Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2016-03-07 Cont ID  
Sent By shill Date 2016-03-07 Time 07:39 Rev Time 0.00
Received By shill Date 2016-03-07 Time 07:38 Sent To Z
Notes
2016-03-07 07:38:54****PROVISOS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. WITHIN 90 DAYS OF PERMIT ISSUANCE, PROVIDE EVIDENCE
 OF COMPLIANCE WITH THE ART IN PUBLIC PLACES ORDINANCE.
 PLEASE PROVIDE THIS VIA EMAIL TO [email protected],
 [email protected].
  
 2. ROOF PRODUCT APPROVAL WITH PROPOSED ASSEMBLY
 INDICATED, RAS 117 CALCULATIONS FOR ENHANCED FASTENING
 (IF REQUIRED), AND ROOF DESIGN PRESSURES TO BE
 SUBMITTED WITH ROOF SUB PERMIT APPLICATION FOR REVIEW
 PRIOR TO INSTALLATION. THE PRODUCT APPROVAL IS TO BE
 REVIEWED BY DESIGNER OF RECORD PRIOR TO SUBMITTAL.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2016-01-22 Cont ID  
Sent By shill Date 2016-01-22 Time 11:36 Rev Time 0.00
Received By shill Date 2016-01-21 Time 15:47 Sent To  
Notes
2016-01-22 11:33:02****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY REQUIRED
 PRIOR TO PERMIT ISSUANCE; 561-233-5025. THE PLANS ARE
 TO BE STAMPED AND THE RECEIPT PROVIDED.
  
 2. PROVIDE AN ORIGINAL SOILS REPORT LETTER, FS 471.
  
  
 ****PROVISOS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. WITHIN 90 DAYS OF PERMIT ISSUANCE, PROVIDE EVIDENCE
 OF COMPLIANCE WITH THE ART IN PUBLIC PLACES ORDINANCE.
  
 2. ROOF PRODUCT APPROVAL WITH PROPOSED ASSEMBLY
 INDICATED, RAS 117 CALCULATIONS FOR ENHANCED FASTENING
 (IF REQUIRED), AND ROOF DESIGN PRESSURES TO BE
 SUBMITTED WITH ROOF SUB PERMIT APPLICATION FOR REVIEW
 PRIOR TO INSTALLATION. THE PRODUCT APPROVAL IS TO BE
 REVIEWED BY DESIGNER OF RECORD PRIOR TO SUBMITTAL.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2015-10-29 Cont ID  
Sent By jwitmer Date 2015-10-29 Time 16:55 Rev Time 0.00
Received By jwitmer Date 2015-10-29 Time   Sent To E
Notes
2015-10-29 13:38:51BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15030515
 ADD: 3001 OKEECHOBEE BLVD.
 CONT: HEDRICK BROTHERS
 TEL: (561)689-8880
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: THURS. OCT. 29/2015
 ACTION: DENIED
  
 NOTE: CHANGED FROM DIGITAL TO PAPER PLANS. IN SOME
 CASES YOU WILL SEE 2ND REVIEW, IN A FEW CASES WHEN THE
 PROJECT WAS A ELECTRONIC REVIEW SOME COMMENTS WERE
 SATISFIED BUT WITH THIS PAPER SUBMITTAL THE COMMENTS
 THAT WERE SATISFIED WOULD HAVE NEEDED THE BACK UP PAPER
 DOCUMENTS, SINCE THE CONTRACTOR HAS ELECTED TO RESUBMIT
 IN PAPER.
  
 1) THIS PERMIT WILL REQUIRE A RESIDENT INSPECTOR ON
 SITE FOR BUILDINGS WITH STRUCTURAL STEEL, WELDABLE
 JOINTS AND OR BOLTABLE JOINTS, BAR JOIST AND STEEL ROOF
 DECKING AND OR SHORING REQUIREMENTS.
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 110.3.9 OTHER
 INSPECTIONS SERVICES. THE BUILDING OFFICIAL MAY MAKE,
 OR CAUSE TO BE MADE BY OTHERS, THE INSPECTIONS REQUIRED
 BY SECTION 109. HE/SHE MAY ACCEPT REPORTS OF INSPECTORS
 OF RECOGNIZED INSPECTION SERVICES, PROVIDED THAT AFTER
 INVESTIGATION HE/SHE IS SATISFIED AS TO THEIR
 QUALIFICATIONS AND RELIABILITY. A CERTIFICATE CALLED
 FOR BY ANY PROVISION OF THE TECHNICAL CODES SHALL NOT
 BE BASED ON SUCH REPORTS UNLESS THE SAME ARE IN WRITING
 AND CERTIFIED BY A RESPONSIBLE OFFICER OF SUCH SERVICE.
 THE BUILDING OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY
 AN INSPECTION SERVICE IN THE FOLLOWING INSTANCES:
  
 1. FOR BUILDINGS OR ADDITIONS OF TYPE I OR II
 CONSTRUCTION
 2. FOR ALL MAJOR STRUCTURAL ALTERATIONS
 7. FOR BUILDINGS AND STRUCTURES OF UNUSUAL DESIGN OR
 METHODS OF CONSTRUCTION
  
 RESIDENT INSPECTOR FORMS MUST BE SIGNED BY ALL PARTIES
 NOTARIZED AND RETURNED TO THE BUILDING DEPARTMENT.
  
 RESIDENT INSPECTOR FORMS WERE SENT :
 [email protected] 4:04PM 06/23/15
 2ND SET OF RESIDENT INSPECTOR FORMS WERE E-MAILED TO:
 [email protected] 10/29/2015 01:50 PM
  
 1A)SEMI-COMPLIED. RESIDENT INSPECTOR RESUME' RECEIVED.
 THE BUILDING OFFICIAL OR HIS DESIGNEE WILL REVIEW THE
 RESUME'. AFTER THE RESUME' IS REVIEWED, AN INTERVIEW
 WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES WILL AN
 INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST MEETING
 THE ABOVE CRITERIA.
 CONTACT KEN CONRAD
 TEL: 561-805-6666
 E-MAIL: [email protected]
  
 1B) COMPLIED. CONTRACTOR JOB SUMMARY OR HISTORY FOR
 THIS TYPE OF CONSTRUCTION.
  
