Plan Review Details - Permit 15030431
Plan Review Stops For Permit 15030431
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2015-08-28 Cont ID  
Sent By rmcdouga Date 2015-08-28 Time 14:32 Rev Time 0.00
Received By rmcdouga Date 2015-08-28 Time 11:16 Sent To  
Notes
2015-08-28 14:28:18APPROVED WITH EXCEPTION. THIS PLAN HAS BEEN APPROVED
 PROVISIONALLY. FAILURE TO CORRECT THE LISTED
 DEFICIENCIES IN THIS PLAN PRIOR TO INSPECTION WILL
 RESULT IN FAILED INSPECTION(S) AND ASSESSMENT OF
 RE-INSPECTION FEE(S).
 1) FBC - R 301.2.1.2 SUBMIT TWO COPIES OF INSTALLATION
 SCHEDULES AND KEY PLANS FOR THE STORM PANELS. SPECIFY
 THE OPENING SIZE, THE WIND PRESSURES, TYPE OF ANCHOR,
 ANCHOR SPACING, EDGE DISTANCE, PANEL LENGTH, PANEL
 SPAN, SEPARATION DISTANCE FROM PANEL TO GLASS AND THE
 APPLICABLE SECTION NUMBER FROM THE INSTALLATION
 DRAWINGS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2015-08-19 Cont ID  
Sent By rmcdouga Date 2015-08-19 Time 15:49 Rev Time 0.00
Received By rmcdouga Date 2015-08-19 Time 15:49 Sent To  
Notes
2015-08-19 16:01:47PLAN REVIEW COMMENTS
 5TH REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 PREVIOUS COMMENTS HAVE NOT BEEN ADDRESSED. SEE COMMENTS
 BELOW.
  
 DENIED BY BUILDING - ( NOTE: THE PERMIT APPLICATION IS
 MISSING FROM THE CONSTRUCTION DOCUMENTS. A NEW
 REPLACEMENT APPLICATION IS REQUIRED. )
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) REPEAT COMMENT. THE PLANS SPECIFY NEW IMPACT RATED
 DOORS AND WINDOWS. FBC 107.3.4 - PROVIDE TWO SETS OF
 PRODUCT APPROVALS FOR THOSE PRODUCTS WHICH ARE
 REGULATED BY DCA RULE 9N-3 THAT HAVE BEEN REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD. PROVIDE
 TWO COMPLETE PRODUCT APPROVALS WITH FL OR NOA NUMBERS
 INCLUDING INSTALLATION INSTRUCTIONS AND MAXIMUM DESIGN
 PRESSURES FOR EACH OF THE WINDOW AND EXTERIOR DOOR
 TYPES. ONLY ONE SET OF PRODUCT APPROVALS WAS SUBMITTED
 FOR THE SINGLE HUNG WINDOWS (NOA NO. 14-0722.07).
  
 2) REPEAT COMMENT. FBC - R 301.2.1.2 SUBMIT TWO COPIES
 OF AN INSTALLATION SCHEDULE AND KEY PLAN FOR THE STORM
 PANELS. SPECIFY THE OPENING SIZE, THE WIND PRESSURES,
 TYPE OF ANCHOR, ANCHOR SPACING, EDGE DISTANCE, PANEL
 LENGTH, PANEL SPAN, SEPARATION DISTANCE FROM PANEL TO
 GLASS AND THE APPLICABLE SECTION NUMBER FROM THE
 INSTALLATION DRAWINGS. I HAVE INCLUDED A LINK TO THE
 CONSTRUCTION SERVICES DEPARTMENT SITE THAT HAS MANY OF
 THE RELATED FORMS INCLUDING
 THE SCHEDULE FOR INSTALLATION OF OPENING PROTECTIVE
 DEVICES.
 HTTP://WPB.ORG/DEVELOPMENT/FORMS-AND-PUBLICATIONS/
  
 3) THE REVISED PLANS AND THE RESPONSE LETTER INDICATE
 THAT THE FRONT DOOR IS TO BE LARGE MISSILE IMPACT RATED
 TO ALLOW FOR EGRESS WHEN THE STORM PANELS ARE IN PLACE
 DURING THE THREAT OF A STORM PER FBC - R310.4. SUBMIT
 TWO SETS OF PRODUCT APPROVALS FOR THE 3' 0" X 6' 8"
 IMPACT RATED FRONT DOOR THAT HAVE BEEN REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD. PROVIDE
 TWO COMPLETE PRODUCT APPROVALS WITH FL OR NOA NUMBERS
 INCLUDING INSTALLATION INSTRUCTIONS AND MAXIMUM DESIGN
 PRESSURES. FBC 107.3.4
  
 4) ONE SET OF PRODUCT APPROVALS WERE PREVIOUSLY
 SUBMITTED FOR EACH OF THE FOLLOWING NON-IMPACT RATED
 DOORS FL#16106 AND A JELD-WEN CONTOURS PREMIUM STEEL
 WOOD EDGE HALF LITE OUTSWING DOOR WITH NO FL# INDICATED
 ON THE DOCUMENTS. TWO SETS OF PRODUCT APPROVALS WERE
 SUBMITTED FOR NON-IMPACT RATED DOORS (FL#15255.13) WITH
 THE LAST RESUBMITTAL. PLEASE CLARIFY WHICH OF THESE
 WILL BE INSTALLED. AN ADDITIONAL SET OF PRODUCT
 APPROVALS THAT HAVE BEEN REVIEWED BY THE DESIGNER OF
 RECORD WILL BE REQUIRED IF YOU WISH TO USE THE FIRST
 TWO MENTIONED AND A COVER SHEET WITH THE FL# IS
 REQUIRED FOR THE HALF LITE DOOR. FBC 107.2.1
  
 5) THE PERMIT APPLICATION IS MISSING FROM THE
 CONSTRUCTION DOCUMENTS. A NEW REPLACEMENT APPLICATION
 IS REQUIRED.
  
