Plan Review Details - Permit 15030623
Plan Review Stops For Permit 15030623
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-08-31 Cont ID  
Sent By fmittner Date 2015-08-31 Time 16:17 Rev Time 0.00
Received By rmcdouga Date 2015-08-31 Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-07-20 Cont ID  
Sent By R MCDOUG Date 2015-07-20 Time 16:16 Rev Time 0.00
Received By rmcdouga Date 2015-07-17 Time 16:38 Sent To  
Notes
2015-07-20 16:12:06PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE CLASSIFICATION OF WORK ON THE COVER SHEET
 SPECIFIES THIS AS A LEVEL 1 ALTERATION. THE PLANS
 INDICATE THAT THE SPACE HAS BEEN RECONFIGURED AND DOORS
 AND WINDOWS HAVE BEEN ADDED OR ELIMINATED. THIS PROJECT
 MEETS THE REQUIREMENTS FOR A LEVEL 2 ALTERATION. IF THE
 WORK AREA EXCEEDS 50 PERCENT OF THE AGGREGATE AREA OF
 THE BUILDING, THEN IT IS A LEVEL 3 ALTERATION. FBC
 EXISTING BUILDING 401.4
  
 2) SPECIFY THE WIND DESIGN CRITERIA AND THE REQUIRED
 DESIGN PRESSURES FOR THE (2) NEW EXTERIOR DOORS AND (1)
 WINDOW. FBC-R301.2.1
  
 3) FBC 107.3.4 - PROVIDE TWO COMPLETE SETS OF PRODUCT
 APPROVALS FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3 THAT HAVE BEEN REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD.
  
 4) THE ONE SET OF PRODUCT APPROVAL INSTALLATION
 DOCUMENTS THAT WERE SUBMITTED FOR THE JELD-WEN SLIDING
 PATIO DOOR DOES NOT HAVE A FLORIDA PRODUCT APPROVAL FL#
 ON THEM. SUBMIT THE COVER-SHEETS WITH THE FL#.
  
 5) THE DOOR SCHEDULE ON SHEET A-200 FOR DOOR #1
 SPECIFIES THE DOOR TYPE AS SLIDING AND SWING DOORS ARE
 INDICATED UNDER REMARKS FOR THIS DOOR. PRODUCT
 APPROVALS FOR BOTH EXTERIOR DOOR TYPES WERE SUBMITTED.
 PLEASE CLARIFY. FBC 107.2.1
  
 6) THE ENERGY FORM 402-2010 IS REQUIRED TO BE SIGNED
 AND DATED BY THE OWNER/AGENT. FBC ENERGY 103.2.3.2
  
 7) IN ORDER TO REDUCE PLAN REVIEW TIMES AND PROVIDE
 CLARIFICATION, PLEASE SUBMIT A RESPONSE LETTER
 INDICATING HOW EACH OF THE REVIEW COMMENTS HAS BEEN
 ADDRESSED.
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-04-10 Cont ID  
Sent By rmcdouga Date 2015-04-10 Time 07:46 Rev Time 0.00
Received By rmcdouga Date 2015-04-10 Time 07:46 Sent To  
Notes
2015-04-10 07:08:53PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS
 SHALL BE
 SUBMITTED WHEN APPROVED BY THE BUILDING OFFICIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN.
  
 2) FBC 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING
 PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON
 SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM.
 THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE,
 SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO
 RECORDS MANAGEMENT.
  
 3) FBC 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS
 SUBMITTED WITH THE APPLICATION FOR PERMIT SHALL BE
 ACCOMPANIED BY A SITE PLAN SHOWING TO SCALE THE SIZE
 AND LOCATION OF NEW CONSTRUCTION AND EXISTING
 STRUCTURES ON THE SITE.
  
 4) FBC-R314.3.1 ALTERATIONS, REPAIRS AND ADDITIONS.
 WHEN ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS.
  
