Plan Review Details - Permit 15030744
Plan Review Stops For Permit 15030744
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-06-21 Cont ID  
Sent By jwitmer Date 2015-06-21 Time 08:01 Rev Time 0.00
Received By jwitmer Date 2015-06-21 Time 07:28 Sent To  
Notes
2015-06-21 08:11:25BUILDING PROVISO: THE RESTROOM DOOR TO COMPLY WITH 2010
 FBC-B 1008.1.9.11. DURING ITS SWING, ANY DOOR IN A
 MEANS OF EGRESS SHALL LEAVE UNOBSTRUCTED AT LEAST ONE
 HALF OF THE REQUIRED WIDTH OF AN AISLE, CORRIDOR,
 PASSAGEWAY. THE MINIMUM CLEAR WIDTH CLEAR IS 18 INCHES,
 EITHER THE SHELVING NEEDS TO BE REMOVED OR INSWING DOOR
 INTO THE RESTROOM.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-05-01 Cont ID  
Sent By jwitmer Date 2015-05-01 Time 06:31 Rev Time 0.00
Received By jwitmer Date 2015-05-01 Time 06:16 Sent To  
Notes
2015-05-01 06:33:27BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15030744
 ADD: 420 CLEMATIS ST. SUITE : B
 CONT: TBD
 TEL: (561)909-7117
 E-MAIL:
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 IMPORTANT NOTICE: EFFECTIVE MARCH 30, 2015
 ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED
 ELECTRONICALLY
 UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS
 SUBMISSION OPTIONS ARE AS FOLLOWS:
 1 UPLOAD VIA THE PROJECT DOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL
 SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED
 NAMING CONVENTION FOR EACH DOCUMENT
 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER
 DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE
 REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT
 TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS
 ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES
 AVAILABLE
  
 1ST REVIEW
 DATE: THURS./ MARCH 26/ 2015
 ACTION: DENIED
  
 1) A MEETING TOOK PLACE THURSDAY APRIL 30 WITH THE
 TENANTS, AND STAFF INCLUDING ANA MARIA APONTE WITH
 ZONING, URBAN DESIGN. THE PRESENT PLANS DO NOT REFLECT
 COMPLIANCE WITH THE REQUIREMENTS FOR THE ZONING
 REGULATIONS, THE STAFF RECOMENDED DIFFERENT WAYS OF
 COMPLIANCE, THE TENANTS WILL NEED TO DECIDE AND GET
 WITH THERE DESIGN PROFESSIONAL TO UPDATE PLANS TO
 COMPLY WITH THE ZONING CODE. WITH THIS UNDERSTANDING
 THAT THESE PLANS HAVE TO BE REVISED, THIS REVIEW WILL
 NOT BE ABLE TO BE PASSED, IT DOES NOT REFLECT WHAT IS
 TO BE BUILT.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-03-26 Cont ID  
Sent By jwitmer Date 2015-03-26 Time 07:28 Rev Time  
Received By jwitmer Date 2015-03-26 Time 06:59 Sent To  
Notes
2015-03-26 07:05:22BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15030744
 ADD: 420 CLEMATIS ST. SUITE : B
 CONT: TBD
 TEL: (561)909-7117
 E-MAIL:
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 IMPORTANT NOTICE: EFFECTIVE MARCH 30, 2015
 ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED
 ELECTRONICALLY
 UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS
 SUBMISSION OPTIONS ARE AS FOLLOWS:
 1 UPLOAD VIA THE PROJECT DOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL
 SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED
 NAMING CONVENTION FOR EACH DOCUMENT
 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER
 DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE
 REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT
 TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS
 ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES
 AVAILABLE
  