 6) IN ORDER TO REDUCE PLAN REVIEW TIMES AND PROVIDE
 CLARIFICATION, PLEASE SUBMIT A RESPONSE LETTER
 INDICATING HOW EACH OF THE REVIEW COMMENTS HAS BEEN
 ADDRESSED.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2015-07-29 Cont ID  
Sent By rmcdouga Date 2015-07-29 Time 18:01 Rev Time 0.00
Received By rmcdouga Date 2015-07-29 Time 14:39 Sent To  
Notes
2015-07-29 16:56:38PLAN REVIEW COMMENTS
 4TH REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING - ( NOTE: THE PERMIT APPLICATION IS
 MISSING FROM THE CONSTRUCTION DOCUMENTS. A NEW
 REPLACEMENT APPLICATION IS REQUIRED. )
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) REPEAT COMMENT. THE PLANS SPECIFY NEW IMPACT RATED
 DOORS AND WINDOWS. FBC 107.3.4 - PROVIDE TWO SETS OF
 PRODUCT APPROVALS FOR THOSE PRODUCTS WHICH ARE
 REGULATED BY DCA RULE 9N-3 THAT HAVE BEEN REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD. PROVIDE
 TWO COMPLETE PRODUCT APPROVALS WITH FL OR NOA NUMBERS
 INCLUDING INSTALLATION INSTRUCTIONS AND MAXIMUM DESIGN
 PRESSURES FOR EACH OF THE WINDOW AND EXTERIOR DOOR
 TYPES. ONLY ONE SET OF PRODUCT APPROVALS WAS SUBMITTED
 FOR THE SINGLE HUNG WINDOWS (NOA NO. 14-0722.07).
  
 2) REPEAT COMMENT. FBC - R 301.2.1.2 SUBMIT TWO COPIES
 OF AN INSTALLATION SCHEDULE AND KEY PLAN FOR THE STORM
 PANELS. SPECIFY THE OPENING SIZE, THE WIND PRESSURES,
 TYPE OF ANCHOR, ANCHOR SPACING, EDGE DISTANCE, PANEL
 LENGTH, PANEL SPAN, SEPARATION DISTANCE FROM PANEL TO
 GLASS AND THE APPLICABLE SECTION NUMBER FROM THE
 INSTALLATION DRAWINGS. I HAVE INCLUDED A LINK TO THE
 CONSTRUCTION SERVICES DEPARTMENT SITE THAT HAS MANY OF
 THE RELATED FORMS INCLUDING
 THE SCHEDULE FOR INSTALLATION OF OPENING PROTECTIVE
 DEVICES.
 HTTP://WPB.ORG/DEVELOPMENT/FORMS-AND-PUBLICATIONS/
  
 3) THE REVISED PLANS AND THE RESPONSE LETTER INDICATE
 THAT THE FRONT DOOR IS TO BE LARGE MISSILE IMPACT RATED
 TO ALLOW FOR EGRESS WHEN THE STORM PANELS ARE IN PLACE
 DURING THE THREAT OF A STORM PER FBC - R310.4. SUBMIT
 TWO SETS OF PRODUCT APPROVALS FOR THE 3' 0" X 6' 8"
 IMPACT RATED FRONT DOOR THAT HAVE BEEN REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD. PROVIDE
 TWO COMPLETE PRODUCT APPROVALS WITH FL OR NOA NUMBERS
 INCLUDING INSTALLATION INSTRUCTIONS AND MAXIMUM DESIGN
 PRESSURES. FBC 107.3.4
  
 4) ONE SET OF PRODUCT APPROVALS WERE PREVIOUSLY
 SUBMITTED FOR EACH OF THE FOLLOWING NON-IMPACT RATED
 DOORS FL#16106 AND A JELD-WEN CONTOURS PREMIUM STEEL
 WOOD EDGE HALF LITE OUTSWING DOOR WITH NO FL# INDICATED
 ON THE DOCUMENTS. TWO SETS OF PRODUCT APPROVALS WERE
 SUBMITTED FOR NON-IMPACT RATED DOORS (FL#15255.13) WITH
 THE LAST RESUBMITTAL. PLEASE CLARIFY WHICH OF THESE
 WILL BE INSTALLED. AN ADDITIONAL SET OF PRODUCT
 APPROVALS THAT HAVE BEEN REVIEWED BY THE DESIGNER OF
 RECORD WILL BE REQUIRED IF YOU WISH TO USE THE FIRST
 TWO MENTIONED AND A COVER SHEET WITH THE FL# IS
 REQUIRED FOR THE HALF LITE DOOR. FBC 107.2.1
  
 5) THE PERMIT APPLICATION IS MISSING FROM THE
 CONSTRUCTION DOCUMENTS. A NEW REPLACEMENT APPLICATION
 IS REQUIRED.
  