 5) PROVIDE AN INTERIOR WALL SECTION OF THE WALL TO ROOF
 EXTENSION. SPECIFY THE FRAMING MATERIAL, CONNECTIONS
 AND FASTENERS THAT WILL BE USED. FBC 107.2.1
  
 7) PROVIDE A SECTION THROUGH THE ROOF / CEILING
 ASSEMBLY. SHOW THE TYPE AND LOCATION OF THE INSULATION
 THAT IS TO BE ADDED. SHOW ATTIC ATTIC ACCESS AND
 VENTILATION. FBC 107.2.1
  
 8) REMOVE ITEMS FROM THE SCOPE OF WORK LISTED ON THE
 PLAN THAT WILL NOT BE INCLUDED WITH THIS PERMIT. FBC
 107.2.1
  
 9) THE PLANS THAT WERE SUBMITTED HAVE THE TITLE BLOCK
 OF AN ARCHITECT. FS 481 & FAC 61G1-16 REQUIRES PLANS
 THAT ARE SUBMITTED FROM AN ARCHITECT TO HAVE THEIR SEAL
 AND HANDWRITTEN SIGNATURE.
  
 IN ORDER TO REDUCE PLAN REVIEW TIMES AND PROVIDE
 CLARIFICATION, PLEASE SUBMIT A RESPONSE LETTER
 INDICATING HOW EACH OF THE REVIEW COMMENTS HAS BEEN
 ADDRESSED.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-07-20 Cont ID  
Sent By R MCDOUG Date 2015-07-20 Time 14:56 Rev Time 0.00
Received By rmcdouga Date 2015-07-17 Time 16:38 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-04-10 Cont ID  
Sent By rmcdouga Date 2015-04-10 Time 07:02 Rev Time 0.00
Received By rmcdouga Date 2015-04-10 Time 07:02 Sent To  
Notes
2015-04-09 19:06:16PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010 / 2008 NEC
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY ELECTRICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT TWO SETS OF ELECTRICAL PLANS. SHOWING
 COMPLIANCE WITH THE 2008 NEC FOR REQUIRED RECEPTALCES,
 LIGHTING OUTLETS AND PANEL LOCATION. PROVIDE A PANEL
 SCHEDULE AND INDICATE THE CIRCUIT NUMBERS ON THE PLANS.
 FBC 107.3.5.3
  
 2) FBC 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING
 PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON
 SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM.
 THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE,
 SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO
 RECORDS MANAGEMENT.
  
 3) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN.
  
 4) FBC-R314.3.1 ALTERATIONS, REPAIRS AND ADDITIONS.
 WHEN ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS.
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2015-08-31 Cont ID  
Sent By rmcdouga Date 2015-08-31 Time 16:45 Rev Time 0.00
Received By rmcdouga Date 2015-08-31 Time 16:18 Sent To  
Notes
2015-08-31 16:45:36APPROVED WITH EXCEPTION. THIS PLAN HAS BEEN APPROVED
 PROVISIONALLY. FAILURE TO CORRECT THE LISTED
 DEFICIENCIES IN THIS PLAN PRIOR TO INSPECTION WILL
 RESULT IN FAILED INSPECTION(S) AND ASSESSMENT OF
 RE-INSPECTION FEE(S). SUBMIT (2) SETS OF REVISED GAS
 RISER DIAGRAMS FOR APPROVAL PRIOR TO FIRST GAS
 INSPECTION.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2015-07-17 Cont ID  
Sent By rmcdouga Date 2015-07-17 Time 17:59 Rev Time 0.00
Received By rmcdouga Date 2015-07-17 Time 16:38 Sent To  
Notes
2015-07-17 18:08:16PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 GAS REVIEW DENIED
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THERE IS A DISCREPANCY BETWEEN THE TANKLESS WATER
 HEATER BTUS ON THE PLANS. SHEET P-1 SPECIFIES 120,000
 BTUS AND P-2 HAS 199,000 BTUS. SUBMIT THE
 MANUFACTURER'S SPECIFICATIONS, LISTING AND INSTALLATION
 INSTRUCTIONS FOR THE TANKLESS WATER HEATER THAT WILL BE
 INSTALLED. FBC 107.2.1 AND FBC-R G2413.2
  
 2) ON SHEET P-2 THE TOTAL BTU LOAD WOULD BE 279,000
 BTUS FOR THE SUM OF 80,000 AND 199,000 BTUS. FBC
 107.2.1
  
 3) USING THE LONGEST LENGTH SIZING METHOD, THE 3/4" PE
 PIPE SUPPLYING THE 199,000 BTU TANKLESS WATER HEATER IS
 TOO SMALL. AT 50 FEET THE CAPACITY IS 169,000 BTUS.
 FBC-R 2413.4.1
  

