Plan Review Details - Permit 15030511
Plan Review Stops For Permit 15030511
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2015-06-01 Cont ID  
Sent By rmcdouga Date 2015-06-01 Time 11:15 Rev Time 0.00
Received By rmcdouga Date 2015-06-01 Time 11:15 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2015-05-20 Cont ID  
Sent By rmcdouga Date 2015-05-20 Time 18:00 Rev Time 0.00
Received By rmcdouga Date 2015-05-20 Time 18:00 Sent To  
Notes
2015-05-20 17:55:18PLAN
 REVIEW COMMENTS
  
 3RD REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE STORM PANEL INSTALLATION SCHEDULE IS NOT
 CORRECT. AND THERE IS NO KEY PLAN. R301.2.1.2
  
 2) THERE IS NO EXTERIOR DOOR PRODUCT APPROVAL. FBC
 107.3.4

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-04-21 Cont ID  
Sent By rmcdouga Date 2015-04-21 Time 11:50 Rev Time 0.00
Received By rmcdouga Date 2015-04-21 Time 09:59 Sent To Z
Notes
2015-04-21 10:35:52PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) (REPEAT COMMENT) FBC 107.3.4 - PROVIDE TWO SETS OF
 PRODUCT APPROVALS FOR THOSE PRODUCTS WHICH ARE
 REGULATED BY DCA RULE 9N-3 THAT HAVE BEEN REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD. PROVIDE
 TWO COMPLETE PRODUCT APPROVALS WITH FL OR NOA NUMBERS
 INCLUDING INSTALLATION INSTRUCTIONS AND MAXIMUM DESIGN
 PRESSURES FOR EACH OF THE DIFFERENT WINDOW/GLASS TYPES,
 STRUCTURAL MULLIONS AND EXTERIOR DOOR TYPES.
 (NEW COMMENT.) THE EXISTING / DEMOLITION PLAN HAS NOTES
 AT THE EXTERIOR FRONT DOOR, KITCHEN AND BEDROOM WINDOWS
 ARE TO BE REMOVED. THE DOOR SCHEDULE LISTS THIS DOOR
 AND THE NEW WINDOW SCHEDULE LISTS THESE WINDOWS AS
 EXISTING. ARE THESE BEING REPLACED WITH NEW ONES?
 CLARIFY. IF THE DOOR IS TO BE REPLACED WITH A NEW ONE,
 THEN SUBMIT 2 SETS OF PRODUCT APPROVALS THAT HEV BEEN
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD.
  
 2) (REPEAT COMMENT) R301.2.1.2 PROTECTION OF OPENINGS.
 WINDOWS IN BUILDINGS LOCATED IN WINDBORNE DEBRIS
 REGIONS SHALL HAVE GLAZED OPENINGS PROTECTED FROM
 WINDBORNE DEBRIS. GLAZED OPENING PROTECTION FOR
 WINDBORNE DEBRIS SHALL MEET THE REQUIREMENTS OF THE
 LARGE MISSILE TEST OF ASTM E 1996, ASTM E 1886, SSTD 12
 OR TAS 201, 202 AND 203 OR AAMA 506 REFERENCED THEREIN.
 IF STORM PANELS ARE USED SUBMIT TWO SETS OF PRODUCT
 APPROVALS, KEY PLAN AND INSTALLATION SCHEDULE.
 (NEW COMMENT.)THE STORM PANEL INFORMATION THAT WAS
 SUBMITTED DOES NOT HAVE A FLORIDA FL # OR MIAMI-DADE
 NOA NO. WITH IT. IT ALSO HAS NOT BEEN REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD. THERE
 WERE NO KEY PLANS OR INSTALLION SCHEDULES SUBMITTED.
  
 3) NEW COMMENT. THE DESIGNER OF RECORD (ENGINEER)
 SHOULD NOT BE SIGNING AND SEALING THE PRODUCT APPROVALS
 AS THEY ARE NOT HIS DESIGNS. HE SHOULD USE HIS SHOP
 REVIEW STAMP AND SIGNATURE TO SHOW THAT HE HAS REVIEWED
 AND APPROVED IT.
  