 6) IN ORDER TO REDUCE PLAN REVIEW TIMES AND PROVIDE
 CLARIFICATION, PLEASE SUBMIT A RESPONSE LETTER
 INDICATING HOW EACH OF THE REVIEW COMMENTS HAS BEEN
 ADDRESSED.
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2015-07-07 Cont ID  
Sent By rmcdouga Date 2015-07-07 Time 08:20 Rev Time 0.00
Received By rmcdouga Date 2015-07-07 Time 08:20 Sent To  
Notes
2015-07-06 19:27:53PLAN REVIEW COMMENTS
 3RD REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING - ( NOTE: THE PERMIT APPLICATION IS
 MISSING FROM THE CONSTRUCTION DOCUMENTS. A NEW
 REPLACEMENT APPLICATION IS REQUIRED. )
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) REPEAT COMMENT. THE PLANS SPECIFY NEW IMPACT RATED
 DOORS AND WINDOWS. FBC 107.3.4 - PROVIDE TWO SETS OF
 PRODUCT APPROVALS FOR THOSE PRODUCTS WHICH ARE
 REGULATED BY DCA RULE 9N-3 THAT HAVE BEEN REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD. PROVIDE
 TWO COMPLETE PRODUCT APPROVALS WITH FL OR NOA NUMBERS
 INCLUDING INSTALLATION INSTRUCTIONS AND MAXIMUM DESIGN
 PRESSURES FOR EACH OF THE WINDOW AND EXTERIOR DOOR
 TYPES. ONLY ONE SET OF PRODUCT APPROVALS WAS SUBMITTED
 AND TWO SETS ARE REQUIRED.
  
 2)THE PRODUCT APPROVALS THAT WERE SUBMITTED ARE FOR
 NON-IMPACT RATED WINDOWS AND GLAZED EXTERIOR DOORS.
 SUBMIT PRODUCT APPROVALS FOR THE REQUIRED IMPACT
 PROTECTION DEVICES. FBC-R301.2.1.2
  
 3) SUBMIT TWO COPIES OF A KEY PLAN AND INSTALLATION
 SCHEDULE FOR THE STORM PANELS. FBC 107.2.1 &
 FBC-R301.2.1
  
 4) FBC-R310.4 REQUIRES AT LEAST ONE MEANS OF ESCAPE TO
 BE PROVIDED WHILE STORM PANELS ARE IN PLACE DURING THE
 THREAT OF A STORM. OCCUPANTS IN ANY PART OF THE
 DWELLING SHALL BE ABLE TO ACCESS THE MEANS OF ESCAPE
 WITHOUT PASSING THROUGH A LOCKABLE DOOR NOT UNDER THEIR
 CONTROL. SHOW COMPLIANCE.
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-05-26 Cont ID  
Sent By rmcdouga Date 2015-05-26 Time 10:37 Rev Time 0.00
Received By rmcdouga Date 2015-05-26 Time 08:02 Sent To  
Notes
2015-05-26 10:17:31PLAN REVIEW COMMENTS
  
 2ND REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING - ( NOTE: THE PERMIT APPLICATION AND
 OLD PLANS ARE MISSING FROM THIS RESUBMITTAL. )
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) NEW COMMENT. BASED ON YOUR RESPOSE TO THE PREVIOUS
 COMMENT, YOU INTEND TO BRING THE ILLEGALLY ENCLOSED
 PORCHES INTO CODE COMPLIANCE. SUBMIT TWO COPIES OF
 ENERGY CALCULATIONS TO SHOW THAT THE ENCLOSED PORCHES
 COMPLY WITH THE 2010 FBC ENERGY CONSERVATION AND SEE
 THE IMPACT FEE REVIEW STOP.
  
 2) REPEAT COMMENT. THE VALUE OF $7500.00 SPECIFIED ON
 THE APPLICATION IS LOW FOR THE WORK SHOWN ON THE PLANS.
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 3) REPEAT COMMENT. THE PLANS SPECIFY NEW IMPACT DOORS
 AND WINDOWS. FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT
 APPROVALS FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3 THAT HAVE BEEN REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD. PROVIDE TWO COMPLETE
 PRODUCT APPROVALS WITH FL OR NOA NUMBERS INCLUDING
 INSTALLATION INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES
 FOR EACH OF THE DIFFERENT ROOFING MATERIALS,
 WINDOW/GLASS TYPES, STRUCTURAL MULLIONS AND EXTERIOR
 DOOR TYPES.
 NEW COMMENT. THE PRODUCT APPROVALS THAT WERE SUBMITTED
 ARE FOR NON-IMPACT RATED WINDOWS AND GLAZED EXTERIOR
 DOORS. IF YOU WILL BE INSTALLING NON-IMPACT WINDOWS AND
 DOORS, REVISE THE PLAN NOTES AND SUBMIT PRODUCT
 APPROVALS FOR THE REQUIRED IMPACT PROTECTION
  
 4) REPEAT COMMENT. SHOW COMPLIANCE WITH FBC R311.7.7
 AND R312 FOR GUARDS AND HANDRAILS ON THE DECK STAIRS.
 NEW COMMENT.THE PLAN SPECIFIES THAT THE STAIRS HAVE 6
 RISERS. FBC-R311.7.7 REQUIRES HANDRAILS NOT LESS THAN
 34 INCHES OR MORE THAN 38 INCHES ON AT LEAST ONE SIDE
 OF A FLIGHT OF STAIRS WITH FOUR OR MORE RISERS.
  