 1ST REVIEW
 DATE: THURS./ MARCH 26/ 2015
 ACTION: DENIED
  
 1) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION 107.3.5.1
 COMMERCIAL BUILDINGS. 107.3.5 MINIMUM PLAN REVIEW
 CRITERIA FOR BUILDINGS. THE EXAMINATION OF THE
 DOCUMENTS BY THE BUILDING OFFICIAL SHALL INCLUDE THE
 FOLLOWING MINIMUM CRITERIA AND DOCUMENTS:
 A).OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS
 SHALL BE DETERMINED.
 B). MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED
 (SEE TABLE 503).
 C). FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL
 INCLUDE THE FOLLOWING COMPONENTS: FIRE-RESISTANT
 SEPARATIONS
 D). FIRE SPRINKLERS YES OR NO REQUIRED YES OR NO
 E). FIFE SAFETY PLAN SHALL INCLUDE THE FOLLOWING:
 FLOOR PLAN WITH FURNITURE/ EQUIPMENT LAYOUT AND MEANS
 OF EGRESS ROUTE
 OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD/
 GROSS OR NET
 MEANS OF EGRESS
 EXIT ACCESS
 EXIT
 EXIT DISCHARGE
 STAIRS CONSTRUCTION/GEOMETRY AND PROTECTION
 DOORS
 EMERGENCY LIGHTING AND EXIT SIGNS
 F). 10. ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE
 FOLLOWING:
 SITE REQUIREMENTS
 ACCESSIBLE ROUTE
 TOILET FACILITIES
 DRINKING FOUNTAINS
  
 2) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2015-07-06 Cont ID  
Sent By dhayes Date 2015-07-06 Time 11:06 Rev Time 0.00
Received By dhayes Date 2015-07-06 Time 10:05 Sent To  
Notes
2015-07-06 11:06:28APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN APPROVED
 PROVISIONALLY. FAILURE TO CORRECT THE LISTED
 DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED
 INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION
 FEE(S).
  
 1) ELECTRIC DRINKING FOUNTAINS SHALL BE PROTECTED WITH
 GROUND FAULT CIRCUIT INTERRUPTER PROTECTION. NEC 422.52
  
 2) WHERE RECEPTACLES ARE INSTALLED WITHIN 1.8 M (6 FT)
 OF THE OUTSIDE EDGE OF THE SINK GROUND-FAULT
 CIRCUIT-INTERRUPTER PROTECTION FOR PERSONNEL IS
 REQUIRED. NEC 210.8 (B) (5) SINKS.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-05-14 Cont ID  
Sent By albarran Date 2015-05-14 Time 14:29 Rev Time 0.00
Received By albarran Date 2015-05-14 Time 14:08 Sent To  
Notes
2015-05-14 14:44:08DISPOSITION AND RESPECTIVE COMMENTS FOR ELECTRICAL PLAN
 REVIEW
 APPLICABLE CODES: FBC 2010; WPB AMENDMENTS TO FBC 2010
 CHAPTER 1; NEC 2008
 REVIEW CYCLE: 2ND REVIEW, MIKE ALBARRAN
 ACTION: FAILED, THIS ELECTRICAL REVIEW FAILED AS
 OUTLINED BELOW:
 1. NEC 600.5 REQUIRES THAT THERE BE A DEDICATED SIGN
 OUTLET AT EVERY ENTRANCE.
 2. NEC 210.62 REQUIRES THAT THERE BE AN SHOW WINDOW
 OUTLET FOR EVERY 12' OF SHOW WINDOW OR FRACTION
 THEREOF. THIS OUTLET SHALL BE WITHIN 18" FROM THE TOP
 OF THE WINDOW.
 3. AN EXIT LIGHT SHALL BE PLACED IN THE AREA OF COMMON
 PATH OF EGRESS TRAVEL INDICATING EXIT TO EITHER
 DIRECTION.
 4. COMPLIANCE W/FBC ENERGY CONSERVATION SECTION 505
 SHALL BE REQUIRED.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-04-07 Cont ID  
Sent By dhayes Date 2015-04-07 Time 15:03 Rev Time 0.00
Received By dhayes Date 2015-04-07 Time 15:03 Sent To  
Notes
2015-04-07 15:19:14NO ELECTRICAL PLANS HAVE BEEN INCLUDED IN THIS
 SUBMITTAL PACKAGE. AN APPLICATION WITH THE DESCRIPTION
 MINOR INTERIOR REMODEL INCLUDING ELECTRIC AND PLUMBING
 FOR NEW FOOT MASSAGE BUSINESS. PROVIDE COMPLETE
 ELECTRICAL PLANS REQUIRED TO INDICATE COMPLIANCE WITH
 THE FBC AND THE NEC
 PROVIDE A FLOOR PLAN INDICATING LOCATIONS FOR THE
 ELECTRICAL SERVICE, ELECTRICAL PANEL(S) FOOT MASSAGE
 EQUIPMENT. LWPB AMENDMENTS TO FBC 107.3.2, NEC 110.26
 PROVIDE A PANEL SCHEDULE INDICATING ALL NEW CIRCUITS
 FOR NEW FOOT MASSAGE EQUIPMENT. NEC 408.4
 PROVIDE A LOAD CALCULATION THAT INCLUDES ALL EXISTING
 PLUS ADDITIONAL BRANCH CIRCUITS REQUIRED FOR NEW FOOT
 MASSAGE EQUIPMENT.
2015-03-23 17:35:56SEE PERMIT APPLICATION. JG.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2015-06-12 Cont ID  
Sent By pleduc Date 2015-06-12 Time   Rev Time 0.00
Received By pleduc Date 2015-06-12 Time 14:00 Sent To  
Notes
2015-06-12 14:15:36THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 1) THERE ARE INCORRECT REFERENCES TO THE FIRE CODE;
 HOWEVER, THEY DO NOT APPEAR TO NEGATIVELY AFFECT THE
 PROJECT. PLEASE ENSURE THAT THE PROJECT MEETS THE
 APPROPRIATE REFERNECE AT THE TIME OF INSPECTION AND
 CORRECT YOUR RECORDS FOR FUTURE SUBMITTALS.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2010 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2010 EDITION.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2009 EDITION.
 FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 10, 2010 EDITION.
 ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION.
  