 1C) NOTICE ONLY NO ACTION NEED TO BE TAKEN AT THIS
 TIME. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, THE
 PERMIT LIBRARIAN WILL E-MAIL YOU, THE APPROVED AND
 BATCH STAMPED PLANS SO YOU MAY PRINT YOUR PLANS, TWO
 SETS OF PLANS WILL NEED TO BE PRINTED IN COLOR, (1) FOR
 THE RESIDENT INSPECTOR, THE OTHER FOR THE MEP
 INSPECTORS.
  
 1D)NOTICE ONLY, NO ACTION NEED TO BE TAKEN AT THIS
 TIME. PLEASE CALL THE CITY OF WEST PALM BEACH?S
 AUTOMATED TELEPHONE INSPECTIONS LINE (561) 805-6700)
 FOR IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS.
  
 2) 2ND REQUEST. FOUNDATIONS WILL NEED SOILS ENGINEERS'
 REPORT. SHEET S-3 FOUNDATION NOTE 1-A. 2010 FBC-B
 1803.5.2 QUESTIONABLE SOIL.
 WHERE THE CLASSIFICATION, STRENGTH OR COMPRESSIBILITY
 OF THE SOIL IS IN DOUBT OR WHERE A LOAD-BEARING VALUE
 SUPERIOR TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE
 BUILDING OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A
 GEOTECHNICAL INVESTIGATION BE CONDUCTED.
  
 3) SHEET S-3:
  
 3A) THIS PERMIT WAS SUBMITTED ON MARCH 12/ 2015 UNDER
 THE 2010 FBC-B. SHEET S-3 REFERENCES THE 2014 FBC, THE
 5TH EDITION OF THE FLORIDA BUILDING CODE, PLEASE
 CORRECT. THE 5TH EDITION WAS NOT ADOPTED UNTIL JUNE 30/
 2015 STATEWIDE.
  
 3B) PLEASE PROVIDE WIND PRESSURES FOR UNDER THE 2010
 FBC-B IN VASD 140 MPH 3 SECOND GUST. 2010 FBC-B
 1609.1.1 DETERMINATION OF WIND DESIGN- CHAPTER 6 OF
 ASCE 7-10.
  
 3C) SHEET S3 THE VASD PRESSURES FOR 140 MPH VASD WITH A
 MEAN ROOF HEIGTH OF APPROX. 16.5 FT ARE CORRECT FOR THE
 ROOF ZONES, THE NEGATIVE PRESSURES FOR WALL ZONES 4 & 5
 ARE LOW FOR 10 SQ. FT.
  
 4) 2ND REVIEW. COMPONENTS & CLADDING 2010 FBC-B
 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41 COMPONENTS
 & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS & MULLIONS.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, ACM PANELS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF CURBS,
 EXHAUST FANS
 (G)PRE-ENGINEERED A/C STANDS
  
 5) 2ND REQUEST. 1407.4 STRUCTURAL DESIGN. MCM SYSTEMS
 SHALL BE DESIGNED AND CONSTRUCTED TO RESIST WIND LOADS
 AS REQUIRED BY CHAPTER 16 FOR COMPONENTS AND CLADDING.
 1407.5 APPROVAL. RESULTS OF APPROVED TESTS OR AN
 ENGINEERING ANALYSIS SHALL BE SUBMITTED TO THE BUILDING
 OFFICIAL TO VERIFY COMPLIANCE WITH THE REQUIREMENTS OF
 CHAPTER 16 FOR WIND LOADS.
  
 6) 2ND REQUEST. 2010 FBC 107.3.4.1 PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE
 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
  
 7) COMPLIED.
  
 8) PROVISO: ART IN PUBLIC PLACES. THE CITY OF WEST PALM
 BEACH ART IN PUBLIC PLACES ORDINANCE REQUIREMENT THAT
 APPLIES TO ANY REMODEL OR NEW CONSTRUCTION PROJECT FOR
 WHICH THE PERMIT APPLICATION WAS SUBMITTED AFTER
 7/1/14, AND THE TOTAL PROJECT CONSTRUCTION COSTS ARE
 EQUAL TO OR GREATER THAN $500,000. PER CITY OF WEST
 PALM BEACH ORDINANCE NO. 4504-14, AND CITY OF WEST PALM
 BEACH CODE OF ORDINANCES, ARTICLE V, ART IN PUBLIC
 PLACES, SECTION 78-123(A) AND SECTION 78-126(A), THE
 ART ASSESSMENT IS 1% OF THE TOTAL PROJECT CONSTRUCTION
 COST.
  
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE
 V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND
 NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO
 THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS.
  
 9) IMPACT FEES BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-06-23 Cont ID  
Sent By jwitmer Date 2015-06-23 Time 16:53 Rev Time 0.00
Received By jwitmer Date 2015-06-23 Time 15:36 Sent To  
Notes
2015-06-23 16:52:54BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15030515
 ADD: 3001 OKEECHOBEE BLVD.
 CONT: HEDRICK BROTHERS
 TEL: (561)689-8880
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. JUNE 23/2015
 ACTION: DENIED
  
 1) THIS PERMIT WILL REQUIRE A RESIDENT INSPECTOR ON
 SITE FOR BUILDINGS WITH STRUCTURAL STEEL, WELDABLE
 JOINTS AND OR BOLTABLE JOINTS, BAR JOIST AND STEEL ROOF
 DECKING AND OR SHORING REQUIREMENTS.
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 110.3.9 OTHER
 INSPECTIONS SERVICES. THE BUILDING OFFICIAL MAY MAKE,
 OR CAUSE TO BE MADE BY OTHERS, THE INSPECTIONS REQUIRED
 BY SECTION 109. HE/SHE MAY ACCEPT REPORTS OF INSPECTORS
 OF RECOGNIZED INSPECTION SERVICES, PROVIDED THAT AFTER
 INVESTIGATION HE/SHE IS SATISFIED AS TO THEIR
 QUALIFICATIONS AND RELIABILITY. A CERTIFICATE CALLED
 FOR BY ANY PROVISION OF THE TECHNICAL CODES SHALL NOT
 BE BASED ON SUCH REPORTS UNLESS THE SAME ARE IN WRITING
 AND CERTIFIED BY A RESPONSIBLE OFFICER OF SUCH SERVICE.
 THE BUILDING OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY
 AN INSPECTION SERVICE IN THE FOLLOWING INSTANCES:
  
 1. FOR BUILDINGS OR ADDITIONS OF TYPE I OR II
 CONSTRUCTION
 2. FOR ALL MAJOR STRUCTURAL ALTERATIONS
 7. FOR BUILDINGS AND STRUCTURES OF UNUSUAL DESIGN OR
 METHODS OF CONSTRUCTION
  
 RESIDENT INSPECTOR FORMS MUST BE SIGNED BY ALL PARTIES
 NOTARIZED AND RETURNED TO THE BUILDING DEPARTMENT.
  
