORK SHOP (F1 OCCUPANCY)
 AND S1 THE WOOD STORAGE DID NOT REQUIRE A FIRE BARRIER
 ( TABLE 508.4). THE NEW SET OF PLANS NOW SHOWS A CAR
 PARKED WITHIN THE SPACE PREVIOUSLY SHOWN AS A F1/ S1
 OCCUPANCY. CAR STORAGE IN A RESIDENCE IS A U OCCUPANCY
 BUT IN A COMMERCIAL APPLICATION SECTION 2010 FBC-B
 311.3 PUTS OPEN AND ENCLOSED GARAGES AS A S-2 LOW
 HAZARD. TABLE 508.4 WILL REQUIRE A 2 HR. WALL BETWEEN
 THE S2 ENCLOSED GARAGE AND THE F1 & S1 OCCUPANCIES.
  
 4C) 2010 FBC-B 406.4.2 VENTILATION. A MECHANICAL
 VENTILATION SYSTEM SHALL BE PROVIDED IN ACCORDANCE WITH
 THE FLORIDA BUILDING CODE, MECHANICAL.
  
 5-11) COMPLIED.
  
 12) COMPLIED. 2010 FBC 107.3.4.1 PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE
 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 13) NOTICE ONLY! THIS PROJECT HAS REQUESTED PRIVATE
 PROVIDER TEW & TAYLOR FOR ONSITE INSPECTIONS. FORMS
 HAVE BEEN SUBMITTED AND FILED OUT.
  
 13A)NOTICE ONLY! PLEASE CALL THE CITY OF WEST PALM
 BEACHES AUTOMATED TELEPHONE INSPECTIONS LINE (561)
 805-6700) FOR IN-PROGRESS INSPECTIONS FOR AUDITING OF
 JOBSITE INSPECTIONS.
  
 14) COMPLIED. IMPACT FEES PAID TO PALM BEACH COUNTY.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-09-03 Cont ID  
Sent By jwitmer Date 2015-09-03 Time 15:24 Rev Time 0.00
Received By jwitmer Date 2015-09-03 Time 11:34 Sent To  
Notes
2015-09-03 15:24:43BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15030795
 ADD: 5390 GEORGIA AVE.
 CONT: TIM GIVENS BUILDING
 TEL: (561)533-5825
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: THURS. SEPT. 03/2015
 ACTION: DENIED
  
 1) COMPLIED.
  
 2)COMPLIED. THE CALCULATED VALUE OF THE PROPOSED
 PROJECT IS $214,564.00.
 LANDSCAPE 15,000.00
 PAVING 8,000.00
 LOW VOLTAGE 2,500.00
 _____________
 NET CALC. VALUE THIS PERMIT $189,064.00
  
 3) COMPLIED. THE SUBMITTED SOILS REPORTS .
  
 4A)(1) SEMI- COMPLIED. THE PLANS DO NOT PROVIDE
 OCCUPANCY SEPARATION WALLS. PLEASE IDENTIFY THE
 OCCUPANCY SEPARATION WALLS BETWEEN THE F1 & S1
 OCCUPANCIES AND HOUR RATING OF WALL AND OPENING
 PROTECTIVE.
 2010 FBC-B TABLE 508.4
 2010 FBC-B TABLE 715.4.
 UNKNOWN DOOR, NOT IDENTIFIED BETWEEN THE F1 & S1
 OCCUPANCIES. 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 4A)(2) DOOR # 4 IS SHOWN TO BE IN A 2 HOUR FIRE RATED
 WALL, THE DOOR SCHEDULE INDICATES THIS DOOR IS TO HAVE
 GLAZING IN THE DOOR, PLEASE PROVIDE THE AMOUNT OF SQ.
 INCHES IN THIS DOOR. 2010 FBC-B TABLE 715.5.4.
  
 4B) SPECIFIC OCCUPANCY REQUIREMENTS: NOTE IF THE
 CARPENTRY STUDIO AND OR CARPENTER WORK SHOP SHOW
 COMPLIANCE WITH:
  
 4B) (1) COMPLIED. NOTE LESS THAN 2500 SQ. FT. SCALES ON
 PLAN 2105 SQ. FT. W FBC-M 903.2.4.1 WOODWORKING
 OPERATIONS. AN AUTOMATIC SPRINKLER SYSTEM SHALL BE
 PROVIDED THROUGHOUT ALL GROUP F-1 OCCUPANCY FIRE AREAS
 THAT CONTAIN WOODWORKING OPERATIONS IN EXCESS OF 2,500
 SQUARE FEET (232 M2) IN AREA WHICH GENERATE FINELY
 DIVIDED COMBUSTIBLE WASTE OR USE FINELY DIVIDED
 COMBUSTIBLE MATERIALS.
  
 4B)(2) EXISTING OCCUPANCY. FBC-M 503.2 FANS. PARTS OF
 FANS IN CONTACT WITH EXPLOSIVE OR FLAMMABLE VAPORS,
 FUMES OR DUSTS SHALL BE OF NONFERROUS OR NONSPARKING
 MATERIALS, OR THEIR CASING SHALL BE LINED OR
 CONSTRUCTED OF SUCH MATERIAL. WHEN THE SIZE AND
 HARDNESS OF MATERIALS PASSING THROUGH A FAN ARE CAPABLE
 OF PRODUCING A SPARK, BOTH THE FAN AND THE CASING SHALL
 BE OF NONSPARKING MATERIALS. WHEN FANS ARE REQUIRED TO
 BE SPARK RESISTANT, THEIR BEARINGS SHALL NOT BE WITHIN
 THE AIRSTREAM, AND ALL PARTS OF THE FAN SHALL BE
 GROUNDED. FANS IN SYSTEMS-HANDLING MATERIALS THAT ARE
 CAPABLE OF CLOGGING THE BLADES, AND FANS IN BUFFING OR
 WOODWORKING EXHAUST SYSTEMS, SHALL BE OF THE
 RADIAL-BLADE OR TUBE-AXIAL TYPE.
  
 4B)(3) EXISTING OCCUPANCY. FBC-M [F] 510.2.1 LUMBER
 YARDS AND WOODWORKING FACILITIES.
 EQUIPMENT OR MACHINERY LOCATED INSIDE BUILDINGS AT
 LUMBER YARDS AND WOODWORKING FACILITIES WHICH GENERATES
 OR EMITS COMBUSTIBLE DUST SHALL BE PROVIDED WITH AN
 APPROVED DUST-COLLECTION AND EXHAUST SYSTEM INSTALLED
 IN CONFORMANCE WITH THIS SECTION AND THE FLORIDA FIRE
 PREVENTION CODE. EQUIPMENT AND SYSTEMS THAT ARE USED TO
 COLLECT, PROCESS OR CONVEY COMBUSTIBLE DUSTS SHALL BE
 PROVIDED WITH AN APPROVED EXPLOSION-CONTROL SYSTEM.
  
