2015-03-27 07:39:21 | 3/27/2015 |
| PROJECT: VELERO / CIRCLE K SIGNAGE |
| PERMIT#: 15030455 |
| CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| 1ST ELECTRICAL PLAN REVIEW |
| ACTION: DENIED |
| |
| PLEASE REVISE YOUR DESIGN DOCUMENTS TO ADDRESS THE |
| FOLLOWING ELECTRICAL REVIEW COMMENTS: |
| |
| 1) NEC 600.3 LISTING. |
| ELECTRIC SIGNS, SECTION SIGNS, AND OUTLINE LIGHTING, |
| FIXED, MOBILE, OR PORTABLE SHALL BE LISTED AND |
| INSTALLED IN CONFORMANCE WITH THAT LISTING, UNLESS |
| OTHERWISE APPROVED BY SPECIAL PERMISSION. 600.3 |
| LISTING. |
| |
| 2) NEC 600.6(A)(1) |
| EACH SIGN AND OUTLINE LIGHTING SYSTEM, OR FEEDER |
| CIRCUIT OR BRANCH CIRCUIT SUPPLYING A SIGN OR OUT-LINE |
| LIGHTING SYSTEM, SHALL BE CONTROLLED BY AN EXTERNALLY |
| OPERABLE SWITCH OR CIRCUIT BREAKER THAT WILL OPEN ALL |
| UNGROUNDED CONDUCTORS WITHIN SIGHT OF THE SIGN NEC |
| 600.6(A)(1) |
| |
| 3) FBC-ENERGY 505.2.4 |
| ALL EXTERIOR LIGHTING NOT EXEMPTED BY FBC 505.1 SHALL |
| HAVE AUTOMATIC CONTROLS TO TURN OFF AT DAYLIGHT OR WHEN |
| NOT REQUIRED. CONTROLS SHALL BE PHOTOSENSOR & TIME |
| CLOCK OR ASTRONOMICAL TIME SWITCH. ALL TIME SWITCHES |
| SHALL BE CAPABLE OF RETAINING PROGRAMING DURING A LOSS |
| OF POWER FOR A MINIMUM OF 10 HOURS. FBC-E 505.2.4 |
| |
| 4) WPB AMENDMENTS TO FBC 109.3 |
| PROVIDE PROOF OF OVERALL VALUE OF THE PROJECT IS |
| REQUIRED AND SHALL BE THE TOTAL REPLACEMENT VALUE TO |
| INCLUDE ARCHITECTURAL DESIGN FEES, FABRICATION, |
| STRUCTURAL, AND ELECTRICAL, PLUS OVERHEAD AND PROFIT. |
| FINAL PERMIT VALUATION SHALL BE SET BY THE BUILDING |
| OFFICIAL. REVISE THE VALUE SUBMITTED OR SUBMIT |
| SUPPORTING DOCUMENTATION INCLUDING BREAKDOWN ON |
| CONTRACTS. WPB AMENDMENTS.TO FBC 109.3 |
| |
| 5) WPB AMENDMENTS TO FBC,107.2.1 |
| ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND |
| ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF |
| THE PERSON RESPONSIBLE FOR THE DESIGN. WPB AMENDMENTS |
| TO FBC,107.2.1, FL SS 471, 668.001-668.006 |
| |
| 6) WPB AMENDMENTS TO FBC 107.3.2 |
| CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| OFFICIAL. |
| |
| 7) WPB AMENDMENTS FBC 107.2.1 |
| THE CONSTRUCTION DOCUMENTS SUBMITTED WITH THE |
| APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY A SITE |
| PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF NEW |
| CONSTRUCTION. WPB AMENDMENTS FBC 107.2.1 |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| |
| ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| REVIEW. |
| |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| 561-805-6717 OR [email protected] |
| |