 RESIDENT INSPECTOR FORMS WERE SENT :
 [email protected] 4:04PM 06/23/15
  
 1A)SEMI-COMPLIED. RESIDENT INSPECTOR RESUME' RECEIVED.
 THE BUILDING OFFICIAL OR HIS DESIGNEE WILL REVIEW THE
 RESUME'. AFTER THE RESUME' IS REVIEWED, AN INTERVIEW
 WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES WILL AN
 INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST MEETING
 THE ABOVE CRITERIA.
 CONTACT KEN CONRAD
 TEL: 561-805-6666
 E-MAIL: [email protected]
  
 1B) COMPLIED. CONTRACTOR JOB SUMMARY OR HISTORY FOR
 THIS TYPE OF CONSTRUCTION.
  
 1C) NOTICE ONLY NO ACTION NEED TO BE TAKEN AT THIS
 TIME. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, THE
 PERMIT LIBRARIAN WILL E-MAIL YOU, THE APPROVED AND
 BATCH STAMPED PLANS SO YOU MAY PRINT YOUR PLANS, TWO
 SETS OF PLANS WILL NEED TO BE PRINTED IN COLOR, (1) FOR
 THE RESIDENT INSPECTOR, THE OTHER FOR THE MEP
 INSPECTORS.
  
 1D)NOTICE ONLY, NO ACTION NEED TO BE TAKEN AT THIS
 TIME. PLEASE CALL THE CITY OF WEST PALM BEACH?S
 AUTOMATED TELEPHONE INSPECTIONS LINE (561) 805-6700)
 FOR IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS.
  
 2) COMPLIED. SOILS ENGINEERS' LETTER
  
 3) COMPLIED.
  
 4-5)2ND REVIEW. THE ROOFING APPROVAL SUBMITTED
 MIAMI-DADE NOA 12-0605.02 DOES NOT HAVE ANY OF THE
 SUB-SYSTEMS CIRCLED IDENTIFYING WHICH SUB-SYSTEM IS
 GOING TO BE INSTALLED. PLEASE REVIEW PRESSURES AND IF
 LIMITATION NUMBER 7 OR 9. IF THE SUB-SYSTEM HAS
 LIMITATION #7 AND ROOF ZONES 2 & 3 REQUIRE ENHANCED
 FASTENING A DESIGN PROFESSIONAL CAN COMPLETE THE RAS
 117 CALCULATION.
  
 COMPONENTS & CLADDING 2010 FBC-B 1609.1.2 PROTECTION OF
 OPENINGS, 1609.6.4.41 COMPONENTS & CLADDING FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010
 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS
 THAT WILL REQUIRE PRODUCT APPROVALS:
 (31(D) ROOFING PRODUCTS AND ASSEMBLIES
  
  
 6) COMPLIED.
  
 7) COMPLIED.
  
 8) PROVISO: ART IN PUBLIC PLACES. THE CITY OF WEST PALM
 BEACH ART IN PUBLIC PLACES ORDINANCE REQUIREMENT THAT
 APPLIES TO ANY REMODEL OR NEW CONSTRUCTION PROJECT FOR
 WHICH THE PERMIT APPLICATION WAS SUBMITTED AFTER
 7/1/14, AND THE TOTAL PROJECT CONSTRUCTION COSTS ARE
 EQUAL TO OR GREATER THAN $500,000. PER CITY OF WEST
 PALM BEACH ORDINANCE NO. 4504-14, AND CITY OF WEST PALM
 BEACH CODE OF ORDINANCES, ARTICLE V, ART IN PUBLIC
 PLACES, SECTION 78-123(A) AND SECTION 78-126(A), THE
 ART ASSESSMENT IS 1% OF THE TOTAL PROJECT CONSTRUCTION
 COST.
  
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE
 V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND
 NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO
 THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-04-23 Cont ID  
Sent By jwitmer Date 2015-04-23 Time 16:18 Rev Time 0.00
Received By jwitmer Date 2015-04-23 Time 13:03 Sent To  
Notes
2015-04-23 16:18:36BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15030515
 ADD: 3001 OKEECHOBEE BLVD.
 CONT: HEDRICK BROTHERS
 TEL: (561)689-8880
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 IMPORTANT NOTICE: EFFECTIVE MARCH 30, 2015
 ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED
 ELECTRONICALLY
 UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS
 SUBMISSION OPTIONS ARE AS FOLLOWS:
 1 UPLOAD VIA THE PROJECT DOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL
 SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED
 NAMING CONVENTION FOR EACH DOCUMENT
 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER
 DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE
 REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT
 TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS
 ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES
 AVAILABLE.
  
 1ST REVIEW
 DATE: THURS. APRIL 23/2015
 ACTION: DENIED
  
 1) THIS PERMIT WILL REQUIRE A RESIDENT INSPECTOR ON
 SITE FOR BUILDINGS WITH STRUCTURAL STEEL,WELDABLE
 JOINTS AND OR BOLTABLE JOINTS, BAR JOIST AND STEEL ROOF
 DECKING AND OR SHORING REQUIREMENTS.
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 110.3.9 OTHER
 INSPECTIONS SERVICES. THE BUILDING OFFICIAL MAY MAKE,
 OR CAUSE TO BE MADE BY OTHERS, THE INSPECTIONS REQUIRED
 BY SECTION 109. HE/SHE MAY ACCEPT REPORTS OF INSPECTORS
 OF RECOGNIZED INSPECTION SERVICES, PROVIDED THAT AFTER
 INVESTIGATION HE/SHE IS SATISFIED AS TO THEIR
 QUALIFICATIONS AND RELIABILITY. A CERTIFICATE CALLED
 FOR BY ANY PROVISION OF THE TECHNICAL CODES SHALL NOT
 BE BASED ON SUCH REPORTS UNLESS THE SAME ARE IN WRITING
 AND CERTIFIED BY A RESPONSIBLE OFFICER OF SUCH SERVICE.
 THE BUILDING OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY
 AN INSPECTION SERVICE IN THE FOLLOWING INSTANCES:
  
 1. FOR BUILDINGS OR ADDITIONS OF TYPE I OR II
 CONSTRUCTION
 2. FOR ALL MAJOR STRUCTURAL ALTERATIONS
 3. WHERE THE CONCRETE DESIGN IS BASED ON COMPRESSIVE
 STRENGTH (F ?C) IN EXCESS OF 3000
 POUNDS PER SQUARE INCH
 4. FOR PILE DRIVING
 5. FOR BUILDINGS WITH AREA GREATER THAN 20,000 SQUARE
 FOOT
 6. FOR BUILDINGS MORE THAN 2 STORIES IN HEIGHT
 7. FOR BUILDINGS AND STRUCTURES OF UNUSUAL DESIGN OR
 METHODS OF CONSTRUCTION
  
 1A) FOR THE RESIDENT INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
 CONTACT KEN CONRAD
 TEL: 561-805-6666
 E-MAIL: [email protected]
  
 1B) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION. THIS MAY BE
 SUBMITTED TO KEN CONRAD BY E-MAIL. KEN CONRAD:
 [email protected]
  
 1C) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE
 REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, THE
 PERMIT LIBRARIAN WILL E-MAIL YOU, THE APPROVED AND
 BATCH STAMPED PLANS SO YOU MAY PRINT YOUR PLANS, TWO
 SETS OF PLANS WILL NEED TO BE PRINTED IN COLOR, (1) FOR
 THE RESIDENT INSPECTOR, THE OTHER FOR THE MEP
 INSPECTORS.
  
 1D) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR
 IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS.
  
 2) FOUNDATIONS WILL NEED SOILS ENGINEERS' REPORT. SHEET
 S-2 FOUNDATION NOTE 1-A. 2010 FBC-B 1803.5.2
 QUESTIONABLE SOIL.
 WHERE THE CLASSIFICATION, STRENGTH OR COMPRESSIBILITY
 OF THE SOIL IS IN DOUBT OR WHERE A LOAD-BEARING VALUE
 SUPERIOR TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE
 BUILDING OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A
 GEOTECHNICAL INVESTIGATION BE CONDUCTED.
  
 3) SHEET S-2 HAS BOTH VULT AND VASD PRESSURES FOR ROOF
 ZONES 1-3 AND WALL ZONES 4-5. PLEAASE PROVIDE THE MEAN
 ROOF HEIGHT OF THE NEW ROOF, THIS WILL AFFECT THE
 PRESSURES MEAN ROOF HEIGHT APPROXIMATELY 23 FEET,
 EXPOSURE C, HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT,
 * SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 4) COMPONENTS & CLADDING 2010 FBC-B 1609.1.2 PROTECTION
 OF OPENINGS, 1609.6.4.41 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS & MULLIONS.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, ACM PANELS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 5) 1407.4 STRUCTURAL DESIGN.
 MCM SYSTEMS SHALL BE DESIGNED AND CONSTRUCTED TO RESIST
 WIND LOADS AS REQUIRED BY CHAPTER 16 FOR COMPONENTS AND
 CLADDING.
 1407.5 APPROVAL.
 RESULTS OF APPROVED TESTS OR AN ENGINEERING ANALYSIS
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO VERIFY
 COMPLIANCE WITH THE REQUIREMENTS OF CHAPTER 16 FOR WIND
 LOADS.
  
 6) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 7) THE SUBMITTED PACKAGE DIDN'T HAVE ANY DOCUMENTATION
 FOR COMPLYING WITH THE 2010 ENERGY CODE. 101.4.1
 EXISTING BUILDINGS. EXISTING BUILDINGS SHALL MEET THE
 CRITERIA IN TABLE 101.4.1 AS APPROPRIATE TO THE
 CONDITION DESCRIBED. EXCEPT AS SPECIFIED IN THIS
 CHAPTER, THIS CODE SHALL NOT BE USED TO REQUIRE THE
 REMOVAL, ALTERATION OR ABANDONMENT OF, NOR PREVENT THE
 CONTINUED USE AND MAINTENANCE OF, AN EXISTING BUILDING
 OR BUILDING SYSTEM LAWFULLY IN EXISTENCE AT THE TIME OF
 ADOPTION OF THIS CODE. 103.2.1 CODE DEMONSTRATION
 FORMS. SEE TABLE 103.2.1.
  
 8) ART IN PUBLIC PLACES. THE CITY OF WEST PALM BEACH
 ART IN PUBLIC PLACES ORDINANCE REQUIREMENT THAT APPLIES
 TO ANY REMODEL OR NEW CONSTRUCTION PROJECT FOR WHICH
 THE PERMIT APPLICATION WAS SUBMITTED AFTER 7/1/14, AND
 THE TOTAL PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR
 GREATER THAN $500,000. PER CITY OF WEST PALM BEACH
 ORDINANCE NO. 4504-14, AND CITY OF WEST PALM BEACH CODE
 OF ORDINANCES, ARTICLE V, ART IN PUBLIC PLACES, SECTION
 78-123(A) AND SECTION 78-126(A), THE ART ASSESSMENT IS
 1% OF THE TOTAL PROJECT CONSTRUCTION COST.
  
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE
 V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND
 NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO
 THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS
  
