Plan Review Details - Permit 15030405
Plan Review Stops For Permit 15030405
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-03-24 Cont ID  
Sent By jwitmer Date 2015-03-24 Time 09:30 Rev Time 0.00
Received By jwitmer Date 2015-03-24 Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-03-17 Cont ID  
Sent By jwitmer Date 2015-03-17 Time 07:45 Rev Time  
Received By jwitmer Date 2015-03-17 Time   Sent To  
Notes
2015-03-17 07:53:02 
 BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15030405
 ADD: 4801 DREHER TRL N.
 CONT: HEDRICK BROTHERS
 TEL: (561)689-8880
 E-MAIL:[email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. MARCH 18/ 2015
 ACTION: DENIED
  
 IMPORTANT NOTICE: EFFECTIVE MARCH 30, 2015
 ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED
 ELECTRONICALLY
 UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS
 SUBMISSION OPTIONS ARE AS FOLLOWS:
 1 UPLOAD VIA THE PROJECT DOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL
 SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED
 NAMING CONVENTION FOR EACH DOCUMENT
 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER
 DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE
 REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT
 TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS
 ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES
 AVAILABLE
  
 1) SHEET A-1 THE EARLY LEARNING GALLERY SHOWS AN
 OCCUPANT LOAD OF 16. 773 SQ. FT./ 16= 45.8 SQ. FT. PER
 OCCUPANT. PLEASE PROVIDE HOW THIS CALCULATION WAS
 FIGURED. THE PLANS ARE FOR THE SCIENCE MUSEUM WHICH WE
 WOULD USE 15 SQ. FT. PER OCCUPANT FOR VIEWING AREAS
 WHERE THE PUBLIC WILL GATHER.
 2010 FBC-B TABLE 1004.1.1. WHEN 773 SQ. FT. /15= 52
 OCCUPANTS (FBC-B TABLE 1004.1.1.) THIS WILL REQUIRE (2)
 EXITS (TABLE 1015.1) AND 1/3RD THE DISTANCE APART FBC-B
 1015.2.1 EXCEP # 2.
  
 PLEASE PROVIDE WHAT THE USAGE OF THIS ROOM WILL BE AND
 WHY THE REDUCED OCCUPANT LOAD ONLY REQUIRING 1 EXIT
 FROM THIS AREA. 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-03-16 Cont ID  
Sent By scaldero Date 2015-03-16 Time 11:43 Rev Time 0.00
Received By scaldero Date 2015-03-12 Time 12:20 Sent To  
Notes
2015-03-16 11:58:49PERMIT # 15030405
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THIS PLAN HAS BEEN REVIEWED AND APPROVED WITH COMMENTS.
 PROVISO:
 1) ALL REQUIRED FIRE ALARM DEVICES TO BE VERIFIED IN
 THE FIELD. SEPARATE PLANS AND PERMITS ARE REQUIRED FOR
 THE INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
 2) EMERGENCY LIGHTING REQUIRED IN THE EARLY LEARNING
 CENTER GALLERY - TO BE VERIFIED IN THE FIELD.
 3) A 2-HOUR SEPERATION IS REQUIRED FOR THE DEVISING
 WALL BETWEEN THE OFFICES/WOOD SHOP AND THE PLANETARIUM.
 (PLANS DO NOT SHOW THE CURRENT SEPARATION FOR THIS
 WALL.)
  
  
 ROY LINDOW
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4754
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-03-24 Cont ID  
Sent By jwitmer Date 2015-03-24 Time 09:31 Rev Time 0.00
Received By jwitmer Date 2015-03-23 Time   Sent To  
Notes
2015-03-23 14:37:37INCOMING SENT TO J. W, DESK.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-03-21 Cont ID  
Sent By hmoser Date 2015-03-21 Time 10:23 Rev Time 0.00
Received By hmoser Date 2015-03-11 Time 12:44 Sent To  
Notes
2015-03-11 12:48:12B10

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2015-03-24 Cont ID  
Sent By jwitmer Date 2015-03-24 Time   Rev Time 0.00
Received By jwitmer Date 2015-03-24 Time   Sent To  
Notes
2015-03-24 09:31:23NO PLANS/ NO CHANGE IN A/C LAYOUT.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-03-21 Cont ID  
Sent By hmoser Date 2015-03-21 Time 10:23 Rev Time 0.00
Received By hmoser Date 2015-03-21 Time 10:22 Sent To  
Notes
2015-03-21 10:23:28NO MECHANICAL PLAN SUBMITTED WITH PACKAGE. HM.

Review Stop Z ZONING
Rev No 1 Status P Date 2015-03-19 Cont ID  
Sent By ajones Date 2015-03-19 Time 16:20 Rev Time 0.00
Received By ajones Date 2015-03-19 Time 16:20 Sent To  
Notes
***NONE***