 5) REPEAT COMMENT. SHOW COMPLIANCE WITH FBC-R314.3.1
 WHEN ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS.
 NEW COMMENT. IN ADDITION TO THE SMOKE ALARMS REQUIRED
 IN EACH SLEEPING ROOM, THEY ARE REQUIRED OUTSIDE EACH
 SLEEPING AREA IN THE IMMEDIATE VICINITY OF THE
 BEDROOMS.
  
 6) NEW COMMENT. THE TYPICAL EXTERIOR WALL SECTION ON
 SHEET 5 SPECIFIES 6" BATT INSULATION WITH AN R-30 MIN.
 INSULATION VALUE. THERE ARE NOT ANY 6 INCH THICK BATT
 INSULATIONS THAT CAN PROVIDE A R-30 THERMAL RESISTANCE.
 DEPENDING ON THE INSULATING MATERIAL USED, THE
 THICKNESS REQUIRED TO ACHIEVE R-30 VARIES. YOU CAN
 REVISE NOTE TO SAY MINIMUM R-30 BATT INSULATION. FBC
 107.2.1
  
 7) IN ORDER TO REDUCE PLAN REVIEW TIMES AND PROVIDE
 CLARIFICATION, PLEASE SUBMIT A RESPONSE LETTER
 INDICATING HOW EACH OF THE REVIEW COMMENTS HAS BEEN
 ADDRESSED.
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-04-13 Cont ID  
Sent By rmcdouga Date 2015-04-13 Time 13:09 Rev Time 0.00
Received By rmcdouga Date 2015-04-13 Time 10:09 Sent To  
Notes
2015-04-10 11:25:10PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) ACCORDING TO THE PALM BEACH COUNTY PROPERTY
 APPRAISER THE MASTER BEDROOM, BATHROOM NO. 1 AND FOYER
 ARE EITHER ENCLOSED OR OPEN PORCHES AND NOT CONSIDERED
 HABITABLE SPACE. YOU WILL NEED TO SUBMIT DOCUMENTATION
 TO SHOW THAT THE PORCHES WERE LEGALLY CONVERTED WITH
 THE PROPER PERMITS AND INSPECTIONS. OTHERWISE, YOU WILL
 HAVE TWO OPTIONS EITHER CONVERT THE AREAS BACK TO
 PORCHES OR BRING THEM INTO COMPLIANCE WITH THE 2010
 FLORIDA BUILDING CODE AND 2008 NATIONAL ELECTRICAL
 CODE. UNDER THE 2010 FBC EXISTING BUILDING THIS IS
 CONSIDERED A CHANGE OF OCCUPANCY WITHOUT A CHANGE OF
 OCCUPANCY CLASSIFICATION. IN ORDER FOR THESE AREAS TO
 BE BROUGHT INTO COMPLIANCE, THEY WILL BE REQUIRED TO
 COMPLY WITH CHAPTER 9 OF THE 2010 FBC EXISTING
 BUILDING. THE FOLLOWING ITEMS WILL BE REQUIRED TO BE
 MADE CODE COMPLIANT. THE STRUCTURE IN THESE AREAS ARE
 REQUIRED TO MEET THE WINDLOAD REQUIREMENTS FOR THE
 BUILDING ENVELOPE ( IN ADDITION TO GRAVITY LOADS),
 PRODUCT APPROVALS FOR EXTERIOR DOORS AND WINDOWS,
 EGRESS REQUIREMENTS, LIGHT AND VENTILATION, SMOKE AND
 CARBON MONOXIDE ALARMS, FIRE SEPARATION REQUIREMENTS (
 SEPARATION DISTANCE AND ALLOWABLE OPENINGS), THE
 REQUIREMENTS OF THE 2010 FBC ENERGY CONSERVATION, 2010
 FBCR MECHANICAL, THE REQUIREMENTS OF THE 2010 FBCR
 PLUMBING AND THE ELECTRICAL SYSTEM IS REQUIRED TO
 COMPLY WITH THE 2008 NATIONAL ELECTRIC CODE. THE PLANS
 ARE REQUIRED TO BE REVIEWED BY PLAM BEACH COUNTY TO
 DETERMINE IF IMPACT FEES ARE DUE. SPECIFY THE SQUARE
 FOOTAGE OT THE EXISTING CONDITIONED SPACE AND THE
 UNCONDITIONED SPACE (ILLEGALLY CONVERTED) ON THE PLANS.
  
 2) THE VALUE OF $7500.00 SPECIFIED ON THE APPLICATION
 IS LOW FOR THE WORK SHOWN ON THE PLANS. FBC 109.3
 BUILDING PERMIT VALUATION. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRIC,
 PLUMBING, MECHANICAL, INTERIOR FINISH, RELATIVE SITE
 WORK, ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 3) THE PLANS HAVE AN ENGINEER'S TITLE BLOCK AND ARE
 REQUIRED BY FS 471 & FAC 61G15 TO HAVE HIS SEAL AND
 HANDWRITTEN SIGNATURE ON THEM.
  
 4) THE PLANS SPECIFY NEW IMPACT DOORS AND WINDOWS. FBC
 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS FOR
 THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. PROVIDE TWO COMPLETE PRODUCT
 APPROVALS WITH FL OR NOA NUMBERS INCLUDING INSTALLATION
 INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES FOR EACH OF
 THE DIFFERENT ROOFING MATERIALS, WINDOW/GLASS TYPES,
 STRUCTURAL MULLIONS AND EXTERIOR DOOR TYPES.
  
 5) SPECIFY THE TYPES AND SIZES OF THE WINDOWS THAT WILL
 BE REPLACED. EXISTING BEDROOM EMERGENCY ESCAPE AND
 RESCUE WINDOWS ARE REQUIRED TO COMPLY WITH FBC EXISTING
 BUILDING 604.1 MEANS OF EGRESS FOR BUILDINGS UNDERGOING
 ALTERATION SHALL COMPLY WITH THE REQUIREMENTS OF
 SECTION 601.1 AND THE SCOPING PROVISIONS OF CHAPTER 1
 WHERE APPLICABLE. EXCEPTION: DOOR AND WINDOW
 DIMENSIONS. IN RESIDENTIAL DWELLINGS AND DWELLING
 UNITS, A MAXIMUM OF 5 PERCENT REDUCTION IN THE CLEAR
 OPENING DIMENSIONS OF REPLACEMENT DOORS AND WINDOWS
 SHALL BE ALLOWED.
  
 6) THERE IS CONFLICTING INFORMATION ON SHEET 5. THE
 EXTERIOR WALL SECTION SPECIFIES A WOOD FRAME WALL ON A
 MONOLITHIC CONCRETE SLAB. THE DECK PLAN INDICATES THAT
 THE EXISTING EXTERIOR WALL IS CBS AND PROBABLY HAS A
 CRAWL SPACE SINCE THE DECK IS 3 FEET OFF THE GROUND.
 PLEASE CLARIFY. FBC 107.2.1
  
 7) SHOW COMPLIANCE WITH FBC R311.7.7 AND R312 FOR
 GUARDS AND HANDRAILS ON THE DECK STAIRS.
  
 8) SPECIFY THE CONNECTORS THAT WILL BE USED TO ATTACH
 THE 2 X 8 JOISTS TO THE 2 X 10 BEAMS AND 2 X 6 LEDGERS
 AND THE 2 X 10 BEAMS TO THE 2 X 6 LEDGERS TO PROVIDE A
 CONTINOUS LOAD PATH REQUIRED BY FBC-R 301.1 .
  
 9) SPECIFY THE REQUIRED LIVE LOADS FOR THE PORCH ON THE
 PROPOSED DECK ON THE PLANS. FBC-R301.5
  
 10) SHOW COMPLIANCE WITH FBC-R314.3.1 WHEN ALTERATIONS,
 REPAIRS OR ADDITIONS REQUIRING A PERMIT OCCUR, OR WHEN
 ONE OR MORE SLEEPING ROOMS ARE ADDED OR CREATED IN
 EXISTING DWELLINGS, THE INDIVIDUAL DWELLING UNIT SHALL
 BE EQUIPPED WITH SMOKE ALARMS LOCATED AS REQUIRED FOR
 NEW DWELLINGS.
  
 11) IN ORDER TO REDUCE PLAN REVIEW TIMES AND PROVIDE
 CLARIFICATION, PLEASE SUBMIT A RESPONSE LETTER
 INDICATING HOW EACH OF THE REVIEW COMMENTS HAS BEEN
 ADDRESSED.
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2015-07-06 Cont ID  
Sent By rmcdouga Date 2015-07-06 Time 17:26 Rev Time 0.00
Received By rmcdouga Date 2015-07-06 Time 17:26 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-05-26 Cont ID  
Sent By rmcdouga Date 2015-05-26 Time 07:31 Rev Time 0.00
Received By rmcdouga Date 2015-05-23 Time 12:26 Sent To  
Notes
2015-05-26 07:31:03PLAN REVIEW COMMENTS
  
 2ND REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY ELECTRICAL
 THE FOLLOWING COMMENTS FROM THE 1ST REVIEW WERE NOT
 ADDRESSED. PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) NEC 210.52 (C) (1) - A RECEPTACLE OUTLET SHALL BE
 INSTALLED AT EACH COUNTERTOP SPACE 12 INCHES OR WIDER
 SO THAT NO POINT ALONG THE WALL LINE IS MORE THAN 2
 FEET MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET IN
 THAT SPACE.
  
 2) NEC 210.8 (A)(6) RECEPTACLES SERVING COUNTERTOP
 SURFACES ARE REQUIRED TO BE GFCI PROTECTED.
  
 3) NEC 210.12 (B) - OUTLETS ARE REQUIRED TO BE AFCI
 PROTECTED.
  
 4) NEC 406.11 - TAMPER-RESISTANT RECEPTACLES ARE
 REQUIRED.
  
 5) NEC 440.11 & 440.14 SHOW THE LOCATION OF THE
 REQUIRED A/C EQUIPMENT DISCONNECTING MEANS ON THE
 PLANS.
  
 6) NEC 210.63 - PROVIDE A GFCI PROTECTED SERVICE OUTLET
 FOR WITHIN 25' OF MECHANICAL EQUIPMENT.
  
 7) THE CONDUIT AND WIRE SIZE FOR THE WEATHER HEAD SHOWN
 ON THE SERVICE RISER PLAN IS INCORRECT. NEC 310.15 (B)
 (6).
  