 IN ORDER TO REDUCE PLAN REVIEW TIMES AND PROVIDE
 CLARIFICATION, PLEASE SUBMIT A RESPONSE LETTER
 INDICATING HOW EACH OF THE REVIEW COMMENTS HAS BEEN
 ADDRESSED.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-04-09 Cont ID  
Sent By rmcdouga Date 2015-04-09 Time 10:26 Rev Time 0.00
Received By rmcdouga Date 2015-04-09 Time 10:26 Sent To  
Notes
2015-04-09 10:50:14PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. PROVIDE TWO COMPLETE PRODUCT
 APPROVALS WITH FL OR NOA NUMBERS INCLUDING INSTALLATION
 INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES FOR EACH OF
 THE DIFFERENT WINDOW/GLASS TYPES, STRUCTURAL MULLIONS
 AND EXTERIOR DOOR TYPES.
  
 2) R301.2.1.2 PROTECTION OF OPENINGS. WINDOWS IN
 BUILDINGS LOCATED IN WINDBORNE DEBRIS REGIONS SHALL
 HAVE GLAZED OPENINGS PROTECTED FROM WINDBORNE DEBRIS.
 GLAZED OPENING PROTECTION FOR WINDBORNE DEBRIS SHALL
 MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST OF ASTM
 E 1996, ASTM E 1886, SSTD 12 OR TAS 201, 202 AND 203 OR
 AAMA 506 REFERENCED THEREIN. IF STORM PANELS ARE USED
 SUBMIT TWO SETS OF PRODUCT APPROVALS, KEY PLAN AND
 INSTALLATION SCHEDULE.
  
 IN ORDER TO REDUCE PLAN REVIEW TIMES AND PROVIDE
 CLARIFICATION, PLEASE SUBMIT A RESPONSE LETTER
 INDICATING HOW EACH OF THE REVIEW COMMENTS HAS BEEN
 ADDRESSED.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-04-09 Cont ID  
Sent By rmcdouga Date 2015-04-09 Time 10:25 Rev Time 0.00
Received By rmcdouga Date 2015-04-09 Time 10:25 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2015-04-22 Cont ID  
Sent By fmittner Date 2015-04-22 Time 15:42 Rev Time 0.00
Received By fmittner Date 2015-04-22 Time 15:42 Sent To  
Notes
2015-04-22 15:43:16CONFIRMED WITH CONTRACTOR WINDOWS WILL BE WHITE FRAMES,
 CLEAR/LOW-E GLASS, NO GRIDS.

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2015-04-07 Cont ID  
Sent By fmittner Date 2015-04-07 Time 13:19 Rev Time 0.00
Received By fmittner Date 2015-03-31 Time 15:29 Sent To  
Notes
2015-04-07 13:21:11NEED PRODUCT APPROVALS FOR WINDOWS...FRAME COLOR? GLASS
 COLOR? MATERIAL? QUESTIONS CONTACT FRIEDERIKE MITTNER,
 CITY HISTORIC PRESERVATION PLANNER AT 822-1457

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2015-06-01 Cont ID  
Sent By rmcdouga Date 2015-06-01 Time 11:15 Rev Time 0.00
Received By rmcdouga Date 2015-05-22 Time 17:23 Sent To  
Notes
2015-05-22 17:24:19SENT TO R MCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-05-20 Cont ID  
Sent By rmcdouga Date 2015-05-20 Time 18:01 Rev Time 0.00
Received By rmcdouga Date 2015-05-13 Time   Sent To  
Notes
2015-05-13 18:26:22SENT TO R MCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-04-26 Cont ID  
Sent By skennedy Date 2015-04-26 Time 11:14 Rev Time 0.00
Received By skennedy Date 2015-04-13 Time 09:37 Sent To  
Notes
2015-04-21 11:59:09SENT TO ZONING FOR HISTORIC REVIEW.
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
2015-04-17 09:38:29R20
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-04-09 Cont ID  
Sent By rmcdouga Date 2015-04-09 Time 10:26 Rev Time 0.00
Received By rmcdouga Date 2015-03-12 Time 15:02 Sent To  
Notes
2015-03-13 10:23:03R22
  
2015-03-12 15:03:23HISTORIC WILL REVIEW PER SANDY. LWL

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-04-09 Cont ID  
Sent By rmcdouga Date 2015-04-09 Time 10:25 Rev Time 0.00
Received By rmcdouga Date 2015-04-09 Time 10:25 Sent To  
Notes
***NONE***