Plan Review Details - Permit 15030292
Plan Review Stops For Permit 15030292
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-05-18 Cont ID  
Sent By rmcdouga Date 2015-05-18 Time 15:50 Rev Time 0.00
Received By rmcdouga Date 2015-05-18 Time 15:50 Sent To Z
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-04-08 Cont ID  
Sent By rmcdouga Date 2015-04-08 Time 18:07 Rev Time 0.00
Received By rmcdouga Date 2015-04-08 Time 17:11 Sent To  
Notes
2015-04-08 18:07:52PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. PROVIDE TWO COMPLETE PRODUCT
 APPROVALS WITH FL OR NOA NUMBERS INCLUDING INSTALLATION
 INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES FOR EACH OF
 THE DIFFERENT ROOFING MATERIALS, WINDOW/GLASS TYPES,
 STRUCTURAL MULLIONS AND EXTERIOR DOOR TYPES.
 A) THE PLANS SPECIFY SINGLE HUNG WINDOWS AND PRODUCT
 APPROVALS WERE SUBMITTED FOR CASEMENT WINDOWS. FBC
 107.2.1
 B) PRODUCT APPROVALS WERE SUBMITTED FOR GLAZED FRENCH
 DOORS. THE ELEVATIONS SHOW A FLUSH DOOR AND TWO (2)
 PANEL DOORS. ONE OF THE PANEL DOORS HAS AN ARCHED TOP.
  
 2) SHOW COMPLIANCE WITH FBC EXISTING BUILDING 604.1 AND
 FBC-R310.1 FOR EMERGENCY ESCAPE AND RESCUE AT THE
 BEDROOM WINDOWS.
  
 IN ORDER TO REDUCE PLAN REVIEW TIMES AND PROVIDE
 CLARIFICATION, PLEASE SUBMIT A RESPONSE LETTER
 INDICATING HOW EACH OF THE REVIEW COMMENTS HAS BEEN
 ADDRESSED.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-04-08 Cont ID  
Sent By rmcdouga Date 2015-04-08 Time 15:37 Rev Time 0.00
Received By rmcdouga Date 2015-04-08 Time 15:37 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2015-06-01 Cont ID  
Sent By fmittner Date 2015-06-01 Time 15:55 Rev Time 0.00
Received By fmittner Date 2015-06-01 Time 15:55 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2015-03-06 Cont ID  
Sent By fmittner Date 2015-03-06 Time 16:27 Rev Time 0.00
Received By fmittner Date 2015-03-06 Time 16:27 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-06-02 Cont ID  
Sent By lmarchan Date 2015-06-02 Time 07:39 Rev Time 0.00
Received By lmarchan Date 2015-05-01 Time 17:27 Sent To  
Notes
2015-05-01 17:27:26SENT TO R MCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2015-04-08 Time   Rev Time 0.00
Received By jgomez Date 2015-03-06 Time 18:14 Sent To  
Notes
2015-03-06 18:15:21SENT TO R6 BIN FOR REVIEW. JG.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2015-05-18 Cont ID  
Sent By rmcdouga Date 2015-05-18 Time 16:36 Rev Time 0.00
Received By rmcdouga Date 2015-05-18 Time 15:51 Sent To  
Notes
2015-05-18 16:51:02CONTRACTOR, NICK VILLE, REMOVED HVAC FROM THE SCOPE OF
 WORK. A SEPARATE PERMIT, APPLICATION AND REVIEW IS
 REQUIRED. THE VALUE OF THE HVAC WORK ( $9000.00 ) WAS
 REMOVED FOR THE MASTER PERMIT.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-04-08 Cont ID  
Sent By rmcdouga Date 2015-04-08 Time 15:37 Rev Time 0.00
Received By rmcdouga Date 2015-04-08 Time 15:37 Sent To  
Notes
2015-04-08 16:19:38PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE SCOPE OF WORK ON THE PRIMARY PERMIT APPLICATION
 STATES ADD A/C. HOWEVER NO MECHANICAL PLANS OR PERMIT
 APPLICATION WAS SUBMITTED. FBC 107.1
  
 2) FBC-R - M1401.3 SIZING. HEATING AND COOLING
 EQUIPMENT SHALL BE SIZED BASED ON BUILDING LOADS
 CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR OTHER
 APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES.
 PROVIDE EQUIPMENT SIZING CALCULATIONS.
  
 3) FBC - 107.3.5.3 PROVIDE TWO SETS OF A MECHANICAL
 PLAN TO SHOW EQUIPMENT (SCHEDULE ON PLANS) AND LOCATION
 AND DUCT SYSTEMS PER FBC-R M16 & BATH EXHAUST PER FBC-R
 M15.

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-04-04 Cont ID  
Sent By tklarge Date 2015-04-04 Time 09:33 Rev Time 0.00
Received By tklarge Date 2015-04-04 Time 09:17 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2015-03-06 Cont ID  
Sent By fmittner Date 2015-03-06 Time 16:27 Rev Time 0.00
Received By fmittner Date 2015-03-06 Time 16:27 Sent To B
Notes
***NONE***