Plan Review Details - Permit 15030536
Plan Review Stops For Permit 15030536
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2015-03-28 Cont ID  
Sent By tklarge Date 2015-03-28 Time 12:27 Rev Time 0.00
Received By tklarge Date 2015-03-28 Time 11:51 Sent To  
Notes
2015-03-28 11:51:57TRAVELING WITH PERMIT APPLICATION # 15030535.TKL.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2015-03-19 Cont ID  
Sent By tklarge Date 2015-03-19 Time 10:27 Rev Time 0.00
Received By tklarge Date 2015-03-19 Time 08:57 Sent To  
Notes
2015-03-19 10:27:281) SUBMIT TWO COPIES OF MANUFACTURER'S
 SPECIFICATIONS/INSTALLATION SHEETS FOR THE
 GENERATOR.THE GENERATOR SHALL BE UL2200 COMPLIANT PER
 THE FUEL GAS CODE SEC.616.1.
 2) THE GENERATOR SHALL BE INSTALLED IN ACCORDANCE WITH
 THE MANUF. INSTALLATION INSTRUCTIONS AND NFPA 37. 2010
 FGC SEC.616.1.
 3) SHOW THE TERMINUS OF THE GAS VENT. THE LOCATION
 SHALL COMPLY WITH THE 2010 FGC SEC. 503.6.4, 503.8.
 4) THE GENERATOR SHALL BE LOCATED A MINIMUM OF 5 FEET
 FROM OPENINGS IN THE EXTERIOR BUILDING WALLS AND AT
 LEAST 5 FEET FROM STRUCTURES HAVING COMBUSTIBLE WALLS.
 IF THE EXTERIOR WALL IS NOT 1 HOUR FIRE RATED THEN THE
 GENERATOR SHALL BE A MIN. OF 5 FEET FROM THE EXTERIOR
 PER NFPA 37 SEC. 4.1.4.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-03-28 Cont ID  
Sent By tklarge Date 2015-03-28 Time 12:28 Rev Time 0.00
Received By tklarge Date 2015-03-28 Time 11:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-03-19 Cont ID  
Sent By tklarge Date 2015-03-19 Time 10:27 Rev Time 0.00
Received By tklarge Date 2015-03-13 Time 17:14 Sent To  
Notes
2015-03-13 17:15:39SENT TO PLUMBING UNDER $5000