 8) FBC-R314.3.1 WHEN ALTERATIONS, REPAIRS OR ADDITIONS
 REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING
 ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE
 INDIVIDUAL DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE
 ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS.
 R314.3 LOCATION.
 SMOKE ALARMS SHALL BE INSTALLED IN THE FOLLOWING
 LOCATIONS:
 1. IN EACH SLEEPING ROOM.
 2. OUTSIDE EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE
 VICINITY OF THE BEDROOMS.
 3. ON EACH ADDITIONAL STORY OF THE DWELLING, INCLUDING
 BASEMENTS AND HABITABLE ATTICS BUT NOT INCLUDING CRAWL
 SPACES AND UNINHABITABLE ATTICS. IN DWELLINGS OR
 DWELLING UNITS WITH SPLIT LEVELS AND WITHOUT AN
 INTERVENING DOOR BETWEEN THE ADJACENT LEVELS, A SMOKE
 ALARM INSTALLED ON THE UPPER LEVEL SHALL SUFFICE FOR
 THE ADJACENT LOWER LEVEL PROVIDED THAT THE LOWER LEVEL
 IS LESS THAN ONE FULL STORY BELOW THE UPPER LEVEL.
 WHEN MORE THAN ONE SMOKE ALARM IS REQUIRED TO BE
 INSTALLED WITHIN AN INDIVIDUAL DWELLING UNIT THE ALARM
 DEVICES SHALL BE INTERCONNECTED IN SUCH A MANNER THAT
 THE ACTUATION OF ONE ALARM WILL ACTIVATE ALL OF THE
 ALARMS IN THE INDIVIDUAL UNIT.
  
 9) SPECIFY THE LOCATION OF THE ELECTRIC METER AND
 PANELS ON THE PLANS. FBC 107.2.1
  
 10) THE LUMINAIRES LOCATED IN THE BEDROOM CLOSETS SHALL
 MEET THE REQUIREMENTS OF NEC 410.
  
 11) FBC 107.2.1 - INFORMATION ON CONSTRUCTION
 DOCUMENTS. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. THIS ITEM WAS
 ADDRESSED. PLANS WERE SIGNED AND SEALED BY A FLORIDA
 LICENSED ENGINEER.
  
 12) IN ORDER TO REDUCE PLAN REVIEW TIMES AND PROVIDE
 CLARIFICATION, PLEASE SUBMIT A RESPONSE LETTER
 INDICATING HOW EACH OF THE REVIEW COMMENTS HAS BEEN
 ADDRESSED.
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-05-23 Cont ID  
Sent By rmcdouga Date 2015-04-13 Time 17:12 Rev Time 0.00
Received By rmcdouga Date 2015-04-13 Time 16:38 Sent To  
Notes
2015-04-13 17:12:52PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY ELECTRICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) NEC 210.52 (C) (1) - A RECEPTACLE OUTLET SHALL BE
 INSTALLED AT EACH COUNTERTOP SPACE 12 INCHES OR WIDER
 SO THAT NO POINT ALONG THE WALL LINE IS MORE THAN 2
 FEET MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET IN
 THAT SPACE.
  
 2) NEC 210.8 (A)(6) RECEPTACLES SERVING COUNTERTOP
 SURFACES ARE REQUIRED TO BE GFCI PROTECTED.
  
 3) NEC 210.12 (B) - OUTLETS ARE REQUIRED TO BE AFCI
 PROTECTED.
  
 4) NEC 406.11 - TAMPER-RESISTANT RECEPTACLES ARE
 REQUIRED.
  
 5) NEC 440.11 & 440.14 SHOW THE LOCATION OF THE
 REQUIRED A/C EQUIPMENT DISCONNECTING MEANS ON THE
 PLANS.
  
 6) NEC 210.63 - PROVIDE A GFCI PROTECTED SERVICE OUTLET
 FOR WITHIN 25' OF MECHANICAL EQUIPMENT.
  
 7) THE CONDUIT AND WIRE SIZE FOR THE WEATHER HEAD SHOWN
 ON THE SERVICE RISER PLAN IS INCORRECT. NEC 310.15 (B)
 (6).
  
 8) FBC-R314.3.1 WHEN ALTERATIONS, REPAIRS OR ADDITIONS
 REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING
 ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE
 INDIVIDUAL DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE
 ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS.
 R314.3 LOCATION.
 SMOKE ALARMS SHALL BE INSTALLED IN THE FOLLOWING
 LOCATIONS:
 1. IN EACH SLEEPING ROOM.
 2. OUTSIDE EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE
 VICINITY OF THE BEDROOMS.
 3. ON EACH ADDITIONAL STORY OF THE DWELLING, INCLUDING
 BASEMENTS AND HABITABLE ATTICS BUT NOT INCLUDING CRAWL
 SPACES AND UNINHABITABLE ATTICS. IN DWELLINGS OR
 DWELLING UNITS WITH SPLIT LEVELS AND WITHOUT AN
 INTERVENING DOOR BETWEEN THE ADJACENT LEVELS, A SMOKE
 ALARM INSTALLED ON THE UPPER LEVEL SHALL SUFFICE FOR
 THE ADJACENT LOWER LEVEL PROVIDED THAT THE LOWER LEVEL
 IS LESS THAN ONE FULL STORY BELOW THE UPPER LEVEL.
 WHEN MORE THAN ONE SMOKE ALARM IS REQUIRED TO BE
 INSTALLED WITHIN AN INDIVIDUAL DWELLING UNIT THE ALARM
 DEVICES SHALL BE INTERCONNECTED IN SUCH A MANNER THAT
 THE ACTUATION OF ONE ALARM WILL ACTIVATE ALL OF THE
 ALARMS IN THE INDIVIDUAL UNIT.
  