 9) WHEN RESUBMITTING PLANS PLEASESUBMIT A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2016-02-10 Cont ID  
Sent By rlecky Date 2016-02-10 Time 11:08 Rev Time 0.00
Received By rlecky Date 2016-02-10 Time 10:25 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2015-11-18 Cont ID  
Sent By albarran Date 2015-11-18 Time 18:00 Rev Time 0.00
Received By albarran Date 2015-11-18 Time 15:47 Sent To I
Notes
2015-11-18 17:33:36THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
 1. FBC-E SECTION 502.3.8: RECESSED LUMINARIES INSTALLED
 IN THE BUILDING ENVELOPE SHALL BE IC RATED AND SEALED
 TO LIMIT THE LEAKAGE OF AIR FROM THE CONDITIONED SPACE
 TO THE NON-CONDITIONED SPACE.
 2. FBC-E SECTION 505.2 LIGHTING CONTROLS (MANDATORY):
 YOU SHALL PROVIDE THE REQUIRED LIGHTING CONTROLS FOR
 ROOMS 107 - 114 AND 121 - 123. THERE MAY BE ADDITIONAL
 LOCATIONS WHICH I MAY HAVE MISSED SO REVIEW YOUR
 LIGHTING DESIGN TO COMPLY WITH SUCH REQUIREMENT.
 3. FBC-E SECTION 505 ELECTRICAL POWER & LIGHTING
 SYSTEMS (MANDATORY): HAS NUMEROUS LIGHTING REQUIREMENTS
 WHICH MAY APPLY.
 4. FBC-E YOU SHALL SUBMIT INTERIOR AND EXTERIOR
 LIGHTING POWER ALLOWANCES CHARTS INDICATING COMPLIANCE
 WITH LIGHTING POWER ALLOWANCES.
 5. FBC-E 505.7.3: ALL FEEDER AND BRANCH CIRCUIT
 CALCULATIONS SHALL TAKE INTO ACCOUNT THE CODE REQUIRED
 VOLTAGE DROP MAXIMUMS.
 6. FBC-E 505.7.4 COMPLETION REQUIREMENTS: A NOTE ON THE
 APPROVED PLANS SHALL INDICATE THAT WITHIN 30 DAYS OF
 SYSTEM ACCEPTANCE AN AS-BUILT SET OF ELECTRICAL
 DRAWINGS SHALL BE PROVIDED TO THE BUILDING OWNER.
 7. NEC 110.16: ALL ELECTRICAL PANELS AND EQUIPMENT
 SHALL BE MARKED WITH AN ARCH-FLASH HAZARD WARNING
 DECAL.
 8. NEC 210.62: THERE SHALL BE A 125 V. SINGLE PHASE 15
 OR 20 AMP RECEPTACLE OUTLET FOR EVERY 12 FT. OR MAJOR
 PORTION OF SHOW WINDOW AREA MEASURED HORIZONTALLY.
 9. NEC 215.5: YOU SHALL SUBMIT A SITE SPECIFIC FEEDER
 DIAGRAM SHOWING FEEDER DETAILS, LOAD CALCULATIONS,
 CONDUCTOR SIZING AND INSULATION. THIS SHALL INCLUDE THE
 LOAD FOR THE ADDITIONAL OUTLETS REQUIRED ABOVE.
 10. NEC 230: YOU SHALL INDICATE ON THE FLOOR PLAN OR
 SITE PLAN THE LOCATION OF THE SERVICE EQUIPMENT AND ANY
 UTILITY TRANSFORMERS. IF AUXILIARY GENERATOR IS
 PROPOSED. MANUFACTURERS? DOCUMENTATION FOR THE
 GENERATOR SHALL BE SUBMITTED.
 11. NEC 314.27(C): ALL FLOOR RECEPTACLES SHALL ME IN
 BOXES LISTED FOR THIS PURPOSE.
 12. NEC 408.4: CIRCUIT DIRECTORY FOR PANEL "AC" SHALL
 BE PROVIDED. ALL ADDITIONAL SHOW WINDOW LOADS SHALL BE
 INCLUDED ON THE PANEL SCHEDULES.
 13. NEC 408.58: ALL PANELS SHALL BE MARKED WITH THEIR
 OPERATING VOLTAGE AND PHASE DESIGNATION
 14. NEC 600.5: EACH COMMERCIAL ESTABLISHMENT ACCESSIBLE
 TO PEDESTRIANS SHALL HAVE A DEDICATED SIGN OUTLET IN AN
 ACCESSIBLE LOCATION AT EVERY ENTRANCE ACCESSIBLE TO
 PEDESTRIANS.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE
 INSERT CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2015-07-09 Cont ID  
Sent By dhayes Date 2015-07-09 Time 08:36 Rev Time 0.00
Received By dhayes Date 2015-07-09 Time 07:46 Sent To  
Notes
2015-07-09 08:39:557/9/2015
 PROJECT: SCHUMACHER VOLVO
 PERMIT#: 15030515
 CODE: 2011EDITION OF THE NEC, FIFTH EDITION OF THE FBC
 , WPB AMENDMENTS TO THE FBC, CHAPTER 1, ADMINISTRATION,
 FBC SUPPLEMENTS.
 2ND ELECTRICAL PLAN REVIEW
 ACTION: APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN
 APPROVED PROVISIONALLY. FAILURE TO CORRECT THE LISTED
 DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED
 INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION
 FEE(S).
  
 1) LIGHTING SYSTEMS SHALL BE PROVIDED WITH CONTROLS AS
 REQUIRED IN. OCCUPANCY SENSORS REQUIRED IN ACCORDANCE
 WITH PROVIDE AUTOMATIC LIGHTING SHUTOFF. FBC-ENERGY
 CODE SECTIONS 505.2.1, 505.2.2, 505.2.3 AND 505.2.4.
  
 2) RECEPTACLE OUTLET BOXES INSTALLED IN THE FLOOR SHALL
 BE LISTED SPECIFICALLY FOR THIS APPLICATION. NEC
 314.27(C)
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2015-07-08 Cont ID  
Sent By   Date 2015-07-08 Time   Rev Time 0.00
Received By dhayes Date 2015-07-08 Time 14:50 Sent To  
Notes
2015-07-08 15:07:40 
 A LOCKED 2ND REVIEW STOP PROMPTED THE OPENING OF A
 THIRD REVIEW STOP. SEE THAT FOR THE MOST RECENT
 ELECTRICAL RECIEW ON 7/09/2015.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-04-27 Cont ID  
Sent By dhayes Date 2015-04-27 Time 13:27 Rev Time 0.00
Received By dhayes Date 2015-04-27 Time 08:10 Sent To  
Notes
2015-04-27 13:27:044/27/2015
 PROJECT: SHUMACHER VOLVO RENNOVATION
 PERMIT#: 15030515
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW
 COMMENTS:
  
 1) PROVIDE A VOLTAGE DROP CALCULATION FOR BRANCH
 CIRCUIT WIRING. THE DISTANCE FROM THE PANELS IN THE
 ELECTRICAL ROOM TO THE OUTSIDE BOLLARDS AND UPLIGHTS IS
 BEYOND THE PERCENTAGE OF VOLTAGE DROP ALLOWED ON AN
 8AMP BRANCH CIRCUIT. OPERATING AT 120VOLTS NEC
 210.19(A)
  
 2) PROVIDE CIRCUIT DIRECTORIES WITH EACH CIRCUIT HAVING
 A CLEAR AND SPECIFIC PURPOSE. NEC 408.4
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2016-01-28 Cont ID  
Sent By pleduc Date 2016-01-28 Time   Rev Time 0.00
Received By pleduc Date 2016-01-28 Time 16:39 Sent To  
Notes
2016-01-28 16:39:55THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1. SHEET A 1.3 - FOR CO PROTECTION PROVIDE CONTINUOUS
 VENTILATION PER NFPA 720.
  