  
 2) THE DOOR TO THE BATHROOM SWINGS OUT INTO THE EXIT
 CORRIDOR. THE DOOR CAN NOT SWING OUT TO MORE THAN HALF
 OF THE REQUIRED EXIT WIDTH. THE SHALL BE SELF CLOSING
 OR SWING IN TO THE BATHROOM.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-05-04 Cont ID  
Sent By pleduc Date 2015-05-04 Time   Rev Time 0.00
Received By pleduc Date 2015-05-04 Time 15:27 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-03-25 Cont ID  
Sent By pleduc Date 2015-03-25 Time   Rev Time 0.00
Received By pleduc Date 2015-03-25 Time 09:30 Sent To  
Notes
2015-03-25 09:36:58THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PROVIDE A LIFE SAFTY PLAN SHOWING EXITS, EXIT LIGHTS,
 EMERGENCY LIGHTS, EXIT DOOR HARDWARE, FIRE
 EXTINGUISHERS, OCCUPANY LOADS, EGRESS PATHS, COMMON
 PATHS OF TRAVEL, FIRE ALARM DEVICE LOCATIONS, ETC.
  
 PROVIDE EXISTING LIFE SAFETY SYSTEMS, I.E. FIRE ALARM &
 FIRE SPRINKLER. IF LIFE SAFETY SYSTEMS EXIST, PROVIDE A
 NOTE INDICATING: THE NATURE OF THE REMODEL REQUIRES AN
 EVALUATION OF THE FIRE ALARM AND SPRINKLER SYSTEM FOR
 CODE COVERAGE AND COMPLIANCE.
  
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-07-06 Cont ID  
Sent By dhayes Date 2015-07-06 Time 11:06 Rev Time 0.00
Received By dhayes Date 2015-06-12 Time 07:35 Sent To  
Notes
2015-06-12 07:41:23ROUTED TO B04/CC

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-05-27 Cont ID  
Sent By tklarge Date 2015-05-27 Time 03:37 Rev Time 0.00
Received By tklarge Date 2015-04-29 Time 16:45 Sent To  
Notes
2015-04-29 16:46:09B09 "EXPEDITE"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-04-24 Cont ID  
Sent By skennedy Date 2015-04-24 Time 09:38 Rev Time 0.00
Received By skennedy Date 2015-03-18 Time 10:46 Sent To  
Notes
2015-03-23 10:47:23SENT TO B4 FOR REVIEW. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2015-05-01 Cont ID  
Sent By jwitmer Date 2015-05-01 Time 06:34 Rev Time 0.00
Received By jwitmer Date 2015-05-01 Time 06:34 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-03-26 Cont ID  
Sent By jwitmer Date 2015-03-26 Time 07:05 Rev Time 0.00
Received By jwitmer Date 2015-03-26 Time 07:05 Sent To  
Notes
2015-03-26 07:06:45PLANS SUBMITTED WITH INSUFFICIENT INFORMATION TO
 DETERMINE IF COUNTY IMPACR FEES ARE TO BE ASSESSED. A
 THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2015-07-01 Cont ID  
Sent By tklarge Date 2015-07-01 Time 06:14 Rev Time 0.00
Received By tklarge Date 2015-07-01 Time 05:56 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2015-05-27 Cont ID  
Sent By tklarge Date 2015-05-27 Time 03:37 Rev Time 0.00
Received By tklarge Date 2015-05-27 Time 02:42 Sent To  
Notes
2015-05-27 03:30:151)THE PERMIT APPLICATION AND PLANS ARE VAGUE AS TO THE
 EXTENT OF PLUMBING WORK THAT WILL BE DONE IN THIS
 SPACE.SUBMIT INFORMATION AND ON THE PLANS SHOWING THE
 ENTIRE SCOPE OF PLUMBING WORK TO BE DONE.107.1.2.
 SUBMIT TWO COPIES OF CLEAR AND LEGIBLE PLANS FOR
 REVIEW. ONE SET OF PLANS IS SO LIGHT THEY ARE
 ILLEGIBLE.PLANS SHALL BE DRAWN ON A MIN. OF 1/8 " SCALE
 AND SHALL CLEARLY SHOW THE SCOPE OF WORK TO BE DONE.
 WPB AMEND. TO 2010 FBC SEC. 107.2.1
 2) IS ANY EQUIPMENT/ PEDICURE CHAIRS THAT USE WATER
 BEING INSTALLED? IF SO, SUBMIT MANUFACTURER'S
 SPECIFICATIONS & INSTALLATION INSTRUCTIONS FOR THE
 EQUIPMENT.IDENTIFY THE CHAIRS ON THE PLAN IF
 APPLICABLE. NOW THERE IS JUST IMAGES NOTED AS "SEAT
 WITH STOOL".
 3) SUBMIT A WATER RISER FOR REVIEW. WPB AMEND. TO 2010
 FBC SEC.107.3.5.1.3.
 4) BOTH SETS OF PLANS SHALL BE SIGNED AND SEALED BY THE
 DESIGN PROFESSIONAL OF RECORD PER THE FL. ADMIN. CODE
 RULE 61G1-16.003.
 5)SHT. A-1 - HANDICAP DETAILS - THE GRAB BAR SHALL BE
 MEASURED FROM THE FINISH FLOOR TO THE TOP OF THE
 GRIPPING SURFACE, NOT TO THE CENTERLINE AS SHOW. FAC
 SEC. 609.4.
 6) THE TOILET PAPER DISPENSER SHALL BE LOCATED 7-9
 INCHES IN FRONT OF THE WATER CLOSET MEASURED TO THE
 CENTERLINE OF THE DISPENSER. SHOW THIS ON THE HANDICAP
 DETAILS.
 7) THE FINISH SCHEDULE ON SHT A-1 NOTES THE TOILET ROOM
 WALLS TO BE PAINTED AND A 2 INCH WOOD BASE
 INSTALLED.THE BASE SHALL BE A MINIMUM OF 4 INCHES AND
 COMPLY WITH FBC SEC.1210.1. THE WALLS & PARTITIONS
 WITHIN 2 FEET OF WATER CLOSETS SHALL HAVE SMOOTH, HARD,
 NONABSORBENT SURFACE, TO A HEIGHT OF 4 FEET ABOVE THE
 FLOOR AND COMPLY WITH FBC SEC. 1210.2.
 8) INDICATE ON THE PLANS WHAT PLUMBING IS NEW AND WHAT
 IS EXISTING TO REMAIN. WPB AMEND. TO FBC SEC. 107.2.1.
 9) SHT. E-1 SHOWS A 100 GALLON WATER HEATER. IS THIS
 CORRECT?
 10) SHT. E-1 - SUBMIT A WATER RISER DIAGRAM FOR REVIEW.
 WPB AMEND. TO FBC SEC. 107.3.5.1.3. THE PLAN VIEW
 REQUIRES A MAGNIFYING GLASS TO REVIEW. PLANS SHALL BE
 DRAWN ON A MIN. OF 1/8 " SCALE AND SHALL CLEARLY SHOW
 THE SCOPE OF WORK TO BE DONE. WPB AMEND. TO 2010 FBC
 SEC. 107.2.1
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-04-17 Cont ID  
Sent By tklarge Date 2015-04-17 Time 05:43 Rev Time 0.00
Received By tklarge Date 2015-04-17 Time 05:29 Sent To  
Notes
2015-04-17 05:43:111)THE PERMIT APPLICATION AND PLANS ARE VAGUE AS TO THE
 EXTENT OF PLUMBING WORK THAT WILL BE DONE IN THIS
 SPACE.SUBMIT INFORMATION AND ON THE PLANS SHOWING THE
 ENTIRE SCOPE OF PLUMBING WORK TO BE DONE.107.1.2.
 SUBMIT TWO COPIES OF CLEAR AND LEGIBLE PLANS FOR
 REVIEW. PLANS SHALL BE DRAWN ON A MIN. OF 1/8 " SCALE
 AND SHALL CLEARLY SHOW THE SCOPE OF WORK TO BE DONE.
 WPB AMEND. TO 2010 FBC SEC. 107.2.1
 2) IS ANY EQUIPMENT/CHAIRS THAT USE WATER BEING
 INSTALLED? IF SO, SUBMIT MANUFACTURER'S SPECIFICATIONS
 & INSTALLATION INSTRUCTIONS FOR THE EQUIPMENT.
 3) IF ANY CHANGES ARE BEING DONE TO THE PLUMBING
 SYSTEM, SUBMIT A SANITARY AND WATER RISER FOR REVIEW.
 WPB AMEND. TO 2010 FBC SEC.107.3.5.1.3.
 4) A DRINKING FOUNTAIN WILL BE REQUIRED IN THIS BAY.
 THE 2010 FL. ACCESSIBILITY CODE REQUIRES A MINIMUM OF
 TWO DRINKING FOUNTAINS PER SEC. 211.2.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
2015-03-23 17:36:24SEE PERMIT APPLICATION. JG.