 4B)(4) EXISTING OCCUPANCY. FBC-M 511.4 WOOD PROCESSING
 AND WOODWORKING FACILITIES.
 WOOD PROCESSING FACILITIES THAT PRODUCE OR UTILIZE
 FINELY DIVIDED WOOD PARTICLES OR WOOD FIBERS SHALL
 CONFORM WITH NFPA 664.
 EXCEPTION: FACILITIES WITH AN AREA OF 2,000 SQUARE FEET
 (185.8 M2) OR LESS AND HAVE A DUST COLLECTION FLOW RATE
 OF 1500 CUBIC FEET PER MINUTE (0.708 M3/SEC) OR LESS.
  
 5) 2ND REQUEST . SHEET A100 THE RESTROOM DOES NOT
 COMPLY WITH THE 2010 FL ACCESSIBILITY CODE 604.3.2.
  
 6) COMPLIED. SHEET A100 THE CONFERENCE ROOM SHOWS A WET
 BAR PLEASE SHOW COMPLIANCE WITH 2010 FL ACC. CODE
 606.1-5.
  
 7) COMPLIED. SHEET A100 THE RECEPTION DESK DOES NOT
 INDICATE COMPLIANCE WITH 2010 FBC- ACCESS. 04.4 SALES
 AND SERVICE COUNTERS. SALES COUNTERS AND SERVICE
 COUNTERS SHALL COMPLY WITH 904.4.1 OR 904.4.2.
  
 8 )COMPLIED. SHEET A400 THE DOORS IDENTIFIED AS 2 & 3
 IN THE DOOR SCHEDULE AS A 2 FT. 8 INCH DOORS. 2010 FL
 ACC. CODE THE DOORS WILL NEED TO COMPLY WITH 404.2.3
 CLEAR WIDTH. DOOR OPENINGS SHALL PROVIDE A CLEAR WIDTH
 OF 32 INCHES (815 MM) MINIMUM. CLEAR OPENINGS OF
 DOORWAYS WITH SWINGING DOORS SHALL BE MEASURED BETWEEN
 THE FACE OF THE DOOR AND THE STOP, WITH THE DOOR OPEN
 90 DEGREES.
  
 9) COMPLIED. THE DOOR THAT LEADS TO THE RESTROOM DOES
 NOT COMPLY WITH 2010 FL ACCESS. CODE 404.2.4
 MANEUVERING CLEARANCES REQUIRING 18 INCHES ON THE LATCH
 SIDE OF THE DOOR. THERE IS A DOOR IDENTIFICATION TAG #
 6 BUT THERE ARE 2 DOORS IN THIS LOCATION WHICH IS IT
 FOR, OR FOR BOTH?
  
 8A) 2ND REQUEST, NOTE THE WIND DESIGN FOUND ON S-4.0
 INDICATES THE EXPOSURE AS A ?D? SHOULD BE A ?C? BUT NOT
 A ?B?.
 SHEET S-3.0 THE ROOF WIND DESIGN IS OFF, THE POSITIVE
 PRESSURES ARE HIGHER THAN THE NEGATIVE PRESSURES, THE
 OTHER ISSUE, ZONES 2 & 3 HAVE THE SAME PRESSURE, THE
 ROOF WIND DESIGN CHART DOES NOT INDICATE IF THESE
 VALUES ARE IN VULT OR VASD OR WHAT SQ. FT OF TRIBUTARY
 AREA THIS CHART IS FOR. 2010 FBC-B 1609.1.1
 DETERMINATION OF WIND DESIGN- CHAPTER 6 OF ASCE 7-10.
  
 8B) COMPLIED. SHEET S4.0 THE WINDOW AND DOOR PRESSURES
 ARE PROVIDED. THE NORTH ELEVATION THE CORNER ZONE # 5
 THE WINDOW PRESSURES ARE LOW. THE SOUTH ELEVATION OF
 THE NORTH WING THE PRESSURES ARE LOW IN ZONES 5 THE
 UPPER AND LOWER WINDOWS, IN ZONE 4 THE UPPER AND LOWER
 WINDOW PRESSURES ARE ALSO LOW. 2010 FBC-B 1609.1.1
 DETERMINATION OF WIND DESIGN- CHAPTER 6 OF ASCE 7-10.
  
 8C) 2ND REQUEST, HAND WRITTEN ON SHEET A -100.
 PRESSURES FOR THE OFFICE DOOR ARE NOT PROVIDED. 2010
 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN- CHAPTER 6
 OF ASCE 7-10.
  
 8D) THE SOUTH WING NORTH ELEVATION THE PRESSURES ARE
 LOW FOR BOTH WINDOW ZONES 4 & 5. 2010 FBC-B 1609.1.1
 DETERMINATION OF WIND DESIGN- CHAPTER 6 OF ASCE 7-10.
 THE GARAGE DOOR PRESSURES ARE ALSO LOW..
  
 8E) 2ND REQUEST, HAND WRITTEN IN ON SHEET A-100. DOOR 8
 ON THE SOUTH WING PRESSURES ARE NOT PROVIDED.
  
 9-10) COMPLIED.
  
 11) SEMI-COMPLIED. NO ROOFING SUBMITTALS HAVE BEEN
 PROVIDED FOR WOOD DECKS.
 APPROVED. NOA 10-0608.05 SEALOFLEX WATERPROOFING SYSTEM
 FOR CONCRETE DECKS .
  
 12) COMPLIED. 2010 FBC 107.3.4.1 PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE
 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 13) NOTICE ONLY! THIS PROJECT HAS REQUESTED PRIVATE
 PROVIDER TEW & TAYLOR FOR ONSITE INSPECTIONS. FORMS
 HAVE BEEN SUBMITTED AND FILED OUT.
  
 13A)NOTICE ONLY! PLEASE CALL THE CITY OF WEST PALM
 BEACH?S AUTOMATED TELEPHONE INSPECTIONS LINE (561)
 805-6700) FOR IN-PROGRESS INSPECTIONS FOR AUDITING OF
 JOBSITE INSPECTIONS.
  
 14) COMPLIED. BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 15) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-04-02 Cont ID  
Sent By jwitmer Date 2015-03-31 Time 07:43 Rev Time 0.00
Received By jwitmer Date 2015-03-31 Time 06:28 Sent To  
Notes
2015-03-31 09:22:08BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15030795
 ADD: 5390 GEORGIA AVE.
 CONT: TIM GIVENS BUILDING
 TEL: (561)533-5825
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. MARCH 30/2015
 ACTION: DENIED
  
 IMPORTANT NOTICE: EFFECTIVE MARCH 30, 2015
 ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED
 ELECTRONICALLY
 UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS
 SUBMISSION OPTIONS ARE AS FOLLOWS:
 1 UPLOAD VIA THE PROJECT DOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL
 SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED
 NAMING CONVENTION FOR EACH DOCUMENT
 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER
 DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE
 REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT
 TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS
 ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES
 AVAILABLE
  
 1) COVERSHEET A-000 THE BUILDING AREA CALCULATIONS
 APPEAR NOT TO INCLUDE UNDER ROOF PARKING AND DUMPSTER
 ENCLOSURE. ALL AREA UNDER ROOF OR FOOTPRINT OF BUILDING
 IS TO BE CONSIDERED IN THE BUILDING SQUARE FOOT AREA.
 2010 FBC-B DEFINITIONS AREA, BUILDING.
  
 2) THE PERMIT VALUE OF $150,000.00 IS LOW. THE
 CALCULATED VALUE OF THE PROPOSED PROJECT IS
 $214,564.00.
 PERMIT FEES/ PLAN REVIEW:
 THE PERMIT APPLIED VALUE IS STATED AS $4,055,000 THE
 CALCULATED VALUE IS $4,131,694.00 IN VALUE. W P B
 ADMINISTRATIVE CODE 108.2 SCHEDULE OF PERMIT FEES. ON
 BUILDINGS, STRUCTURES, ELECTRICAL, GAS, MECHANICAL AND
 PLUMBING SYSTEMS OR ALTERATIONS REQUIRING A PERMIT, A
 FEE FOR EACH PERMIT SHALL BE PAID AS REQUIRED, IN
 ACCORDANCE WITH THE SCHEDULE ESTABLISHED BY THE
 APPLICABLE GOVERNING AUTHORITY.
  
 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 3) THE SUBMITTED SOILS REPORTS ARE COPIES NOT ORIGINAL
 SIGNED AND SEALED DOCUMENTS. PLANS, SPECIFICATIONS,
 REPORTS OR OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC RECORD SHALL
 HAVE THE SIGNATURE AND SEAL OF THE DESIGN PROFESSIONAL
 AFFIXED TO THE DOCUMENT. FL ADMIN CODE 61G15-23.002
 ENGINEERS
  
 4) MISSING FROM THE SET OF PLANS IS A LIFE SAFETY PLAN.
 THIS PLAN WILL NEED TO SHOW COMPLIANCE WITH:
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION,
 107.3.5.1.1 MINIMUM PLAN REVIEW CRITERIA FOCOMMERCIAL
 BUILDINGS
 LIFE SAFETY PLAN SHOW FURNATURE AND EQUIPMENT
 OCCUPANCY LOAD
 GROSS
 NET
 MEANS OF EGRESS
 EXIT ACCESS
 EXIT
 EXIT DISCHARGE
 STAIRS CONSTRUCTION/GEOMETRY AND PROTECTION
 DOORS
 EMERGENCY LIGHTING AND EXIT SIGNS
 SPECIFIC OCCUPANCY REQUIREMENTS:
  
 2) SPECIFIC OCCUPANCY REQUIREMENTS: NOTE IF THE
 CARPENTRY STUDIO AND OR CARPENTER WORK SHOP SHOW
 COMPLIANCE WITH:
  
 2A) FBC-M 903.2.4.1 WOODWORKING OPERATIONS. AN
 AUTOMATIC SPRINKLER SYSTEM SHALL BE PROVIDED THROUGHOUT
 ALL GROUP F-1 OCCUPANCY FIRE AREAS THAT CONTAIN
 WOODWORKING OPERATIONS IN EXCESS OF 2,500 SQUARE FEET
 (232 M2) IN AREA WHICH GENERATE FINELY DIVIDED
 COMBUSTIBLE WASTE OR USE FINELY DIVIDED COMBUSTIBLE
 MATERIALS.
  
 2B) FBC-M 503.2 FANS. PARTS OF FANS IN CONTACT WITH
 EXPLOSIVE OR FLAMMABLE VAPORS, FUMES OR DUSTS SHALL BE
 OF NONFERROUS OR NONSPARKING MATERIALS, OR THEIR CASING
 SHALL BE LINED OR CONSTRUCTED OF SUCH MATERIAL. WHEN
 THE SIZE AND HARDNESS OF MATERIALS PASSING THROUGH A
 FAN ARE CAPABLE OF PRODUCING A SPARK, BOTH THE FAN AND
 THE CASING SHALL BE OF NONSPARKING MATERIALS. WHEN FANS
 ARE REQUIRED TO BE SPARK RESISTANT, THEIR BEARINGS
 SHALL NOT BE WITHIN THE AIRSTREAM, AND ALL PARTS OF THE
 FAN SHALL BE GROUNDED. FANS IN SYSTEMS-HANDLING
 MATERIALS THAT ARE CAPABLE OF CLOGGING THE BLADES, AND
 FANS IN BUFFING OR WOODWORKING EXHAUST SYSTEMS, SHALL
 BE OF THE RADIAL-BLADE OR TUBE-AXIAL TYPE.
  
 2C) FBC-M [F] 510.2.1 LUMBER YARDS AND WOODWORKING
 FACILITIES.
 EQUIPMENT OR MACHINERY LOCATED INSIDE BUILDINGS AT
 LUMBER YARDS AND WOODWORKING FACILITIES WHICH GENERATES
 OR EMITS COMBUSTIBLE DUST SHALL BE PROVIDED WITH AN
 APPROVED DUST-COLLECTION AND EXHAUST SYSTEM INSTALLED
 IN CONFORMANCE WITH THIS SECTION AND THE FLORIDA FIRE
 PREVENTION CODE. EQUIPMENT AND SYSTEMS THAT ARE USED TO
 COLLECT, PROCESS OR CONVEY COMBUSTIBLE DUSTS SHALL BE
 PROVIDED WITH AN APPROVED EXPLOSION-CONTROL SYSTEM.
  
 2D) FBC-M 511.4 WOOD PROCESSING AND WOODWORKING
 FACILITIES.
 WOOD PROCESSING FACILITIES THAT PRODUCE OR UTILIZE
 FINELY DIVIDED WOOD PARTICLES OR WOOD FIBERS SHALL
 CONFORM WITH NFPA 664.
 EXCEPTION: FACILITIES WITH AN AREA OF 2,000 SQUARE FEET
 (185.8 M2) OR LESS AND HAVE A DUST COLLECTION FLOW RATE
 OF 1500 CUBIC FEET PER MINUTE (0.708 M3/SEC) OR LESS.
  