 2. SHEET A 1.3 - PROVIDE INTERIOR DRAPES AND
 FURNISHINGS PROTECTION REQUIRMENTS PER NFPA 701.
  
 3. THE NATURE OF THE REMODEL MAY REQUIRE AN EVALUATION
 OF THE FIRE ALARM AND SPRINKLER SYSTEM FOR CODE
 COVERAGE AND COMPLIANCE. ANY REMOVAL AND/OR ADDED
 CONSTRUCTION OF WALLS REQUIRES AN EVALUATION.
  
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2015-10-28 Cont ID  
Sent By wjolin Date 2015-10-28 Time 09:11 Rev Time 0.00
Received By wjolin Date 2015-10-28 Time 08:50 Sent To  
Notes
2015-10-28 09:11:39THE PREVIOUS PLAN REVIEW FOR THIS PERMIT NUMBER WAS FOR
 3021 OKEECHOBEE BOULEVARD. THE RESUBMITTED PLAN
 INDICATES A DIFFERENT BUILDING WITH AN ADDRESS OF 3001
 OKEECHOBEE BOULEVARD. PLEASE EXPLAIN?
  
  
  
 3021 OKEECHOBEE BOULEVARD
 PERMIT #15030515
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET A-1.3: CARBON MONOXIDE IS A COLORLESS, ODORLESS,
 TASTELESS GAS. PROVIDE CONTINUOUS VENTILATION OR CARBON
 MONOXIDE DETECTION PER NFPA 720 FOR INDOOR NEW CAR
 DELIVERY #102.
  
 SHEET A-1.3: NEW CAR DELIVERY DRAPES: CURTAINS, DRAPES
 AND OTHER LOOSELY HANGING FINISHINGS/DECORATIONS SHALL
 MEET THE FLAME PROPAGATION CRITERIA OF NFPA 701
 (MATERIAL WILL SELF EXTINGUISH ONCE DIRECT FIRE FLAME
 HAS BEEN REMOVED).
  
 SHEET LS-1.0 AND SHEET E-2.1: COORDINATE EXIT SIGN
 LOCATIONS.
  
 SHEET E-3.1: PLAN INDICATES 3 EXISTING FIRE ALARM
 DEVICES; HOWEVER, NO ADDITIONAL FIRE ALARM SYSTEM
 INFORMATION PROVIDED. PER FBC SECTION 907.1.1
 CONSTRUCTION DOCUMENTS - "CONSTRUCTION DOCUMENTS FOR
 FIRE ALARM SYSTEMS SHALL BE OF SUFFICIENT CLARITY TO
 INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE, THE FLORIDA FIRE PREVENTION
 CODE, AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL."
  
 GENERAL: PROVIDE AN EXTERIOR KEY SAFE TO ALLOW
 EMERGENCY RESPONDERS NON-FORCIBLE ENTRY INTO THE
 BUILDING DURING NON-BUSINESS HOURS. A KEY SAFE CAN BE
 ORDERED FROM WWW.KNOXBOX.COM.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-04-16 Cont ID  
Sent By wjolin Date 2015-04-16 Time 15:33 Rev Time 0.00
Received By wjolin Date 2015-04-16 Time 15:02 Sent To  
Notes
2015-04-16 15:16:483021 OKEECHOBEE BOULEVARD
 PERMIT #15030515
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET A-1.3: CARBON MONOXIDE IS A COLORLESS, ODORLESS,
 TASTELESS GAS. PROVIDE CONTINUOUS VENTILATION OR CARBON
 MONOXIDE DETECTION PER NFPA 720 FOR INDOOR NEW CAR
 DELIVERY #102.
  
 SHEET A-1.3: NEW CAR DELIVERY DRAPES: CURTAINS, DRAPES
 AND OTHER LOOSELY HANGING FINISHINGS/DECORATIONS SHALL
 MEET THE FLAME PROPAGATION CRITERIA OF NFPA 701
 (MATERIAL WILL SELF EXTINGUISH ONCE DIRECT FIRE FLAME
 HAS BEEN REMOVED).
  
 SHEET LS-1.0 AND SHEET E-2.1: COORDINATE EXIT SIGN
 LOCATIONS.
  
 SHEET E-3.1: PLAN INDICATES 3 EXISTING FIRE ALARM
 DEVICES; HOWEVER, NO ADDITIONAL FIRE ALARM SYSTEM
 INFORMATION PROVIDED. PER FBC SECTION 907.1.1
 CONSTRUCTION DOCUMENTS - "CONSTRUCTION DOCUMENTS FOR
 FIRE ALARM SYSTEMS SHALL BE OF SUFFICIENT CLARITY TO
 INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE, THE FLORIDA FIRE PREVENTION
 CODE, AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL."
  
 GENERAL: PROVIDE AN EXTERIOR KEY SAFE TO ALLOW
 EMERGENCY RESPONDERS NON-FORCIBLE ENTRY INTO THE
 BUILDING DURING NON-BUSINESS HOURS. A KEY SAFE CAN BE
 ORDERED FROM WWW.KNOXBOX.COM.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2016-03-10 Cont ID  
Sent By dkittred Date 2016-03-10 Time 08:16 Rev Time 0.00
Received By shill Date 2016-03-04 Time 11:15 Sent To  
Notes
2016-03-07 10:24:393/7 TO ZONING BOX
  
2016-03-04 11:15:42RESUB ROUTED TO JWITMER

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-02-10 Cont ID  
Sent By rlecky Date 2016-02-10 Time 11:35 Rev Time 0.00
Received By rlecky Date 2016-01-08 Time 16:00 Sent To  
Notes
2016-01-08 16:00:50C40

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-11-18 Cont ID  
Sent By albarran Date 2015-11-18 Time 18:34 Rev Time 0.00
Received By albarran Date 2015-10-05 Time 12:51 Sent To  
Notes
2015-11-18 18:51:3811/18/15 FAILED ELECTRICAL REVIEW. CONTRACTOR NOTIFIED
 VIA EMAIL. SENT TO LARGE DENIED BIN "H". MA
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-07-09 Cont ID  
Sent By lmarchan Date 2015-07-09 Time 11:30 Rev Time 0.00
Received By lmarchan Date 2015-05-14 Time 11:21 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-05-02 Cont ID  
Sent By hmoser Date 2015-05-02 Time 09:23 Rev Time 0.00
Received By hmoser Date 2015-03-23 Time 15:40 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2016-03-07 Cont ID  
Sent By shill Date 2016-03-07 Time 10:03 Rev Time 0.00
Received By shill Date 2016-03-07 Time 10:03 Sent To  
Notes
2016-03-07 10:03:41SEE IMPACT FEE STAMP
 MU 2016-3428
 EXISTING USE CREDIT, NO FEES DUE
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-01-22 Cont ID  
Sent By shill Date 2016-01-22 Time 09:27 Rev Time 0.00
Received By shill Date 2016-01-22 Time 09:27 Sent To  
Notes
2016-01-22 09:28:34****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY REQUIRED.
 561-233-5025 FOR MORE INFORMATION.
  
 THE PLANS ARE TO BE STAMPED AND THE RECEIPT PROVIDED.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2015-10-13 Cont ID  
Sent By ccole Date 2015-10-13 Time 07:48 Rev Time 0.00
Received By ccole Date 2015-10-13 Time 07:48 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-06-23 Cont ID  
Sent By hmoser Date 2015-06-23 Time 09:16 Rev Time 0.00
Received By hmoser Date 2015-06-23 Time 08:55 Sent To  
Notes
2015-06-23 09:16:50PASS POVISO
 PROVIDE GRILL SIZE FOR LINEARS BEFOR ROUGH INSPECTION
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFOCE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2015-05-02 Cont ID  
Sent By hmoser Date 2015-05-02 Time 09:23 Rev Time 0.00
Received By hmoser Date 2015-05-02 Time 08:49 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2016-01-20 Cont ID  
Sent By tklarge Date 2016-01-20 Time 05:06 Rev Time 0.00
Received By tklarge Date 2016-01-20 Time 03:44 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2015-10-13 Cont ID  
Sent By gjohnson Date 2015-10-13 Time 14:34 Rev Time 0.00
Received By gjohnson Date 2015-10-13 Time 13:58 Sent To  
Notes
2015-10-13 14:04:411ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
  
 PLUMBING COMMENTS:
  
 1. SHEET P2.2 IS MISSING SHEET INDEXSHOWS A P2.2 THAT
 SHEET IS REQUIRED TO COMPLETE REVIEW.
 PER WPB AMEND. 107.2.1
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2015-06-11 Cont ID  
Sent By tklarge Date 2015-06-11 Time 05:39 Rev Time 0.00
Received By tklarge Date 2015-06-11 Time 04:48 Sent To  
Notes
2015-06-11 05:36:391) SHTS. P0.1 & P2.2 - AS PREVIOUSLY NOTED, THE SIZE OF
 THE NEW STORM DRAINS SHALL COMPLY WITH THE 2010
 FBC-PLUMBING, TABLE 1106.3. THE STORM WATER ISOMETRIC
 SHOWS A TOTAL OF 3041 SQUARE FEET DRAINING INTO A 4"
 HORIZONTAL STORM WATER PIPE.EVEN AT A 4% SLOPE PER
 TABLE 1106.3, THIS LINE IS UNDERSIZED FOR A RAINFALL
 RATE OF 5 INCHES AND AN AREA OF 3041 SQUARE FEET. THE
 MINIMUM PIPE SIZE SHALL BE 6 INCHES AT A 1 % SLOPE PER
 TABLE 1106.3. THE SAME APPLIES TO THE SECONDARY
 (EMERGENCY) ROOF DRAINS. INDICATE THE SLOPE OF THE
 ELEVATED STORM DRAINAGE PIPING ON THE PLANS AND ALSO
 THE UNDERGROUND AND HORIZONTAL LINE AT GRADE.THE 6"
 HORIZONTAL LINE AT GRADE FOR THE EMERGENCY ROOF DRAINS
 AND THE LINE CONNECTING TO THE EXISTING SHALL BE
 INSTALLED WITH A MINIMUM OF A 2% SLOPE TO COMPLY WITH
 TABLE 1106.3. CLEARLY INDICATE ALL OF THE ABOVE
 APPLICABLE INFORMATION ON THE PLANS.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-04-18 Cont ID  
Sent By tklarge Date 2015-04-18 Time 05:01 Rev Time 0.00
Received By tklarge Date 2015-04-18 Time 04:51 Sent To  
Notes
2015-04-18 05:01:371) THE NEW SINK IN THE LIVING ROOM AREA SHALL COMPLY
 WITH THE FL. ACCESSIBILITY CODE SEC.212 & 606.2, 606.3.
 2) SUBMIT CALCULATIONS FOR THE SIZING OF THE NEW
 RAINWATER DRAINS & PIPING PER THE 201 FPC SEC.1106.1 &
 TABLES 1106.2 (1) & 1106.2 (2), & TABLE 1106.3. SHOW
 THE SQUARE FOOTAGE DRAINED BY EACH ROOF DRAIN.ONE-HALF
 THE AREA OF THE NEW PARAPET WALL SHALL BE ADDED TO THE
 PROJECTED ROOF AREA FOR THE SIZING OF THE DRAINS.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2016-07-01 Cont ID  
Sent By shill Date 2016-07-01 Time 14:45 Rev Time 0.00
Received By shill Date 2016-07-01 Time 14:45 Sent To  
Notes
2016-07-01 14:48:26SEE REVIEW UNDER REVISION 16070044
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2016-01-22 Cont ID  
Sent By shill Date 2016-01-22 Time 09:37 Rev Time 0.00
Received By shill Date 2016-01-22 Time 09:37 Sent To  
Notes
2016-01-22 09:44:21ROOF REVIEW REQUIRED
  
 AT TIME OF ROOF SUB PERMIT SUBMITTAL, PROVIDE A PRODUCT
 APPROVAL REVIEWED BY DOR AND ENGINEERING FOR ENHANCED
 FASTENING IF REQUIRED.
  
 ROOF COVERING IS TO COMPLY WITH THE DESIGN PRESSURES
 SPECIFIED BY ENGINEER ON SHEET S3:
  
 ZONE 1: -39
 ZONE 2: -65
 ZONE 3: -65
  
  
  
  
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status P Date 2016-01-22 Cont ID  
Sent By shill Date 2016-01-22 Time 11:50 Rev Time 0.00
Received By shill Date 2016-01-21 Time 17:12 Sent To  
Notes
2016-01-21 17:13:10CONTRACTOR: HEDRICK BROTHERS
  
 RESIDENT INSPECTOR: GFA (ERIC F. TRILLAS, PE, NOEL
 WOODALL, JENNINGS HILL, MARK SHARMAN)
  
 1 SET ROUTED TO K CONRAD DESK
  

Review Stop Z ZONING
Rev No 5 Status P Date 2016-03-10 Cont ID  
Sent By dkittred Date 2016-03-10 Time 08:01 Rev Time 0.00
Received By dkittred Date 2016-03-07 Time 10:56 Sent To  
Notes
2016-03-10 08:08:24PLANNING AND ZONING COMMENTS:
  
 3/10/16
  
 1. SEPARATE LANDSCAPE PERMIT REQUIRED FOR FINAL
 LANDSCAPING MATERIALS AND CONFIGURATION WITH
 APPROPRIATE LANDSCAPE PROTECTION, SUCH AS CURBING,
 WHERE NONE EXISTS AROUND RECONFIGURED AREAS.
  