Review Stop Z ZONING
Rev No 3 Status P Date 2015-06-25 Cont ID  
Sent By aaponte Date 2015-06-25 Time 10:26 Rev Time 0.00
Received By aaponte Date 2015-06-25 Time 10:26 Sent To  
Notes
2015-06-25 10:42:01PROVISO: SPACE ALONG CLEMATIS ST. SHALL BE DEDICATED TO
 RETAIL USE.SERVICES CANNOT BE PERFORMED WITHIN THE
 RETAIL AREA.
 THE TWO BUSINESSSES SHARE AN ENTRANCE BUT ARE SEPARATE
 BUSINESSES.
 FOR ADDIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.

Review Stop Z ZONING
Rev No 2 Status F Date 2015-05-21 Cont ID  
Sent By eschneid Date 2015-05-21 Time 08:45 Rev Time 0.00
Received By eschneid Date 2015-05-21 Time 08:45 Sent To  
Notes
2015-05-21 08:48:45ACCORDING TO DRAWINGS SUBMITTED, THE BUSINESS LOOKS
 LIKE A SERVICE AND NOT A RETAIL USE.
 IF A RETAIL USE IS PROPOSED ALONG WITH THE SERVICE,
 PLEASE INDICATE THE LOCATION OF ALL THE MERCHANDISE FOR
 SALE, LOCATION OF DISPLAY SHELFS AND TABLES.
 50% OF THE BUSINESS INCOME SHALL COME FROM THE SALE OF
 MERCHANDISE.
 PLEASE REMOVE THE WALL SEPARATING THE ENTRANCE FROM THE
 AREA ADJACENT TO THE WINDOW, IT SHOULD BE ONE SINGLE
 SPACE.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.

Review Stop Z ZONING
Rev No 1 Status F Date 2015-04-24 Cont ID  
Sent By aaponte Date 2015-04-24 Time 09:12 Rev Time 0.00
Received By aaponte Date 2015-04-24 Time 09:12 Sent To  
Notes
2015-04-24 09:15:16PROPOSED BUSINESS " AMAZING FEET" IS NOT ALLOWED AT
 THIS LOCATION. THE CLEMATIS STREET FRONTAGE IS A RETAIL
 REQUIRED FRONTAGE WHERE RETAIL USES ARE REQUIRED WITH A
 MINIMUM DEPTH OF 25'.
 PLEASE INDICATE HOW IS THE BUSINESS OPERATING. A FOOT
 MASSAGE BUSINESS IS CONSIDERED PERSONAL SERVICES AND
 NOT RETAIL.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved