Plan Review Details - Permit 15030658
Plan Review Stops For Permit 15030658
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-05-15 Cont ID  
Sent By shill Date 2015-05-15 Time 11:46 Rev Time 0.00
Received By shill Date 2015-05-15 Time 11:46 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2015-04-17 Cont ID  
Sent By shill Date 2015-04-17 Time 09:43 Rev Time 0.00
Received By shill Date 2015-04-17 Time 09:43 Sent To E
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-05-26 Cont ID  
Sent By albarran Date 2015-05-26 Time 20:29 Rev Time 0.00
Received By albarran Date 2015-05-26 Time 20:14 Sent To I
Notes
2015-05-26 20:21:29IMPORTANT NOTICE: FOR FINAL ELECTRICAL INSPECTION,
 REGARDLESS IF THIS SIGN WAS CONNECTED TO NEW OR
 EXISTING POWER, FULL COMPLIANCE WITH 2008 NEC & 2010
 FBC ENERGY CONSERVATION SECTION 505.2.4 WILL BE
 REQUIRED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-04-22 Cont ID  
Sent By dhayes Date 2015-04-22 Time 14:49 Rev Time 0.00
Received By dhayes Date 2015-04-22 Time 14:49 Sent To  
Notes
2015-04-22 14:49:59REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW
 COMMENTS:
  
 1) ELECTRIC SIGNS, SECTION SIGNS, AND OUTLINE LIGHTING,
 FIXED, MOBILE, OR PORTABLE, SHALL BE LISTED AND
 INSTALLED IN CONFORMANCE WITH THAT LISTING, UNLESS
 OTHERWISE APPROVED BY SPECIAL PERMISSION. 600.3
 LISTING.
  
 2) EACH SIGN AND OUTLINE LIGHTING SYSTEM, OR FEEDER
 CIRCUIT OR BRANCH CIRCUIT SUPPLYING A SIGN OR OUT-LINE
 LIGHTING SYSTEM, SHALL BE CONTROLLED BY AN EXTERNALLY
 OPERABLE SWITCH OR CIRCUIT BREAKER THAT WILL OPEN ALL
 UNGROUNDED CONDUCTORS WITHIN SIGHT OF THE SIGN NEC
 600.6(A)(1)
  
 3) ALL EXTERIOR LIGHTING NOT EXEMPTED BY FBC 505.1
 SHALL HAVE AUTOMATIC CONTROLS TO TURN OFF AT DAYLIGHT
 OR WHEN NOT REQUIRED. CONTROLS SHALL BE PHOTOSENSOR &
 TIME CLOCK OR ASTRONOMICAL TIME SWITCH. ALL TIME
 SWITCHES SHALL BE CAPABLE OF RETAINING PROGRAMING
 DURING A LOSS OF POWER FOR A MINIMUM OF 10 HOURS. FBC-E
 505.2.4
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-05-26 Cont ID  
Sent By albarran Date 2015-05-26 Time 20:28 Rev Time 0.00
Received By albarran Date 2015-05-08 Time   Sent To  
Notes
2015-05-26 20:29:18SENT TO READY BIN "F"
2015-05-15 11:46:11TO DAH DESK
  
2015-05-08 17:26:52SENT TO ZONING

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-04-22 Cont ID  
Sent By dhayes Date 2015-04-22 Time 14:50 Rev Time 0.00
Received By dhayes Date 2015-03-17 Time 15:57 Sent To  
Notes
2015-04-17 09:44:204/17 TO ELEC BOX
  
2015-03-17 15:57:37ROUTED TO ZONING

Review Stop Z ZONING
Rev No 2 Status P Date 2015-05-11 Cont ID  
Sent By sgraham Date 2015-05-11 Time 15:59 Rev Time 0.00
Received By sgraham Date 2015-05-11 Time 16:00 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2015-04-06 Cont ID  
Sent By sgraham Date 2015-04-06 Time 14:10 Rev Time 0.00
Received By sgraham Date 2015-04-06 Time 14:10 Sent To B
Notes
2015-04-06 14:11:314/6/15 ZONING FAILED
  
 1. PROVIDE THE DIMENSIONS FOR THE EXISTING SIGN.