 2. TREE ALTERATION PERMIT REQUIRED THROUGH PLANNING
 DIVISION FOR REMOVAL OR RELOCATION OF ANY TREES.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]
  

Review Stop Z ZONING
Rev No 4 Status F Date 2016-01-12 Cont ID  
Sent By dkittred Date 2016-01-12 Time 08:57 Rev Time 0.00
Received By dkittred Date 2016-01-12 Time 08:51 Sent To  
Notes
2016-01-12 08:57:35PLANNING AND ZONING COMMENTS: ***FAILED***
  
 1/12/16
  
 1, MINOR PD AMENDMENT IS STILL UNDER REVIEW AND
 REQUIRED TO BE APPROVED PRIOR TO APPROVAL THE BUILDING
 PERMIT. IF MINOR PD AMENDMENT IS APPROVED PRIOR TO
 COMPLETION OF THE BUILDING PERMIT REVIEW CYCLE AND
 FOUND CONSISTENT WITH THE APPROVED PLANS, THEN THE
 ZONING REVIEW WILL BE UPDATED APPROPRIATELY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]
  

Review Stop Z ZONING
Rev No 3 Status F Date 2015-10-15 Cont ID  
Sent By dkittred Date 2015-10-15 Time 11:18 Rev Time 0.00
Received By dkittred Date 2015-10-15 Time 09:20 Sent To  
Notes
2015-10-15 11:18:54PLANNING AND ZONING COMMENTS: ***FAILED***
  
 10/15/15
  
 1. PLANS COMPLETELY REVISED TO RENOVATE A DIFFERENT
 BUILDING ON THE SUBJECT PROPERTY. PLANNED DEVELOPMENT
 AMENDMENT APPROVAL REQUIRED THROUGH THE PLANNING
 DIVISION REQUIRED PRIOR TO ZONING APPROVAL OF THIS
 BUILDING PERMIT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]
  
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2015-05-19 Cont ID  
Sent By dkittred Date 2015-05-19 Time 14:58 Rev Time 0.00
Received By dkittred Date 2015-05-19 Time 14:21 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2015-03-31 Cont ID  
Sent By dkittred Date 2015-03-31 Time 10:22 Rev Time 0.00
Received By dkittred Date 2015-03-31 Time 09:10 Sent To  
Notes
2015-03-31 10:18:49PLANNING AND ZONING COMMENTS: ***FAILED***
  
 3/31/15
  
 1. A SEPARATE PERMIT IS REQUIRED FOR SIGNAGE. SHEET SP
 1.0 SHOULD BE UPDATED TO REMOVE THE FREESTANDING
 SIGNAGE OR A NOTATION INCLUDED INDICATING THAT THE
 FREESTANDING SIGN WILL BE SUBMITTED UNDER A SEPARATE
 PERMIT. PLEASE NOTE THAT WHEN SUBMITTING A PERMIT FOR
 THE FREESTANDING SIGN, CORRECTIONS MADE TO THE PLANS
 THROUGH THE MINOR PLANNED DEVELOPMENT REVIEW PROCESS IN
 PLANNING AND ZONING WERE NOT CARRIED THROUGH. THESE
 REDLINES INCLUDED CORRECTIONS TO THE CALCULATIONS AND
 INCLUSION OF SETBACK INFORMATION WHICH WILL NEED TO BE
 ADDRESSED ON THE SEPARATE FREESTANDING SIGN PERMIT.
  
 2. SHEET SP 1.0 HAS A NOTATION FOR "FUTURE ACCENT
 LIGHTING", HOWEVER, SHEETS E 0.1 AND E 1.1 INCLUDES THE
 PROPOSED LIGHTING FOR PERMITTING. PLEASE UPDATE SHEET
 SP 1.0 AS IT IS NOT 'FUTURE' LIGHTING.
  
 3. PER CONDITIONS THE MINOR PLANNED DEVELOPMENT
 AMENDMENT FOR THE PROPOSED CHANGES SHEET E 1.1 NEEDS TO
 DEMONSTRATE COMPLIANCE WITH ZLDR SEC. 94-207(D)(8) AND
 94-309(A) REGULATING GLARE AND LIGHT SPILLAGE AT THE
 PROPERTY LINE.
  
 GENERAL COMMENTS:
  
 4. WALL SIGNAGE INDICATED ON SHEET A 4.0 FOR FUTURE
 INSTALLATION WILL REQUIRE A MINOR PLANNED DEVELOPMENT
 AMENDMENT APPLICATION BE SUBMITTED TO AND APPROVED BY
 THE ZONING DIVISION PRIOR TO PERMITTING.
  
 5. IF RECONFIGURATION OF THE PLANTER AREAS IN FRONT OF
 THE BUILDING REQUIRES RELOCATION, REMOVAL, AND/OR
 REPLACEMENT OF TREE(S), THEN A TREE ALTERATION PERMIT
 SHALL BE OBTAINED.
  
 6. REFERENCES TO ZLDR CODE SECTIONS CAN BE ACCESSED
 THROUGH THE FOLLOWING LINK: HTTPS://WWW.MUNICODE.COM/LI
 BRARY/#!/FL/WEST_PALM_BEACH/CODES/CODE_OF_ORDINANCES
  
 7. PURSUANT TO THE ART IN PUBLIC PLACES REGULATIONS
 (CODE OF ORDINANCES, CHAPTER 78, ARTICLE V) AN ART
 ASSESSMENT IS REQUIRED WHEN THE VERTICAL CONSTRUCTION
 VALUE OF ALL NEW PRIVATE DEVELOPMENT, NEW CONSTRUCTION,
 RENOVATION OR REMODELING IS EQUAL TO OR EXCEEDS
 $500,000. PLEASE COMPLETE AN ART IN PUBLIC PLACES FORM
 AND SUBMIT TO CONSTRUCTION SERVICES. THE FORM IS
 AVAILABLE THROUGH CONSTRUCTION SERVICES OR BY
 CONTACTING ME.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  