 3) SHEET A100 THE RESTROOM DOES NOT COMPLY WITH THE
 2010 FL ACCESSIBILITY CODE 604.3.2.
  
 4) SHEET A100 THE CONFERENCE ROOM SHOWS A WET BAR
 PLEASE SHOW COMPLIANCE WITH 2010 FL ACC. CODE 606.1-5.
  
 5) SHEET A100 THE RECEPTION DESK DOES NOT INDICATE
 COMPLIANCE WITH 2010 FBC- ACCESS. 04.4 SALES AND
 SERVICE COUNTERS.
 SALES COUNTERS AND SERVICE COUNTERS SHALL COMPLY WITH
 904.4.1 OR 904.4.2.
  
 6) SHEET A400 THE DOORS IDENTIFIED AS 2 & 3 IN THE DOOR
 SCHEDULE AS A 2 FT. 8 INCH DOORS. 2010 FL ACC. CODE THE
 DOORS WILL NEED TO COMPLY WITH 404.2.3 CLEAR WIDTH.
 DOOR OPENINGS SHALL PROVIDE A CLEAR WIDTH OF 32 INCHES
 (815 MM) MINIMUM. CLEAR OPENINGS OF DOORWAYS WITH
 SWINGING DOORS SHALL BE MEASURED BETWEEN THE FACE OF
 THE DOOR AND THE STOP, WITH THE DOOR OPEN 90 DEGREES.
  
 7) THE DOOR THAT LEADS TO THE RESTROOM DOES NOT COMPLY
 WITH 2010 FL ACCESS. CODE 404.2.4 MANEUVERING
 CLEARANCES REQUIRING 18 INCHES ON THE LATCH SIDE OF THE
 DOOR. THERE IS A DOOR IDENTIFICATION TAG # 6 BUT THERE
 ARE 2 DOORS IN THIS LOCATION WHICH IS IT FOR, OR FOR
 BOTH?
  
 8A) SHEET S-3.0 THE ROOF WIND DESIGN IS OFF, THE
 POSITIVE PRESSURES ARE HIGHER THAN THE NEGATIVE
 PRESSURES, THE OTHER ISSUE, ZONES 2 & 3 HAVE THE SAME
 PRESSURE, THE ROOF WIND DESIGN CHART DOES NOT INDICATE
 IF THESE VALUES ARE IN VULT OR VASD OR WHAT SQ. FT OF
 TRIBUTARY AREA THIS CHART IS FOR. 2010 FBC-B 1609.1.1
 DETERMINATION OF WIND DESIGN- CHAPTER 6 OF ASCE 7-10.
  
 8B) SHEET S4.0 THE WINDOW AND DOOR PRESSURES ARE
 PROVIDED. THE NORTH ELEVATION THE CORNER ZONE # 5 THE
 WINDOW PRESSURES ARE LOW. THE SOUTH ELEVATION OF THE
 NORTH WING THE PRESSURES ARE LOW IN ZONES 5 THE UPPER
 AND LOWER WINDOWS, IN ZONE 4 THE UPPER AND LOWER WINDOW
 PRESSURES ARE ALSO LOW. 2010 FBC-B 1609.1.1
 DETERMINATION OF WIND DESIGN- CHAPTER 6 OF ASCE 7-10.
  
 8C) PRESSURES FOR THE OFFICE DOOR ARE NOT PROVIDED.
 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
  
 8D) THE SOUTH WING NORTH ELEVATION THE PRESSURES ARE
 LOW FOR BOTH WINDOW ZONES 4 & 5. 2010 FBC-B 1609.1.1
 DETERMINATION OF WIND DESIGN- CHAPTER 6 OF ASCE 7-10.
 THE GAGE DOOR PRESSURES ARE NOT PROVIDED.
  
 8E) DOOR 8 ON THE SOUTH WING PRESSURES ARE NOT
 PROVIDED.
  
 9) THE WINDOW, MULLION AND DOOR PRODUCT APPROVALS
 SUBMITTED DO NOT INDICATE THE SIZE OF THE UNIT, TYPE OF
 GLAZING TO BE INSTALLED, MULLION SIZE AND OR IF
 RE-INFORCED ANCHOR TYPE OR SIZE. PLEASE IDENTIFY THESE
 COMPONENTS SO A PLAN REVIEW OF THSE ITEMS CAN TAKE
 PLACE.
  
 10) CLOPAY GARAGE DOORS DOES NOT HAVE THE COVER SHEETS
 FOR EITHER A FLORIDA APPROVAL OR A MIAMI-DADE NOA.
  
 11) NO ROOFING SUBMITTALS HAVE BEEN PROVIDED.
  
 12) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 13) THIS PROJECT WILL REQUIRE A RESIDENT INSPECTOR
 BECAUSE OF THE STEEL THAT WILL BE WELDED ON SITE AND
 THE CONCRETE HOLLOW PLANK SYSTEM. 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION, 110.3.9 OTHER INSPECTIONS SERVICES. THE
 BUILDING OFFICIAL MAY MAKE, OR CAUSE TO BE MADE BY
 OTHERS, THE INSPECTIONS REQUIRED BY SECTION 109. HE/SHE
 MAY ACCEPT REPORTS OF INSPECTORS OF RECOGNIZED
 INSPECTION SERVICES, PROVIDED THAT AFTER INVESTIGATION
 HE/SHE IS SATISFIED AS TO THEIR QUALIFICATIONS AND
 RELIABILITY. A CERTIFICATE CALLED FOR BY ANY PROVISION
 OF THE TECHNICAL CODES SHALL NOT BE BASED ON SUCH
 REPORTS UNLESS THE SAME ARE IN WRITING AND CERTIFIED BY
 A RESPONSIBLE OFFICER OF SUCH SERVICE. THE BUILDING
 OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY AN INSPECTION
 SERVICE IN THE FOLLOWING INSTANCES:
  
 1. FOR BUILDINGS OR ADDITIONS OF TYPE I OR II
 CONSTRUCTION
 2. FOR ALL MAJOR STRUCTURAL ALTERATIONS
 3. WHERE THE CONCRETE DESIGN IS BASED ON COMPRESSIVE
 STRENGTH (F ?C) IN EXCESS OF 3000
 POUNDS PER SQUARE INCH
 4. FOR PILE DRIVING
 5. FOR BUILDINGS WITH AREA GREATER THAN 20,000 SQUARE
 FOOT
 6. FOR BUILDINGS MORE THAN 2 STORIES IN HEIGHT
 7. FOR BUILDINGS AND STRUCTURES OF UNUSUAL DESIGN OR
 METHODS OF CONSTRUCTION
  
 13A) FOR THE RESIDENT INSPECTOR PLEASE PROVIDE A
 RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT.
 THE RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
 CONTACT KEN CONRAD
 TEL: 561-805-6666
 E-MAIL: [email protected]
  
 13B) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION. THIS MAY BE
 SUBMITTED TO KEN CONRAD BY E-MAIL. KEN CONRAD:
 [email protected]
  
 13C) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE
 REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, THE
 PERMIT LIBRARIAN WILL E-MAIL YOU, THE APPROVED AND
 BATCH STAMPED PLANS SO YOU MAY PRINT YOUR PLANS, TWO
 SETS OF PLANS WILL NEED TO BE PRINTED IN COLOR, (1) FOR
 THE RESIDENT INSPECTOR, THE OTHER FOR THE MEP
 INSPECTORS.
  
 13D) PLEASE CALL THE CITY OF WEST PALM BEACH?S
 AUTOMATED TELEPHONE INSPECTIONS LINE (561) 805-6700)
 FOR IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS.
  
 NOTE: RESIDENT INSPECTOR FORMS ARE BEING SENT TO:
 [email protected]
  
 14) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 15) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-01-28 Cont ID  
Sent By rlecky Date 2016-01-28 Time 14:58 Rev Time 0.00
Received By rlecky Date 2016-01-28 Time 12:33 Sent To  
Notes
2016-01-29 10:17:42ISSUED WITH ELECTRICAL PROVISO:
  
 PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION
 FOR THE SERVICE, PANEL BOARDS AND MAIN DISCONNECTING
 MEANS. NEC 110.16, 110.22
 PROVIDE HIGH LEG IDENTIFICATION AT THE ELECTRICAL
 SERVICE AND PANEL BOARDS. NEC 408.3, 110.15, 230.56
 SERVICE NEUTRAL REQUIRED FOR 3 PHASE SERVICE. NEC
 250.24(C)
 PROVIDE GFCI PROTECTION FOR GENERAL PURPOSE RECEPTACLES
 IN GARAGE. NEC 210.8
 PROVIDE A INTERSYSTEM BONDING BAR AT THE ELECTRICAL
 SERVICE. NEC 250 .94
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-09-23 Cont ID  
Sent By skennedy Date 2015-09-23 Time 08:10 Rev Time 0.00
Received By skennedy Date 2015-09-23 Time 08:10 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-04-10 Cont ID  
Sent By dhayes Date 2015-04-10 Time 16:15 Rev Time 0.00
Received By dhayes Date 2015-04-10 Time 16:15 Sent To  
Notes
2015-04-10 16:15:554/10/2015
 PROJECT: 5390 GEORGIA AVE ADDITION AND SITE WORK
 PERMIT#: 15030795
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) REVISE THE RISER DIAGRAM TO ADDRESS THE FOLLOWING:
 A) THE 3PHASE ELECTRICAL FEEDERS TO REFLECT THE CORRECT
 NUMBER OF CONDUCTORS FOR A 3PHASE FEEDER.
 B) PROVIDE THE NUMBER, SIZE, AND TYPE OF WIRES IN THE
 SERVICE ENTRANCE RISER CONDUITS.
  
 2) INDICATE COMPLIANCE WITH FBC-E 505.2 FOR INTERIOR
 AND EXTERIOR LIGHTING CONTROL.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 4 Status P Date 2016-02-09 Cont ID  
Sent By mgonzale Date 2016-02-09 Time   Rev Time 1.00
Received By mgonzale Date 2016-02-09 Time   Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 3 Status F Date 2016-01-20 Cont ID  
Sent By cranford Date 2016-01-20 Time 11:22 Rev Time 0.00
Received By cranford Date 2016-01-20 Time 11:22 Sent To  
Notes
2016-01-20 11:22:57WILL REVIEW NEXT SUBMITTAL

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2015-09-02 Cont ID  
Sent By cranford Date 2015-09-02 Time 13:55 Rev Time 0.00
Received By cranford Date 2015-09-02 Time 13:55 Sent To  
Notes
2015-09-02 13:56:06ALSO SEE ENGINEERING REVIEW UNDER E15080045

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2015-04-29 Cont ID  
Sent By cranford Date 2015-04-29 Time 09:13 Rev Time 0.00
Received By cranford Date 2015-04-29 Time 08:43 Sent To  
Notes
2015-04-29 09:12:491. THE PROPOSED MODIFICATIONS, WHICH INCLUDE THE
 INSTALLATION OF AN EXFILTRATION TRENCH, INSTALLATION OF
 A NEW DUMPSTER ENCLOSURE, AND CONSTRUCTION OF BATHROOM
 FACILITIES WHICH WILL RESULT IN AN INCREASE IN POTABLE
 WATER DEMAND AND SANITARY DISCHARGE RATES WILL REQUIRE
 REVIEW AND APPROVAL THROUGH THE ENGINEERING DIVISION OF
 THE PUBLIC WORKS DEPARTMENT. ENGINEERING DEVELOPMENT
 APPROVAL FROM THE CITY?S PUBLIC WORKS DEPARTMENT IS
 REQUIRED FOR ALL PROJECTS INVOLVING OR AFFECTING THE
 CITY?S STREET RIGHT-OF-WAYS, EASEMENTS, POTABLE WATER
 SYSTEM, SANITARY SEWER SYSTEM, STORMWATER SYSTEM, SOLID
 WASTE COLLECTION, OR PEDESTRIAN AND VEHICULAR TRAFFIC.
 THIS INCLUDES ANY WORK THAT INCREASES IMPERVIOUS AREAS;
 CHANGES THE DIRECTION, VELOCITY, OR TIMING OF
 STORMWATER DISCHARGE; OR CREATES A CONDITION OF
 ENVIRONMENTAL CONCERN. THE ENGINEERING DEVELOPMENT
 APPROVAL APPLICATION FORMS CAN BE DOWNLOADED AT
 HTTP://WPB.ORG/ENGINEERING/FORMS-AND-PUBLICATIONS
  
 PLEASE SUBMIT AN APPLICATION FOR ENGINEERING
 DEVELOPMENT APPROVAL AND MAKE A NOTE ON THE CIVIL PLANS
 INCLUDED IN THE BUILDING APPLICATION SUBMITTAL THAT
 THEY ARE FOR REFERENCE ONLY.
  
 KELLY CRANFORD, P.E.
 LAND DEVELOPMENT ENGINEER
 PUBLIC WORKS DEPARTMENT
 CITY OF WEST PALM BEACH
 [email protected]
 561-494-1098 (OFFICE)
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2016-01-27 Cont ID  
Sent By pleduc Date 2016-01-27 Time   Rev Time 0.00
Received By pleduc Date 2016-01-27 Time 14:05 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2015-12-03 Cont ID  
Sent By pleduc Date 2015-12-03 Time   Rev Time 0.00
Received By pleduc Date 2015-12-03 Time 15:38 Sent To  
Notes
2015-12-03 15:39:54THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1. ONLY ONE SET OF SUBMITTED PLANS WAS IDENTIFIED. IT
 WAS REVIEWED AND STAMPED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-09-17 Cont ID  
Sent By   Date 2015-09-17 Time   Rev Time 0.00
Received By   Date 2015-09-17 Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-03-26 Cont ID  
Sent By pleduc Date 2015-03-26 Time   Rev Time 0.00
Received By pleduc Date 2015-03-24 Time 16:19 Sent To  
Notes
2015-03-26 12:24:14THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 A LIFE SAFETY PLAN SHALL BE SUBMITTED THAT INCLUDES,
 OCCUPANCY LOADS, EQUIPMENT PLAN, EGRESS PATHS OF
 TRAVEL, COMMON PATHS OF TRAVEL, EXITS THAT LEAD TO A
 PUBLIC WAY, EXIT SIGNS, EMERGENCY LIGHTS, FIRE
 EXTINGUISHER LOCATIONS,
  
 PER NFPA 1, 13.3.2.28 WOODWORKING OPERATIONS. AN
 APPROVED AUTOMATIC FIRE SPRINKLER SYSTEM SHALL BE
 INSTALLED IN BUILDINGS CONTAINING WOODWORKING
 OPERATIONS EXCEEDING 2500 FT2 THAT USE EQUIPMENT,
 MACHINERY, OR APPLIANCES, THAT GENERATE FINELY DIVIDED
 COMBUSTIBLE WASTE, OR THAT USE FINELY DIVIDED
 COMBUSTIBLE MATERIALS.
  
 THE FIRE SPRINKLER SYSTEM SHALL BE MONITORED.
  
 PROVIDE OCCUPANY FIRE RATING SEPARATIONS INCLUDING
 RATED DOORS FROM OFFICE, CARPENTRY SHOP, STORAGE,
 MERCANTILE AREAS, MINIMUM 1 HOUR WITH FIRE SPRINKLER
 SYSTEM.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2016-02-09 Cont ID  
Sent By shill Date 2016-02-09 Time 17:16 Rev Time 0.00
Received By shill Date 2016-02-09 Time 14:55 Sent To  
Notes
2016-02-09 14:55:33TO SH DESK
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-02-09 Cont ID  
Sent By shill Date 2016-02-09 Time 14:55 Rev Time 0.00
Received By shill Date 2016-01-20 Time 13:43 Sent To  
Notes
2016-01-21 13:43:29C37

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-01-21 Cont ID  
Sent By shill Date 2016-01-21 Time 10:40 Rev Time 0.00
Received By shill Date 2015-11-30 Time 13:13 Sent To  
Notes
2015-11-30 13:15:20C19

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-09-23 Cont ID  
Sent By C17 Date 2015-09-23 Time 08:10 Rev Time 0.00
Received By skennedy Date 2015-08-28 Time 09:05 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-04-29 Cont ID  
Sent By   Date 2015-04-29 Time   Rev Time 0.00
Received By shill Date 2015-03-19 Time 07:41 Sent To  
Notes
2015-03-20 07:44:23****EXPEDITED****
 C31
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 5 Status P Date 2016-02-09 Cont ID  
Sent By shill Date 2016-02-09 Time 16:14 Rev Time 0.00
Received By shill Date 2016-02-09 Time 16:14 Sent To  
Notes
2016-02-09 16:15:04IMPACT STAMP 2/8/16 (NO FEE DUE)
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status F Date 2016-01-25 Cont ID  
Sent By shill Date 2016-01-25 Time 14:59 Rev Time 0.00
Received By shill Date 2016-01-25 Time 14:59 Sent To  
Notes
2016-01-25 15:22:40****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 IMPACT FEES WERE ASESSED BASED ON A PAGE WHICH SHOWED
 AN ADDITION OF 1028 SF (8/19/2015). THE SCOPE OF THE
 PROJECT HAS INCREASED. PLEASE TAKE A COPY OF THE PLANS
 TO PALM BEACH COUNTY FOR IMPACT FEE ASSESSMENT,
 233-5025. THE PLANS ARE TO BE STAMPED AND THE NEW
 RECEIPT, IF APPLICABLE, IS TO BE PROVIDED.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2015-12-16 Cont ID  
Sent By jwitmer Date 2015-12-16 Time 14:24 Rev Time 0.00
Received By jwitmer Date 2015-12-16 Time 13:19 Sent To  
Notes
2015-12-16 14:23:57IMPACT FEE REVIEW
 AUGUST 18/ 2015
 MU2015-19987
 ADDITION: 1806 SQ. FT.
 $2882.18
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2015-09-03 Cont ID  
Sent By jwitmer Date 2015-09-03 Time 11:14 Rev Time 0.00
Received By jwitmer Date 2015-09-03 Time 11:11 Sent To  
Notes
2015-09-03 11:14:04PALM BEACH COUNTY IMPACT FEE REVIEW:
 TRACKING NUMBER MU-2015-019987-0000
 RECEIPT NUMBER 2015-0820-93
 FEES: $2,882.18

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-08-26 Cont ID  
Sent By jwitmer Date 2015-04-29 Time   Rev Time  
Received By jwitmer Date 2015-04-29 Time   Sent To  
Notes
2015-05-11 15:01:28BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2016-02-02 Cont ID  
Sent By ccole Date 2016-02-02 Time 08:53 Rev Time 0.00
Received By ccole Date 2016-02-02 Time 08:53 Sent To  
Notes
2016-02-02 08:56:45MECHANICAL PROVISOS
 PERMIT #15030795
 2/2/16
  
 1) CONNECTION OF A PARKING GARAGE WITH ANY ROOM IN
 WHICH THERE IS A FUEL-FIRED APPLIANCE SHALL BE BY MEANS
 OF A VESTIBULE PROVIDING A TWO-DOORWAY SEPARATION-
 SECTION 406.2.8 SPECIAL HAZARDS. FBC-10 BUILDING.
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2015-12-02 Cont ID  
Sent By ccole Date 2015-12-02 Time 13:09 Rev Time 0.00
Received By ccole Date 2015-12-02 Time 12:32 Sent To  
Notes
2015-12-02 13:11:461ST REVIEW 2010 MECHANICAL
 PERMIT #15030795
 12/2/15
  
 1 ) COMMENT #2 FROM THE 1ST REVIEW WILL STAND BASED ON
 THE REVISED DRAWING INDICATING THE ADDITION OF AN
 ENCLOSED PARKING GARAGE ATTACHED TO THE CARPENTRY
 BUILDING. PLEASE REFER TO SECTION 406.3, 406.3.3.1, AND
 406.4.2 FBC-10 BUILDING. SECTION 406.3.3.1: "FOR
 NATURAL VENTILATION PURPOSES, THE EXTERIOR SIDE OF THE
 STRUCTURE SHALL HAVE UNIFORMLY DISTRIBUTED OPENINGS ON
 TWO OR MORE SIDES. THE AREA OF SUCH OPENINGS IN
 EXTERIOR WALLS ON A TIER SHALL BE NOT LESS THAN 20
 PERCENT OF THE TOTAL PERIMETER WALL AREA OF EACH TIER.
 THE AGGREGATE LENGTH OF THE OPENINGS CONSIDERED TO BE
 PROVIDING NATURAL VENTILATION SHALL BE NOT LESS THAN 40
 PERCENT OF THE PERIMETER OF THE TIER. INTERIOR WALLS
 SHALL BE NOT LESS THAN 20 PERCENT OPEN WITH UNIFORMLY
 DISTRIBUTED OPENINGS." PER THE CODE SECTIONS LISTED
 ABOVE, THE BUILDING IS DEFINED AS AN "ENCLOSED GARAGE".
 I HAVE REPRINTED COMMENT #2 FROM THE 1ST REVIEW BELOW.
 2) IN REFERENCE TO NEW PARKING GARAGES PLEASE REVIEW
 SECTION 404.1 FBC-10 MECHANICAL, AND PROVIDE CONTINUOUS
 MECHANICAL VENTILATION OR A VENTILATION SYSTEM DESIGNED
 TO OPERATE AUTOMATICALLY UPON DETECTION OF A
 CONCENTRATION OF CARBON MONOXIDE OF 25 PARTS PER
 MILLION (25 PPM) BY APPROVED AUTOMATIC DETECTION
 DEVICES (CO DETECTORS). PLEASE NOTE THAT AUTO OPERATION
 OF THE SYSTEM SHALL NOT REDUCE THE VENTILATION AIRFLOW
 RATE BELOW 0.05 CFM PER SQ. FT. OF THE FLOOR AREA AND
 THE SYSTEM SHALL BE CAPABLE OF PRODUCING A VENTILATION
 AIRFLOW OF 0.75 CFM PER SQ. FT. OF FLOOR AREA.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2015-09-04 Cont ID  
Sent By ccole Date 2015-09-04 Time 12:26 Rev Time 0.00
Received By ccole Date 2015-09-04 Time 12:26 Sent To  
Notes
2015-09-04 12:54:012ND REVIEW: FBC 2010 MECHANICAL
 PERMIT #15030795
 9/4/15
  
 1) THE NEW ADDITION IS IDENTIFIED AS A NEW CARPENTRY
 STUDIO ON SHEET A-001, AND AS A NEW GARAGE ON ALL OTHER
 PLAN SHEETS. PLEASE MAKE ALL THESE PLANS MATCH ONE WAY
 OR THE OTHER. IF CONSTRUCTING A CARPENTRY STUDIO PLEASE
 PROVIDE AN EQUIPMENT FLOOR PLAN LAYOUT, EQUIPMENT
 SCHEDULE, AND A DUST COLLECTION SYSTEM IN COMPLIANCE
 WITH SECTION 511 FBC-10 MECHANICAL.
 2) IN REFERENCE TO NEW PARKING GARAGES PLEASE REVIEW
 SECTION 404.1 FBC-10 MECHANICAL, AND PROVIDE CONTINUOUS
 MECHANICAL VENTILATION OR A VENTILATION SYSTEM DESIGNED
 TO OPERATE AUTOMATICALLY UPON DETECTION OF A
 CONCENTRATION OF CARBON MONOXIDE OF 25 PARTS PER
 MILLION (25 PPM) BY APPROVED AUTOMATIC DETECTION
 DEVICES (CO DETECTORS). PLEASE NOTE THAT AUTO OPERATION
 OF THE SYSTEM SHALL NOT REDUCE THE VENTILATION AIRFLOW
 RATE BELOW 0.05 CFM PER SQ. FT. OF THE FLOOR AREA AND
 THE SYSTEM SHALL BE CAPABLE OF PRODUCING A VENTILATION
 AIRFLOW OF 0.75 CFM PER SQ. FT. OF FLOOR AREA.
 3) THE AIR HANDLER CLOSET SHALL HAVE A LOUVERED METAL
 DOOR FOR RETURN AIR- SECTION 603.1 FBC-10 MECHANICAL.
 THE ARCHITECTURAL PLANS INDICATE A SOLID WOOD PANELED
 DOOR.
 4) A MIAMI DADE NOA (#14-0731.03) FOR AN ROOF TOP OR
 SIDEWALL EXHAUST FAN HAS BEEN SUBMITTED. THIS DOES NOT
 APPEAR TO BE THE EF-1 IN THE TOILET ROOM. PLEASE
 CLARIFY WHERE THE FAN IS TO BE LOCATED- IT IS NOT SHOWN
 ON THE PLAN
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2015-04-28 Cont ID  
Sent By hmoser Date 2015-04-28 Time 10:27 Rev Time 0.00
Received By hmoser Date 2015-04-28 Time 10:26 Sent To  
Notes
2015-04-11 11:48:29 
  
  
  
  
  
  
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2016-01-23 Cont ID  
Sent By tklarge Date 2016-01-23 Time 05:47 Rev Time 0.00
Received By tklarge Date 2016-01-23 Time 05:24 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2015-12-04 Cont ID  
Sent By gjohnson Date 2015-12-04 Time 16:47 Rev Time 0.00
Received By gjohnson Date 2015-12-04 Time 16:47 Sent To  
Notes
2015-12-04 16:54:203RD REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1.SHEET P1 APPEARS TO BE THE SAME DOES NOT REFLECT THE
 REST OF THE PLANS STIIL SHOWS BAR SINK AND NO WATER
 FOUNTAIN AND THE BATHROOM IS TO SMALL TO MEET
 ACCESSIBILTY CODE PLEASE CORRECT,PER WPB AMEND. TO FBC
 SEC.107.2.1
 2. TWO SETS OF PLANS ARE REQUIRED FOR PLAN REVIEW ONLY
 ONE IS PROVIDED PLEASE CLARIFY.
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2015-09-04 Cont ID  
Sent By gjohnson Date 2015-09-04 Time 17:20 Rev Time 0.00
Received By gjohnson Date 2015-09-04 Time 17:20 Sent To  
Notes
2015-09-04 17:35:492ND REVIEW: FBC 2010
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 561-805-6711
 [email protected]
  
  
 PLUMBING COMMENTS:
  
 1.WIDTH OF NEW BATHROOM DOES NOT ALLOW CLEARANCE AROUND
 TOILET MUST .
 FBC ACC. 2010 604.3.1 SIZE.
 CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES
 (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM THE SIDE
 WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED
 PERPENDICULAR FROM THE REAR WALL.
 2.SHOW HEIGHT OF WET BAR SHALL COMPLY WITH. FBC ACC.
 2010 804.3.2 HEIGHT.
 THE KITCHEN WORK SURFACE SHALL BE 34 INCHES (865 MM)
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
 3.SHEET C1 IS STILL SHOWING 2 WET BARS.
 4. MINIMUM NUMBER OF PLUMBING FIXTURES FBCP 403.
 TABLE 403.1 FOR F1 OCCUPANCY REQUIRES 1 DRINKING
 FOUNTAIN AND 1 SERVICE SINK.

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-04-12 Cont ID  
Sent By tklarge Date 2015-04-12 Time 05:05 Rev Time 0.00
Received By tklarge Date 2015-04-12 Time 03:45 Sent To  
Notes
2015-04-12 04:46:461) SHT. A-000 - BUILDING SUMMARY - NOTES THIS AS A
 LEVEL 1 ALTERATION. HOW CAN THIS BE CLASSIFIED AS A
 LEVEL 1 ALTERATION WHEN IT IS AN ADDITION AND NEW
 CONSTRUCTION? CLARIFY.
 2) SHT. A-000 - BUILDING SUMMARY - THE OCCUPANCY IS
 LISTED AS "I" - INDUSTRIAL. GROUP I OCCUPANCY IS
 INSTITUTIONAL IN CHAPTER 3 OF THE FBC. THIS WOULD BE
 CONSIDERED A GROUP F OCCUPANCY. PLEASE REFER TO CHAPTER
 3 OF THE 2010 FBC FOR THE CORRECT TYPE OF F OCCUPANCY
 AND NOTE THE CORRECT TYPE OF OCCUPANCY ON SHT. A-000.
 3) SHT. A-100 - THE WET BAR SHALL COMPLY WITH THE 2010
 FL. ACCESSIBILITY CODE SEC.212.3 & 606.
 4) THE TOILET ROOM IS NOT WIDE ENOUGH TO PROVIDE THE
 SPACE NEEDED FOR THE PLUMBING FIXTURES PER THE FLORIDA
 ACCESSIBILITY CODE SECS. 604.3,604.3.2, FBC-PLUMBING,
 SEC.404.3.1.
 5) SHTS. C-1, LP-1 SHOWS TWO WET BARS ( ONE ADJACENT TO
 THE NEW TOILET ROOM) AND THE ARCHITECTURAL AND PLUMBING
 SHEET ONLY SHOWS ONE. CLARIFY.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2016-02-09 Cont ID  
Sent By shill Date 2016-02-09 Time 17:07 Rev Time 0.00
Received By shill Date 2016-02-09 Time 17:07 Sent To  
Notes
2016-02-09 17:09:37SEALOFLEX NOA 10-0608.04
 ASSEMBLY ON PAGE 10-11
  

Review Stop Z ZONING
Rev No 4 Status P Date 2016-02-02 Cont ID  
Sent By llouie Date 2016-02-02 Time 16:10 Rev Time 0.00
Received By llouie Date 2016-02-02 Time 11:05 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2015-12-10 Cont ID  
Sent By llouie Date 2015-12-10 Time 17:02 Rev Time 0.00
Received By llouie Date 2015-12-08 Time 12:36 Sent To  
Notes
2015-12-08 12:37:0712/8/15 - MEETING WITH PROJECT ARCHITECT TOMORROW 12/9
 TO DISCUSS CHANGES FROM THE APPROVED PLANS.

Review Stop Z ZONING
Rev No 2 Status F Date 2015-09-18 Cont ID  
Sent By llouie Date 2015-09-18 Time 14:09 Rev Time 0.00
Received By llouie Date 2015-09-18 Time 14:09 Sent To  
Notes
2015-09-18 14:10:36** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) A SITE PLAN SHOWING THE COMPLETE PARKING LAYOUT AND
 ALL SITE CALCULATIONS IS REQUIRED AS PART OF THE PERMIT
 APPLICATION SUBMITTAL. NOTE: THE SITE PLAN FOR THE
 PROPOSED ADDITION WAS APPROVED BY THE PLANNING DIVISION
 ON 11/14/14 (REFERENCE: ISPR CASE NO. 14-04).
  
 2.) THE PERMIT PLANS INDICATE A NEW A/C UNIT, WHICH WAS
 NOT DEPICTED IN THE APPROVED SITE PLAN. THE LOCATION OF
 THE PROPOSED A/C UNIT SHALL NOT CONFLICT WITH THE
 PROPOSED LANDSCAPE IMPROVEMENT ON THE PROPERTY.
  
 3.) SEPARATE PERMIT APPLICATION AND REVIEW REQUIRED FOR
 LANDSCAPING.
  
 PLEASE CONTACT LINDA LOUIE @ (561) 822-1458 IF YOU HAVE
 QUESTIONS.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2015-03-30 Cont ID  
Sent By llouie Date 2015-03-30 Time 10:37 Rev Time 0.00
Received By llouie Date 2015-03-27 Time 15:54 Sent To  
Notes
2015-03-30 10:38:23** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) THE APPLICATION PACKET INDICATES THE INSTALLATION
 OF A NEW A/C UNIT. PLEASE ILLUSTRATE THE LOCATION OF
 THE NEW A/C UNIT IN THE SITE PLAN AND LANDSCAPE PLAN.
 PROVIDE SETBACK DIMENSIONS OF THE A/C UNIT IN
 RELATIONSHIP TO THE PROPERTY LINES AND ENSURE THAT
 THERE IS NO CONFLICT WITH THE LOCATION OF THE NEW A/C
 UNIT WITH THE PROPOSED LANDSCAPE IMPROVEMENTS ON THE
 PROPERTY.
  
 2.) SEPARATE PERMIT APPLICATION AND REVIEW REQUIRED FOR
 LANDSCAPING.
  
 PLEASE NOTE THAT ANY CHANGES ON THE RESUBMITTED PLANS
 MAY RESULT IN ADDITIONAL COMMENTS. CONTACT LINDA LOUIE
 @ (561) 822-1458 IF YOU HAVE QUESTIONS.