 9) SPECIFY THE LOCATION OF THE ELECTRIC METER ON THE
 PLANS. FBC 107.2.1
  
 10) THE LUMINAIRES LOCATED IN THE BEDROOM CLOSETS SHALL
 MEET THE REQUIREMENTS OF NEC 410.
  
 11) FBC 107.2.1 - INFORMATION ON CONSTRUCTION
 DOCUMENTS. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN.
  
 12) IN ORDER TO REDUCE PLAN REVIEW TIMES AND PROVIDE
 CLARIFICATION, PLEASE SUBMIT A RESPONSE LETTER
 INDICATING HOW EACH OF THE REVIEW COMMENTS HAS BEEN
 ADDRESSED.
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2015-08-19 Cont ID  
Sent By rmcdouga Date 2015-08-19 Time 15:57 Rev Time 0.00
Received By rmcdouga Date 2015-08-18 Time 12:45 Sent To  
Notes
2015-08-18 12:45:38RESUB ROUTED TO RMCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2015-07-29 Cont ID  
Sent By rmcdouga Date 2015-07-29 Time 18:01 Rev Time 0.00
Received By rmcdouga Date 2015-07-22 Time 10:10 Sent To  
Notes
2015-07-23 10:11:10RESUB ROUTED TO RMCDOUGAL.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-07-07 Cont ID  
Sent By rmcdouga Date 2015-07-07 Time 08:20 Rev Time 0.00
Received By rmcdouga Date 2015-06-19 Time 07:56 Sent To  
Notes
2015-06-19 08:25:56ROUTED TO ZONING/FORWARD TO MCDOUGAL/CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-05-26 Cont ID  
Sent By rmcdouga Date 2015-05-26 Time 12:49 Rev Time 0.00
Received By rmcdouga Date 2015-05-07 Time 09:09 Sent To  
Notes
2015-05-07 09:08:10R14

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-04-13 Cont ID  
Sent By rmcdouga Date 2015-04-13 Time 17:13 Rev Time 0.00
Received By rmcdouga Date 2015-03-11 Time 15:16 Sent To  
Notes
2015-03-11 14:03:58R15

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2015-07-29 Cont ID  
Sent By rmcdouga Date 2015-07-29 Time 14:29 Rev Time 0.00
Received By rmcdouga Date 2015-07-29 Time 14:29 Sent To  
Notes
2015-07-29 14:31:00MU2015-17605, NO FEES WERE DUE

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2015-07-06 Cont ID  
Sent By rmcdouga Date 2015-07-06 Time 17:40 Rev Time 0.00
Received By rmcdouga Date 2015-07-06 Time 17:40 Sent To  
Notes
2015-07-06 17:41:01BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-05-26 Cont ID  
Sent By rmcdouga Date 2015-05-26 Time 08:00 Rev Time 0.00
Received By rmcdouga Date 2015-05-26 Time 08:00 Sent To  
Notes
2015-05-26 08:01:52BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2015-07-06 Cont ID  
Sent By rmcdouga Date 2015-07-06 Time 18:28 Rev Time 0.00
Received By rmcdouga Date 2015-07-06 Time 18:28 Sent To  
Notes
2015-07-06 18:43:49RED-LINED PLANS.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2015-05-26 Cont ID  
Sent By rmcdouga Date 2015-05-26 Time 11:39 Rev Time 0.00
Received By rmcdouga Date 2015-05-26 Time 08:02 Sent To  
Notes
2015-05-26 11:37:59PLAN REVIEW COMMENTS
  
 2ND REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC-R - M1401.3 SIZING. HEATING AND COOLING
 EQUIPMENT SHALL BE SIZED BASED ON BUILDING LOADS
 CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR OTHER
 APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES.
 PROVIDE EQUIPMENT SIZING CALCULATIONS. THE MECHANICAL
 EQUIPMENT LISTED IN THE SCHEDULE ON SHEET 3 IS REQUIRED
 TO MATCH THE SIZING CALCULATIONS.
 NEW COMMENT. THE EQUIPMENT SCHEDULE ON SHEET 3 OF THE
 PLANS DOES NOT MATCH THE ONE SPECIFIED IN THE SIZING
 CALCULATIONS. THE PLAN SPECIFIES A TRANE WITH A 14.5
 SEER AND THE LOAD CALCS. HAVE A GOODMAN, JANITROL,
 AMANA DISTI... WITH A 16 SEER. THE EQUIPMENT SCHEDULE
 COLUMN HEADER FOR SEER HAS 16 SEER WITH 14.5 LISTED AS
 THE SEER FOR THE TRANE UNIT.
  
 2) FBC-R - M 1602.4 PROVIDE BALANCED AIR RETURN AT
 BEDROOMS. SPECIFY THE SIZES OF THE RETURN AIR TRANSFER
 GRILLS ON THE MECHANICAL PLAN. TRANSFER GRILLES SHALL
 USE 50 SQUARE INCHES (OF GRILLE AREA) TO 100 CFM (OF
 SUPPLY AIR) FOR SIZING THROUGH-THE-WALL TRANSFER
 GRILLES AND USING AN UNRESTRICTED 1 INCH UNDERCUTTING
 OF DOORS TO ACHIEVE PROPER RETURN AIR BALANCE.
 HABITABLE ROOMS ONLY SHALL BE REQUIRED TO MEET THESE
 REQUIREMENTS FOR PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND LAUNDRY ROOMS,
 EXCEPT THAT ALL SUPPLY AIR INTO THE MASTER SUITE SHALL
 BE INCLUDED.
 NEW COMMENT. SHEET 3 OF THE PLANS SPECIFIES 8 X 8
 TRANSFER GRILLS (64 SQUARE INCHES) WHICH IS ONLY ENOUGH
 FOR 128 CFM. ALL OF THE BEDROOMS HAVE MORE CFMS THAN
 THIS.
  
