Plan Review Details - Permit 15030443
Plan Review Stops For Permit 15030443
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-05-13 Cont ID  
Sent By aclange Date 2015-05-13 Time 16:17 Rev Time 0.00
Received By aclange Date 2015-05-13 Time 16:17 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-04-06 Cont ID  
Sent By tklarge Date 2015-04-07 Time 05:04 Rev Time 0.00
Received By shill Date 2015-04-06 Time 10:15 Sent To E
Notes
2015-04-06 10:18:31****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. THIS PROJECT INCLUDES PLUMBING AND ELECTRICAL WORK.
 SUBMIT A PLAN WHICH INCLUDES ENTIRE SCOPE OF WORK.
 PLUMBING AND ELECTRICAL WILL BE SUB CONTRACTORS TO THIS
 PERMIT. INCREASE VALUE TO INCLUDE THE SUBCONTRACTORS,
 FBC 109.
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-05-02 Cont ID  
Sent By shill Date 2015-05-02 Time 12:17 Rev Time 0.00
Received By dhayes Date 2015-05-02 Time 12:17 Sent To B
Notes
2015-05-02 12:26:104/6/2015
 PROJECT: KITCHEN RENOVATION
 PERMIT#: 15030443
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN
 APPROVED PROVISIONALLY. FAILURE TO CORRECT THE LISTED
 DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED
 INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION
 FEE(S).
  
 1) ALL 125-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE
 RECEPTACLES INSTALLED IN THE LOCATIONS SPECIFIED IN (1)
 THROUGH (8) SHALL HAVE GROUND-FAULT CIRCUIT-INTERRUPTER
 PROTECTION FOR PERSONNEL. NEC 210.8(6) KITCHENS - WHERE
 THE RECEPTACLES ARE INSTALLED TO SERVE THE COUNTERTOP
 SURFACES.
  
 2) VERIFY OR INSTALL SMOKE DETECTORS WHERE REQUIRED IN
 THE FBC. WHEN ALTERATIONS, REPAIRS, OR ADDITIONS
 REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING
 ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE
 INDIVIDUAL DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE
 ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS.
 FBC-RESIDENTIAL 314 AND 315.
  
 3) ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER
 RESISTANT AND AFCI PROTECTED. NEC 210.12, 406.11
  
 4) VERIFY RECEPTACLE OUTLETS SHALL BE INSTALLED SO THAT
 NO POINT ALONG THE WALL LINE IS MORE THAN 600 MM (24
 IN.) MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET IN
 THAT SPACE.NEC 210.52(C)(1)
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-04-06 Cont ID  
Sent By tlarge Date 2015-04-06 Time 12:30 Rev Time 0.00
Received By dhayes Date 2015-04-06 Time 12:30 Sent To P
Notes
2015-04-06 13:09:564/6/2015
 PROJECT: KITCHEN RENOVATION
 PERMIT#: 15030443
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) PROVIDE ELECTRICAL PLANS THAT INDICATE THE COMPLETE
 SCOPE OF WORK. INCLUDE ANY ELECTRICAL CIRCUITRY OR
 DEVICES IN THE WALL TO BE PARTIALLY DEMOLISHED AS WELL
 ALL ELECTRICAL CIRCUITRY IN THE KITCHEN EITHER EXISTING
 OR PROPOSED TO BE INSTALLED. IDENTIFY ON THE PLANS WHAT
 IS EXISTING TO REMAIN AND WHAT IS PROPOSD.
 A) PROVIDE A PANEL SCHEDULE AND A LOAD CALCULATION TO
 IDENTIFY ALL NEW LOADS OR CIRCUITRY PROPOSED.
  
 2) VERIFY OR INSTALL SMOKE DETECTORS WHERE REQUIRED IN
 THE FBC. WHEN ALTERATIONS, REPAIRS, OR ADDITIONS
 REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING
 ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE
 INDIVIDUAL DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE
 ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS.
 FBC-RESIDENTIAL 314 AND 315.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-05-13 Cont ID  
Sent By aclange Date 2015-05-13 Time 16:20 Rev Time 0.00
Received By aclange Date 2015-04-28 Time 12:35 Sent To  
Notes
2015-04-28 12:36:09RE-SUBMITTAL SENT TO TIM LARGE FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-04-07 Cont ID  
Sent By misc1 Date 2015-04-07 Time 05:04 Rev Time 0.00
Received By tklarge Date 2015-03-12 Time 08:14 Sent To B
Notes
2015-04-06 10:19:02TO ELEC
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-05-02 Cont ID  
Sent By tklarge Date 2015-05-02 Time 10:00 Rev Time 0.00
Received By tklarge Date 2015-05-02 Time 09:48 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-04-07 Cont ID  
Sent By tklarge Date 2015-04-07 Time 05:03 Rev Time 0.00
Received By tklarge Date 2015-04-07 Time 04:54 Sent To  
Notes
2015-04-07 05:01:051) SUBMIT A SET OF PLANS THAT SHOWS THE ENTIRE SCOPE OF
 PLUMBING WORK TO BE DONE. WPB AMEND. TO 2010 FBC SEC.
 107.2.1.
 2) INDICATE ON PLANS IF THE PLUMBING FIXTURES BEING
 REPLACED ARE GOING BACK INTO THE SAME LOCATION.
 3) IF THERE IS ANY WORK TO BE DONE ON THE WATER PIPING,
 WATER-HAMMER ARRESTORS SHALL BE INSTALLED WHERE QUICK
 CLOSING VALVES ARE UTILIZED ( ICE MAKER/WATER DISPENSER
 FROM REFRIGERATOR OR DISHWASHER).
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  