Plan Review Stops For Permit 15030744 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2015-06-21 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2015-06-21 |
Time |
08:01 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2015-06-21 |
Time |
07:28 |
Sent To |
|
|
Notes |
2015-06-21 08:11:25 | BUILDING PROVISO: THE RESTROOM DOOR TO COMPLY WITH 2010 | | FBC-B 1008.1.9.11. DURING ITS SWING, ANY DOOR IN A | | MEANS OF EGRESS SHALL LEAVE UNOBSTRUCTED AT LEAST ONE | | HALF OF THE REQUIRED WIDTH OF AN AISLE, CORRIDOR, | | PASSAGEWAY. THE MINIMUM CLEAR WIDTH CLEAR IS 18 INCHES, | | EITHER THE SHELVING NEEDS TO BE REMOVED OR INSWING DOOR | | INTO THE RESTROOM. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2015-05-01 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2015-05-01 |
Time |
06:31 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2015-05-01 |
Time |
06:16 |
Sent To |
|
|
Notes |
2015-05-01 06:33:27 | BUILDING PLAN REVIEW | | W. P. B. PERMIT: 15030744 | | ADD: 420 CLEMATIS ST. SUITE : B | | CONT: TBD | | TEL: (561)909-7117 | | E-MAIL: | | | | 2010 FLORIDA BUILDING CODE W | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | IMPORTANT NOTICE: EFFECTIVE MARCH 30, 2015 | | ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED | | ELECTRONICALLY | | UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS | | SUBMISSION OPTIONS ARE AS FOLLOWS: | | 1 UPLOAD VIA THE PROJECT DOX PORTAL WITH DIGITAL | | SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE | | THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT | | 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL | | SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED | | NAMING CONVENTION FOR EACH DOCUMENT | | 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER | | DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE | | REQUIRED NAMING CONVENTION FOR EACH DOCUMENT | | 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT | | TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS | | ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES | | AVAILABLE | | | | 1ST REVIEW | | DATE: THURS./ MARCH 26/ 2015 | | ACTION: DENIED | | | | 1) A MEETING TOOK PLACE THURSDAY APRIL 30 WITH THE | | TENANTS, AND STAFF INCLUDING ANA MARIA APONTE WITH | | ZONING, URBAN DESIGN. THE PRESENT PLANS DO NOT REFLECT | | COMPLIANCE WITH THE REQUIREMENTS FOR THE ZONING | | REGULATIONS, THE STAFF RECOMENDED DIFFERENT WAYS OF | | COMPLIANCE, THE TENANTS WILL NEED TO DECIDE AND GET | | WITH THERE DESIGN PROFESSIONAL TO UPDATE PLANS TO | | COMPLY WITH THE ZONING CODE. WITH THIS UNDERSTANDING | | THAT THESE PLANS HAVE TO BE REVISED, THIS REVIEW WILL | | NOT BE ABLE TO BE PASSED, IT DOES NOT REFLECT WHAT IS | | TO BE BUILT. | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | COOPERATION. | | | | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A | | RESULT OF THE ADDITIONAL INFORMATION REQUESTED | | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF | | THIS REVIEW. | | | | JAMES A. WITMER CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | TEL: 561-805-6715 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | DEVELOPMENT SERVICES HOME PAGE | | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2015-03-26 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2015-03-26 |
Time |
07:28 |
Rev Time |
|
Received By |
jwitmer |
Date |
2015-03-26 |
Time |
06:59 |
Sent To |
|
|
Notes |
2015-03-26 07:05:22 | BUILDING PLAN REVIEW | | W. P. B. PERMIT: 15030744 | | ADD: 420 CLEMATIS ST. SUITE : B | | CONT: TBD | | TEL: (561)909-7117 | | E-MAIL: | | | | 2010 FLORIDA BUILDING CODE W | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | IMPORTANT NOTICE: EFFECTIVE MARCH 30, 2015 | | ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED | | ELECTRONICALLY | | UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS | | SUBMISSION OPTIONS ARE AS FOLLOWS: | | 1 UPLOAD VIA THE PROJECT DOX PORTAL WITH DIGITAL | | SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE | | THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT | | 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL | | SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED | | NAMING CONVENTION FOR EACH DOCUMENT | | 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER | | DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE | | REQUIRED NAMING CONVENTION FOR EACH DOCUMENT | | 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT | | TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS | | ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES | | AVAILABLE | | | | 1ST REVIEW | | DATE: THURS./ MARCH 26/ 2015 | | ACTION: DENIED | | | | 1) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE, CHAPTER 1, ADMINISTRATION 107.3.5.1 | | COMMERCIAL BUILDINGS. 107.3.5 MINIMUM PLAN REVIEW | | CRITERIA FOR BUILDINGS. THE EXAMINATION OF THE | | DOCUMENTS BY THE BUILDING OFFICIAL SHALL INCLUDE THE | | FOLLOWING MINIMUM CRITERIA AND DOCUMENTS: | | A).OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS | | SHALL BE DETERMINED. | | B). MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED | | (SEE TABLE 503). | | C). FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL | | INCLUDE THE FOLLOWING COMPONENTS: FIRE-RESISTANT | | SEPARATIONS | | D). FIRE SPRINKLERS YES OR NO REQUIRED YES OR NO | | E). FIFE SAFETY PLAN SHALL INCLUDE THE FOLLOWING: | | FLOOR PLAN WITH FURNITURE/ EQUIPMENT LAYOUT AND MEANS | | OF EGRESS ROUTE | | OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE: | | OCCUPANCY LOAD/ | | GROSS OR NET | | MEANS OF EGRESS | | EXIT ACCESS | | EXIT | | EXIT DISCHARGE | | STAIRS CONSTRUCTION/GEOMETRY AND PROTECTION | | DOORS | | EMERGENCY LIGHTING AND EXIT SIGNS | | F). 10. ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE | | FOLLOWING: | | SITE REQUIREMENTS | | ACCESSIBLE ROUTE | | TOILET FACILITIES | | DRINKING FOUNTAINS | | | | 2) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION | | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | COOPERATION. | | | | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A | | RESULT OF THE ADDITIONAL INFORMATION REQUESTED | | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF | | THIS REVIEW. | | | | JAMES A. WITMER CBO | | | | | | | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2015-07-06 |
|
|
Cont ID |
|
Sent By |
dhayes |
Date |
2015-07-06 |
Time |
11:06 |
Rev Time |
0.00 |
Received By |
dhayes |
Date |
2015-07-06 |
Time |
10:05 |
Sent To |
|
|
Notes |
2015-07-06 11:06:28 | APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN APPROVED | | PROVISIONALLY. FAILURE TO CORRECT THE LISTED | | DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED | | INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION | | FEE(S). | | | | 1) ELECTRIC DRINKING FOUNTAINS SHALL BE PROTECTED WITH | | GROUND FAULT CIRCUIT INTERRUPTER PROTECTION. NEC 422.52 | | | | 2) WHERE RECEPTACLES ARE INSTALLED WITHIN 1.8 M (6 FT) | | OF THE OUTSIDE EDGE OF THE SINK GROUND-FAULT | | CIRCUIT-INTERRUPTER PROTECTION FOR PERSONNEL IS | | REQUIRED. NEC 210.8 (B) (5) SINKS. | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | 561-805-6717 OR [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2015-05-14 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2015-05-14 |
Time |
14:29 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2015-05-14 |
Time |
14:08 |
Sent To |
|
|
Notes |
2015-05-14 14:44:08 | DISPOSITION AND RESPECTIVE COMMENTS FOR ELECTRICAL PLAN | | REVIEW | | APPLICABLE CODES: FBC 2010; WPB AMENDMENTS TO FBC 2010 | | CHAPTER 1; NEC 2008 | | REVIEW CYCLE: 2ND REVIEW, MIKE ALBARRAN | | ACTION: FAILED, THIS ELECTRICAL REVIEW FAILED AS | | OUTLINED BELOW: | | 1. NEC 600.5 REQUIRES THAT THERE BE A DEDICATED SIGN | | OUTLET AT EVERY ENTRANCE. | | 2. NEC 210.62 REQUIRES THAT THERE BE AN SHOW WINDOW | | OUTLET FOR EVERY 12' OF SHOW WINDOW OR FRACTION | | THEREOF. THIS OUTLET SHALL BE WITHIN 18" FROM THE TOP | | OF THE WINDOW. | | 3. AN EXIT LIGHT SHALL BE PLACED IN THE AREA OF COMMON | | PATH OF EGRESS TRAVEL INDICATING EXIT TO EITHER | | DIRECTION. | | 4. COMPLIANCE W/FBC ENERGY CONSERVATION SECTION 505 | | SHALL BE REQUIRED. | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2015-04-07 |
|
|
Cont ID |
|
Sent By |
dhayes |
Date |
2015-04-07 |
Time |
15:03 |
Rev Time |
0.00 |
Received By |
dhayes |
Date |
2015-04-07 |
Time |
15:03 |
Sent To |
|
|
Notes |
2015-04-07 15:19:14 | NO ELECTRICAL PLANS HAVE BEEN INCLUDED IN THIS | | SUBMITTAL PACKAGE. AN APPLICATION WITH THE DESCRIPTION | | MINOR INTERIOR REMODEL INCLUDING ELECTRIC AND PLUMBING | | FOR NEW FOOT MASSAGE BUSINESS. PROVIDE COMPLETE | | ELECTRICAL PLANS REQUIRED TO INDICATE COMPLIANCE WITH | | THE FBC AND THE NEC | | PROVIDE A FLOOR PLAN INDICATING LOCATIONS FOR THE | | ELECTRICAL SERVICE, ELECTRICAL PANEL(S) FOOT MASSAGE | | EQUIPMENT. LWPB AMENDMENTS TO FBC 107.3.2, NEC 110.26 | | PROVIDE A PANEL SCHEDULE INDICATING ALL NEW CIRCUITS | | FOR NEW FOOT MASSAGE EQUIPMENT. NEC 408.4 | | PROVIDE A LOAD CALCULATION THAT INCLUDES ALL EXISTING | | PLUS ADDITIONAL BRANCH CIRCUITS REQUIRED FOR NEW FOOT | | MASSAGE EQUIPMENT. | 2015-03-23 17:35:56 | SEE PERMIT APPLICATION. JG. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2015-06-12 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2015-06-12 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2015-06-12 |
Time |
14:00 |
Sent To |
|
|
Notes |
2015-06-12 14:15:36 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | 1) THERE ARE INCORRECT REFERENCES TO THE FIRE CODE; | | HOWEVER, THEY DO NOT APPEAR TO NEGATIVELY AFFECT THE | | PROJECT. PLEASE ENSURE THAT THE PROJECT MEETS THE | | APPROPRIATE REFERNECE AT THE TIME OF INSPECTION AND | | CORRECT YOUR RECORDS FOR FUTURE SUBMITTALS. | | | | THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE | | 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING | | THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER | | APPLICABLE CODES OR STANDARDS. | | FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS | | OF NFPA 13, 2010 EDITION. | | FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF | | NFPA 72, 2010 EDITION. | | CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF | | NFPA 241, 2009 EDITION. | | FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS | | OF NFPA 10, 2010 EDITION. | | ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION. | | | | | | 2) THE DOOR TO THE BATHROOM SWINGS OUT INTO THE EXIT | | CORRIDOR. THE DOOR CAN NOT SWING OUT TO MORE THAN HALF | | OF THE REQUIRED EXIT WIDTH. THE SHALL BE SELF CLOSING | | OR SWING IN TO THE BATHROOM. | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2015-05-04 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2015-05-04 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2015-05-04 |
Time |
15:27 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2015-03-25 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2015-03-25 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2015-03-25 |
Time |
09:30 |
Sent To |
|
|
Notes |
2015-03-25 09:36:58 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | PROVIDE A LIFE SAFTY PLAN SHOWING EXITS, EXIT LIGHTS, | | EMERGENCY LIGHTS, EXIT DOOR HARDWARE, FIRE | | EXTINGUISHERS, OCCUPANY LOADS, EGRESS PATHS, COMMON | | PATHS OF TRAVEL, FIRE ALARM DEVICE LOCATIONS, ETC. | | | | PROVIDE EXISTING LIFE SAFETY SYSTEMS, I.E. FIRE ALARM & | | FIRE SPRINKLER. IF LIFE SAFETY SYSTEMS EXIST, PROVIDE A | | NOTE INDICATING: THE NATURE OF THE REMODEL REQUIRES AN | | EVALUATION OF THE FIRE ALARM AND SPRINKLER SYSTEM FOR | | CODE COVERAGE AND COMPLIANCE. | | | | THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE | | SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE | | CONSTRUCTION PERIOD. | | | | ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER | | SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND | | BY CERTIFIED LIFE SAFETY CONTRACTORS. | | | | ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS, | | SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE | | WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL | | AND COMPLETE PROTECTION IS RETURNED. | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2015-07-06 |
|
|
Cont ID |
|
Sent By |
dhayes |
Date |
2015-07-06 |
Time |
11:06 |
Rev Time |
0.00 |
Received By |
dhayes |
Date |
2015-06-12 |
Time |
07:35 |
Sent To |
|
|
Notes |
2015-06-12 07:41:23 | ROUTED TO B04/CC |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2015-05-27 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2015-05-27 |
Time |
03:37 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2015-04-29 |
Time |
16:45 |
Sent To |
|
|
Notes |
2015-04-29 16:46:09 | B09 "EXPEDITE" |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2015-04-24 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2015-04-24 |
Time |
09:38 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
2015-03-18 |
Time |
10:46 |
Sent To |
|
|
Notes |
2015-03-23 10:47:23 | SENT TO B4 FOR REVIEW. JG. |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
2 |
Status |
N |
Date |
2015-05-01 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2015-05-01 |
Time |
06:34 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2015-05-01 |
Time |
06:34 |
Sent To |
|
|
Notes |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
F |
Date |
2015-03-26 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2015-03-26 |
Time |
07:05 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2015-03-26 |
Time |
07:05 |
Sent To |
|
|
Notes |
2015-03-26 07:06:45 | PLANS SUBMITTED WITH INSUFFICIENT INFORMATION TO | | DETERMINE IF COUNTY IMPACR FEES ARE TO BE ASSESSED. A | | THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A | | RESULT OF THE ADDITIONAL INFORMATION REQUESTED | | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF | | THIS REVIEW. | | | | JAMES A. WITMER CBO | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2015-07-01 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2015-07-01 |
Time |
06:14 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2015-07-01 |
Time |
05:56 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2015-05-27 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2015-05-27 |
Time |
03:37 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2015-05-27 |
Time |
02:42 |
Sent To |
|
|
Notes |
2015-05-27 03:30:15 | 1)THE PERMIT APPLICATION AND PLANS ARE VAGUE AS TO THE | | EXTENT OF PLUMBING WORK THAT WILL BE DONE IN THIS | | SPACE.SUBMIT INFORMATION AND ON THE PLANS SHOWING THE | | ENTIRE SCOPE OF PLUMBING WORK TO BE DONE.107.1.2. | | SUBMIT TWO COPIES OF CLEAR AND LEGIBLE PLANS FOR | | REVIEW. ONE SET OF PLANS IS SO LIGHT THEY ARE | | ILLEGIBLE.PLANS SHALL BE DRAWN ON A MIN. OF 1/8 " SCALE | | AND SHALL CLEARLY SHOW THE SCOPE OF WORK TO BE DONE. | | WPB AMEND. TO 2010 FBC SEC. 107.2.1 | | 2) IS ANY EQUIPMENT/ PEDICURE CHAIRS THAT USE WATER | | BEING INSTALLED? IF SO, SUBMIT MANUFACTURER'S | | SPECIFICATIONS & INSTALLATION INSTRUCTIONS FOR THE | | EQUIPMENT.IDENTIFY THE CHAIRS ON THE PLAN IF | | APPLICABLE. NOW THERE IS JUST IMAGES NOTED AS "SEAT | | WITH STOOL". | | 3) SUBMIT A WATER RISER FOR REVIEW. WPB AMEND. TO 2010 | | FBC SEC.107.3.5.1.3. | | 4) BOTH SETS OF PLANS SHALL BE SIGNED AND SEALED BY THE | | DESIGN PROFESSIONAL OF RECORD PER THE FL. ADMIN. CODE | | RULE 61G1-16.003. | | 5)SHT. A-1 - HANDICAP DETAILS - THE GRAB BAR SHALL BE | | MEASURED FROM THE FINISH FLOOR TO THE TOP OF THE | | GRIPPING SURFACE, NOT TO THE CENTERLINE AS SHOW. FAC | | SEC. 609.4. | | 6) THE TOILET PAPER DISPENSER SHALL BE LOCATED 7-9 | | INCHES IN FRONT OF THE WATER CLOSET MEASURED TO THE | | CENTERLINE OF THE DISPENSER. SHOW THIS ON THE HANDICAP | | DETAILS. | | 7) THE FINISH SCHEDULE ON SHT A-1 NOTES THE TOILET ROOM | | WALLS TO BE PAINTED AND A 2 INCH WOOD BASE | | INSTALLED.THE BASE SHALL BE A MINIMUM OF 4 INCHES AND | | COMPLY WITH FBC SEC.1210.1. THE WALLS & PARTITIONS | | WITHIN 2 FEET OF WATER CLOSETS SHALL HAVE SMOOTH, HARD, | | NONABSORBENT SURFACE, TO A HEIGHT OF 4 FEET ABOVE THE | | FLOOR AND COMPLY WITH FBC SEC. 1210.2. | | 8) INDICATE ON THE PLANS WHAT PLUMBING IS NEW AND WHAT | | IS EXISTING TO REMAIN. WPB AMEND. TO FBC SEC. 107.2.1. | | 9) SHT. E-1 SHOWS A 100 GALLON WATER HEATER. IS THIS | | CORRECT? | | 10) SHT. E-1 - SUBMIT A WATER RISER DIAGRAM FOR REVIEW. | | WPB AMEND. TO FBC SEC. 107.3.5.1.3. THE PLAN VIEW | | REQUIRES A MAGNIFYING GLASS TO REVIEW. PLANS SHALL BE | | DRAWN ON A MIN. OF 1/8 " SCALE AND SHALL CLEARLY SHOW | | THE SCOPE OF WORK TO BE DONE. WPB AMEND. TO 2010 FBC | | SEC. 107.2.1 | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2015-04-17 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2015-04-17 |
Time |
05:43 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2015-04-17 |
Time |
05:29 |
Sent To |
|
|
Notes |
2015-04-17 05:43:11 | 1)THE PERMIT APPLICATION AND PLANS ARE VAGUE AS TO THE | | EXTENT OF PLUMBING WORK THAT WILL BE DONE IN THIS | | SPACE.SUBMIT INFORMATION AND ON THE PLANS SHOWING THE | | ENTIRE SCOPE OF PLUMBING WORK TO BE DONE.107.1.2. | | SUBMIT TWO COPIES OF CLEAR AND LEGIBLE PLANS FOR | | REVIEW. PLANS SHALL BE DRAWN ON A MIN. OF 1/8 " SCALE | | AND SHALL CLEARLY SHOW THE SCOPE OF WORK TO BE DONE. | | WPB AMEND. TO 2010 FBC SEC. 107.2.1 | | 2) IS ANY EQUIPMENT/CHAIRS THAT USE WATER BEING | | INSTALLED? IF SO, SUBMIT MANUFACTURER'S SPECIFICATIONS | | & INSTALLATION INSTRUCTIONS FOR THE EQUIPMENT. | | 3) IF ANY CHANGES ARE BEING DONE TO THE PLUMBING | | SYSTEM, SUBMIT A SANITARY AND WATER RISER FOR REVIEW. | | WPB AMEND. TO 2010 FBC SEC.107.3.5.1.3. | | 4) A DRINKING FOUNTAIN WILL BE REQUIRED IN THIS BAY. | | THE 2010 FL. ACCESSIBILITY CODE REQUIRES A MINIMUM OF | | TWO DRINKING FOUNTAINS PER SEC. 211.2. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | | | | 2015-03-23 17:36:24 | SEE PERMIT APPLICATION. JG. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2015-06-25 |
|
|
Cont ID |
|
Sent By |
aaponte |
Date |
2015-06-25 |
Time |
10:26 |
Rev Time |
0.00 |
Received By |
aaponte |
Date |
2015-06-25 |
Time |
10:26 |
Sent To |
|
|
Notes |
2015-06-25 10:42:01 | PROVISO: SPACE ALONG CLEMATIS ST. SHALL BE DEDICATED TO | | RETAIL USE.SERVICES CANNOT BE PERFORMED WITHIN THE | | RETAIL AREA. | | THE TWO BUSINESSSES SHARE AN ENTRANCE BUT ARE SEPARATE | | BUSINESSES. | | FOR ADDIONAL INFORMATION PLEASE CONTACT ANA MARIA | | APONTE AT 561-822-1439. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2015-05-21 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2015-05-21 |
Time |
08:45 |
Rev Time |
0.00 |
Received By |
eschneid |
Date |
2015-05-21 |
Time |
08:45 |
Sent To |
|
|
Notes |
2015-05-21 08:48:45 | ACCORDING TO DRAWINGS SUBMITTED, THE BUSINESS LOOKS | | LIKE A SERVICE AND NOT A RETAIL USE. | | IF A RETAIL USE IS PROPOSED ALONG WITH THE SERVICE, | | PLEASE INDICATE THE LOCATION OF ALL THE MERCHANDISE FOR | | SALE, LOCATION OF DISPLAY SHELFS AND TABLES. | | 50% OF THE BUSINESS INCOME SHALL COME FROM THE SALE OF | | MERCHANDISE. | | PLEASE REMOVE THE WALL SEPARATING THE ENTRANCE FROM THE | | AREA ADJACENT TO THE WINDOW, IT SHOULD BE ONE SINGLE | | SPACE. | | FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA | | APONTE AT 561-822-1439. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2015-04-24 |
|
|
Cont ID |
|
Sent By |
aaponte |
Date |
2015-04-24 |
Time |
09:12 |
Rev Time |
0.00 |
Received By |
aaponte |
Date |
2015-04-24 |
Time |
09:12 |
Sent To |
|
|
Notes |
2015-04-24 09:15:16 | PROPOSED BUSINESS " AMAZING FEET" IS NOT ALLOWED AT | | THIS LOCATION. THE CLEMATIS STREET FRONTAGE IS A RETAIL | | REQUIRED FRONTAGE WHERE RETAIL USES ARE REQUIRED WITH A | | MINIMUM DEPTH OF 25'. | | PLEASE INDICATE HOW IS THE BUSINESS OPERATING. A FOOT | | MASSAGE BUSINESS IS CONSIDERED PERSONAL SERVICES AND | | NOT RETAIL. | | FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA | | APONTE AT 561-822-1439. |
|
|