 3) NEW COMMENT. THERE IS ANOTHER MECHANICAL PLAN
 INCLUDED WITH THE ENERGY CALCULATIONS THAT DOES NOT
 MATCH THE ONE ON SHEET 3 OF THE PLANS. THE FOLLOWING
 COMMENTS ADDRESS THAT DRAWING. THERE IS NO EQUIPMENT
 SCHEDULE, THE SIZE OF THE SUPPLY GRILLS ARE NOT
 SPECIFIED, THE SIZE OF THE RETURN GRILL IN THE HALLWAY
 IS NOT SPECIFIED, THE SIZE OF THE RETURN TRANSFER DUCTS
 AT BEDROOMS 1 AND 2 ARE NOT SPECIFIED AND THE NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN.
 REMOVE THE MECHANICAL PLANS THAT WILL NOT BE USED. FBC
 107.2.1
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-04-13 Cont ID  
Sent By rmcdouga Date 2015-04-13 Time 14:39 Rev Time 0.00
Received By rmcdouga Date 2015-04-13 Time 14:39 Sent To  
Notes
2015-04-13 14:31:24PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC-R - M1401.3 SIZING. HEATING AND COOLING
 EQUIPMENT SHALL BE SIZED BASED ON BUILDING LOADS
 CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR OTHER
 APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES.
 PROVIDE EQUIPMENT SIZING CALCULATIONS. THE MECHANICAL
 EQUIPMENT LISTED IN THE SCHEDULE ON SHEET 3 IS REQUIRED
 TO MATCH THE SIZING CALCULATIONS.
  
 2) FBC-R - M 1602.4 PROVIDE BALANCED AIR RETURN AT
 BEDROOMS. SPECIFY THE SIZES OF THE RETURN AIR TRANSFER
 GRILLS ON THE MECHANICAL PLAN. TRANSFER GRILLES SHALL
 USE 50 SQUARE INCHES (OF GRILLE AREA) TO 100 CFM (OF
 SUPPLY AIR) FOR SIZING THROUGH-THE-WALL TRANSFER
 GRILLES AND USING AN UNRESTRICTED 1 INCH UNDERCUTTING
 OF DOORS TO ACHIEVE PROPER RETURN AIR BALANCE.
 HABITABLE ROOMS ONLY SHALL BE REQUIRED TO MEET THESE
 REQUIREMENTS FOR PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND LAUNDRY ROOMS,
 EXCEPT THAT ALL SUPPLY AIR INTO THE MASTER SUITE SHALL
 BE INCLUDED.
  
 3) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN.
  
 4) THE PLANS SHOW THE AIRHANDLER LOCATED IN A CLOSET.
 IF THE RETURN IS THROUGH A LOUVERED DOOR, SPECIFY THAT
 ON THE PLANS. FBC 107.2
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2015-07-06 Cont ID  
Sent By rmcdouga Date 2015-07-06 Time 17:42 Rev Time 0.00
Received By rmcdouga Date 2015-07-06 Time 17:42 Sent To  
Notes
2015-07-06 17:43:13RED-LINED THE PLANS.

Review Stop P PLUMBING
Rev No 2 Status F Date 2015-05-26 Cont ID  
Sent By tlarge Date 2015-05-23 Time 12:07 Rev Time 0.00
Received By rmcdouga Date 2015-05-23 Time 12:07 Sent To  
Notes
2015-05-23 12:10:10REDLINED PLANS. FBC-R P3104.3 EVERY DRY VENT CONNECTING
 TO A HORIZONTAL DRAIN SHALL CONNECT ABOVE THE CENTER
 LINE OF THE HORIZONTAL DRAIN PIPE.

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-04-04 Cont ID  
Sent By tklarge Date 2015-04-04 Time 07:47 Rev Time 0.00
Received By tklarge Date 2015-04-04 Time 07:38 Sent To  
Notes
2015-04-04 07:47:23A CODE COMPLIANT SANITARY RISER SHALL BE SUBMITTED FOR
 REVIEW PRIOR TO ROUGH PLUMBING INSP.

Review Stop Z ZONING
Rev No 3 Status P Date 2015-06-19 Cont ID  
Sent By sgraham Date 2015-06-19 Time 09:33 Rev Time 0.00
Received By sgraham Date 2015-06-19 Time 09:33 Sent To B
Notes
2015-06-19 09:34:446/19/15
  
 DRIVEWAY PERMIT REQUIRES SEPARATE PERMIT, YOU MUST
 REMOVE SOME OF THE PAVERS, YOU MUST MAINTAIN 75% OR
 1000 SQUARE FEET OF LANDSCAPING IS REQUIRED IN THE
 FRONT SETBACK.

Review Stop Z ZONING
Rev No 2 Status P Date 2015-05-11 Cont ID  
Sent By sgraham Date 2015-05-11 Time 08:03 Rev Time 0.00
Received By sgraham Date 2015-05-11 Time 08:03 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2015-03-20 Cont ID  
Sent By sgraham Date 2015-03-20 Time 12:42 Rev Time 0.00
Received By sgraham Date 2015-03-20 Time 12:42 Sent To  
Notes
2015-03-19 15:39:023/19/15