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2015-08-25 Cont ID  
Sent By rmcdouga Date 2015-08-31 Time 16:45 Rev Time 0.00
Received By fmittner Date 2015-08-24 Time 10:07 Sent To B
Notes
2015-08-25 09:19:04CORRECTION NOTED.
2015-08-24 10:08:30PLANS STILL SHOW 2 PAIRS OF DOUBLE DOORS ON FRONT, NOT
 APPROVED BY HPB

Review Stop HIST HISTORICAL
Rev No 2 Status F Date 2015-07-21 Cont ID  
Sent By F MITTNE Date 2015-07-21 Time 13:16 Rev Time 0.00
Received By fmittner Date 2015-07-21 Time 13:16 Sent To  
Notes
2015-07-21 13:17:20HPB ON 6/23/15 DID NOT APPROVE CHANGE OF FRONT DOOR
 FROM DOUBLE TO SINGLE NOR KNEE WALL REDUCATION. PLANS
 MUST BE REVISED.

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2015-04-07 Cont ID  
Sent By fmittner Date 2015-04-07 Time 09:59 Rev Time 0.00
Received By fmittner Date 2015-04-07 Time 09:59 Sent To  
Notes
2015-04-07 10:00:47PROPERTY IS CONTRIBUTING TO THE GRANDVIEW HEIGHT
 HISTORIC DISTRICT. SCOPE OF WORK DOES NOT INCLUDE
 EXTERIOR DOORS, YET REPRESENTED ON PLAN. REQUIRES
 SUBMITTAL OF COA. QUESTIONS CONTACT FRIEDERIKE MITTNER
 AT 822-1457.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-08-31 Cont ID  
Sent By rmcdouga Date 2015-08-31 Time 16:45 Rev Time 0.00
Received By rmcdouga Date 2015-08-04 Time 15:36 Sent To HIST
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-07-21 Cont ID  
Sent By skennedy Date 2015-07-21 Time 14:35 Rev Time 0.00
Received By skennedy Date 2015-06-10 Time 15:33 Sent To  
Notes
2015-06-11 11:05:30R33

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-04-10 Cont ID  
Sent By rmcdouga Date 2015-04-10 Time 07:46 Rev Time 0.00
Received By rmcdouga Date 2015-03-17 Time 10:28 Sent To  
Notes
2015-03-18 10:28:40R09

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-07-17 Cont ID  
Sent By R MCDOUG Date 2015-07-17 Time 15:47 Rev Time 0.00
Received By rmcdouga Date 2015-07-17 Time 15:47 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2015-04-09 Cont ID  
Sent By rmcdouga Date 2015-04-09 Time 18:41 Rev Time 0.00
Received By rmcdouga Date 2015-04-09 Time 18:41 Sent To  
Notes
2015-04-09 18:44:14NO MECHANICAL WORK IS SHOWN ON THE PLANS AND NO
 MECHANICAL PERMIT WAS SUBMITTED. A SEPARATE PERMIT,
 APPLICATION AND REVIEW WILL BE REQUIRED.

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-07-17 Cont ID  
Sent By R MCDOUG Date 2015-07-17 Time 16:38 Rev Time 0.00
Received By rmcdouga Date 2015-07-16 Time 10:53 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-04-09 Cont ID  
Sent By rmcdouga Date 2015-04-09 Time 18:35 Rev Time 0.00
Received By rmcdouga Date 2015-04-09 Time 18:35 Sent To  
Notes
2015-04-09 18:36:04PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT TWO SETS OF PLUMBING RISER DIAGRAMS. FBC
 107.3.5.3
  
 2) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN.

Review Stop Z ZONING
Rev No 2 Status P Date 2015-07-21 Cont ID  
Sent By fmittner Date 2015-07-21 Time 13:17 Rev Time 0.00
Received By fmittner Date 2015-07-21 Time 13:17 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date   Cont ID  
Sent By fmittner Date 2015-04-07 Time   Rev Time 0.00
Received By   Date 2015-04-07 Time   Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy