Plan Review Details - Permit 15030245
Plan Review Stops For Permit 15030245
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-06-10 Cont ID  
Sent By jwitmer Date 2015-06-10 Time 15:43 Rev Time 0.00
Received By jwitmer Date 2015-06-10 Time 15:43 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-03-14 Cont ID  
Sent By jwitmer Date 2015-03-14 Time 11:00 Rev Time  
Received By jwitmer Date 2015-03-14 Time 09:45 Sent To  
Notes
2015-03-14 10:22:27BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15030245
 ADD: 1215 TAMARIND AVE
 CONT: BRINMAR CONSTRUCTION
 TEL: ( 904)360-9066
 E-MAIL:[email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 IMPORTANT NOTICE: EFFECTIVE MARCH 30, 2015
 ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED
 ELECTRONICALLY
 UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS
 SUBMISSION OPTIONS ARE AS FOLLOWS:
 1 UPLOAD VIA THE PROJECT DOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL
 SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED
 NAMING CONVENTION FOR EACH DOCUMENT
 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER
 DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE
 REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT
 TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS
 ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES
 AVAILABLE
  
 1ST REVIEW
 DATE: SAT. MARCH 14/ 2015
 ACTION: DENIED
  
 1) THE VALUE OF THE WORK INDICATED IN THE PERMIT
 ($7,500.00) VALUE IS EXTRMELY, LOW. IF NOT BROUGHT UP
 TO THE FAIR MARKET VALUE PLEASE SEE HOW A CALCULATED
 VALUE WILL BE OBTAINED.
 PERMIT FEES/ PLAN REVIEW:
 W P B ADMINISTRATIVE CODE 108.2 SCHEDULE OF PERMIT
 FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS,
 MECHANICAL AND PLUMBING SYSTEMS OR ALTERATIONS
 REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID
 AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE
 ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY.
  
 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 2) THE PLANS SHOW (2) NEW OPENINGS THROUGH THE EXTERIOR
 WALL AND THERE ARE NO STRUCTURAL PLANS SUBMITTED BY THE
 FL LICENSED P. E. GEORGE ROUMAIN.
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. THE
 EXAMINATION OF THE DOCUMENTS BY THE BUILDING OFFICIAL
 SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA AND
 DOCUMENTS: T; ALL FENESTRATION PENETRATIONS, EXTERIOR
 DOORWAYS AND ROUGH OPENING DIMENSIONS; AND ALL EXTERIOR
 ELEVATIONS:
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 SITE PLAN W/ PROPERTY LINES AND OR SURVEY PROVIDE
 DIMENSIONS FROM THE PROPERTY LINES IT APPEARS THER MAY
 BE PROPERT LINES WITH 5 FT OF EXTERIOR WALLS.
 PARKING & ACCESSIBLE PARKING WITH AN ACCESSIBLE ROUTE
 TO THE ENTRANCE.
 OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS
 SHALL BE DETERMINED.
 MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED (SEE
 TABLE 503, TABLE 602 & TABLE 705.7)
 FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL INCLUDE
 THE FOLLOWING COMPONENTS:
 FIRE-RESISTANT SEPARATIONS
 FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION
 PROTECTION OF OPENINGS AND PENETRATIONS OF RATED WALLS
 FIRE SPRINKLERED OR NOT
 OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD
 USAGE OF ROOMS, OR ROOM IDENTIFICATION NUMBERS
 GROSS
 NET
 MEANS OF EGRESS
 EXIT ACCESS
 EXIT
 EXIT DISCHARGE
 STAIRS CONSTRUCTION/GEOMETRY AND PROTECTION
 EMERGENCY LIGHTING AND EXIT SIGNS
 DOORS
 STRUCTURAL REQUIREMENTS SHALL INCLUDE:
 WIND REQUIREMENTS
 BUILDING ENVELOPE
 ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE FOLLOWING:
 SITE REQUIREMENTS
 ACCESSIBLE ROUTE
 VERTICAL ACCESSIBILITY
 TOILET AND BATHING FACILITIES
 DRINKING FOUNTAINS
  
 3) THE SUBMITTED PRODUCT APPROVAL NOA : 13-1021.05
 ALDORA MK-2 ALUMINUM ENTRANCE DOOR W/ WO TRANSOM NO
 ELEVATION TO SHOW IF THIS IS A SINGLE DOOR, DOUBLE WITH
 OR WITH OUT TRANSOM. NONE OF THE SIZE OF THE UNIT, TYPE
 OF GLAZING, TYPE OF ANCHORS AND ASSOCIATED PRESSURES
 ARE PROVIDED. THE PLANS DO NOT INDICATE IF THIS SAME
 UNIT IS TO BE INSTALLED AT THE FRONT ENTRY AND OR AT
 THE 2 NEW OPENINGS THAT ARE BEING CREATED.
 COMPONENTS & CLADDING
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41
 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
  
 4) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 5) THE WIND DESIGN CRITERIA IS NOT PROVIDE, SHOW
 COMPLIANCE WITH :
 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
  
 5.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 5.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 5.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 5.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 5.5) COMPONENTS & CLADDING PRESSURES POSITIVE &
 NEGATIVE TABLE 1609.2(2)
  
 6) SHEET A1 DETAIL # 2 SHOWS AN EXISTING WOOD RAMP AND
 DETAIL OF A NEW RAILING. SHEET A1 THE CUT SECTION DOES
 NOT SHOW ANY TOP LANDING REQUIED BY THE CODE. SEE FBC-B
 1010.6 AND FL ACCESS. CODE . LANDINGS SHALL COMPLY WITH
 SECTIONS FBC-B 1010.6.1 THROUGH 1010.6.5.
  
 7) SHEET A-1 THE DOOR AT THE TOP OF THE RAMP DOES NOT
 COMPLY WITH THE 2010 FBC ACCESS. 404.2.4.1 MANEUVERING
 CLEARANCES.
  
 8) SHEET A-1 DOES NOT SHOW WHAT THE ROOM IS RIGHT
 BEHIND THE PROPOSED NEW ACCESSIBLE RESTROOM. THE OTHER
 ISSUE IS HOW WILL THE DOOR OPEN WHEN THE PLANS SHOW A
 CABINET BLOCKING THE DOOR SWING. 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIED, A DISCREPANCY IN THE PLANS.
 PLEASE MAKE CORRECTIONS.
  
 9) SHEET A-1 DETAIL 3/ A4 SHOWS A NEW HANDRAIL SYSTEM,
 PLEASE SEE TTHE REQUIREMENTS FOR EXTENSIONS 2010
 FBC-ACCESS. CODE 505.10.
  
 10) THE ELEVATED AREA OFTHE BUILDING PLEASE SHOW
 COMPLIANCE WITH 2010 FL ACCESS. CODE 201.1.1 VERTICAL
 ACCESSIBILITY.
  
 11) SHEET A-4 THE CONCRETE RAMP AND HANDRAIL GAURD RAIL
 LOCATION IS NOT SHOWN ON SHEET A1, NOT ABLE TO COMMENT
 ON THIS BECAUSE OF TO MANY VARIABLES WITHOUT THE
 LOCATION PROVIDED. 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED, LOCATION.
  
 12) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561) 805-6715
 FAX: (561)805-6676
 E-MAIL: [email protected]
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-05-19 Cont ID  
Sent By pleduc Date 2015-05-19 Time   Rev Time 0.00
Received By pleduc Date 2015-05-19 Time 15:33 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-03-12 Cont ID  
Sent By pleduc Date 2015-03-12 Time   Rev Time 0.00
Received By pleduc Date 2015-03-12 Time 12:20 Sent To  
Notes
2015-03-12 14:08:58THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 SHEET A-1 INDICATES NEW EXIT DOORS. NO DIMENSIONS ARE
 PROVIDED.
  
 SHEET A-1 DOES NOT INDICATE ANY EXIT SIGNS, INCLUDING
 NONE AT THE NEWLY CREATED EXIT DOORS.
  
 PROVIDE A DOOR SCHEDULE TO INCLUDE DIMENSIONS, TYPE,
 FINISH, HARDWARE, CLOSERS, ETC.
  
 PROVIDE A LIFE SAFETY PLAN INCLUDING, OCCUPANCY LOADS,
 PATH OF EGRESS, EXIT SIGNS, EMERGENCY LIGHTS, AND FIRE
 EXTIGUISHER LOCATIONS.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2015-07-29 Cont ID  
Sent By tklarge Date 2015-07-29 Time 15:24 Rev Time 0.00
Received By tklarge Date 2015-07-29 Time 15:23 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-07-09 Cont ID  
Sent By skennedy Date 2015-07-09 Time 10:43 Rev Time 0.00
Received By skennedy Date 2015-06-30 Time 10:33 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-06-17 Cont ID  
Sent By   Date 2015-06-17 Time   Rev Time 0.00
Received By dhayes Date 2015-05-15 Time 14:55 Sent To  
Notes
2015-06-23 12:34:12PERMIT FAILED. FILED UNDER "B"
2015-06-17 15:07:59 
  
 ROUTED TO ZONING FOR LAST REMAINING REVIEW.
2015-05-15 14:56:05B28

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-03-31 Cont ID  
Sent By tklarge Date 2015-03-31 Time 08:56 Rev Time 0.00
Received By tklarge Date 2015-03-06 Time 15:22 Sent To  
Notes
2015-03-09 15:23:01SENT TO B9 BIN FOR REVIEW. JG.

Review Stop P PLUMBING
Rev No 4 Status P Date 2015-07-29 Cont ID  
Sent By tklarge Date 2015-07-29 Time 15:24 Rev Time 0.00
Received By tklarge Date 2015-07-29 Time 15:23 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2015-07-01 Cont ID  
Sent By tklarge Date 2015-07-01 Time 05:05 Rev Time 0.00
Received By tklarge Date 2015-07-01 Time 04:49 Sent To  
Notes
2015-07-01 04:35:011 ) SHT. 4 OF 6 & SHEET 6 OF 6 SHOWS A WATER
 DISPENSER.THIS IS NOT ACCEPTABLE AS COMPLIANT WITH 2010
 FPC TABLE 403.1. A DRINKING FOUNTAIN IS REQUIRED FOR
 THIS OCCUPANCY AND FOOTNOTE "E" AT THE BOTTOM OF TABLE
 403.1 STATES THAT THE MINIMUM NUMBER OF REQUIRED
 DRINKING FOUNTAINS SHALL COMPLY WITH TABLE 403.1 AND
 THE FLORIDA BUILDING CODE, ACCESSIBILITY. SECTION 211.2
 OF THE FAC REQUIRES A MINIMUM OF 2 DRINKING FOUNTAINS.
 DELETE THE WATER DISPENSER FROM THESE SHEETS.
 2) THE PLAN THAT WAS SUBMITTED FOR THE NEW DRINKING
 FOUNTAINS HAS A COPY OF AN ENGINEER'S SIGNATURE AND
 SEAL. THE PLAN SHALL BE SIGNED AND SEALED BY THE
 ENGINEER AND SHALL COMPLY WITH FL. ADMIN. CODE RULE
 61G15-23.002.
 3) THE NEW SHEET FOR THE DRINKING FOUNTAINS SHALL BE
 INSERTED INTO EACH SET OF PLANS.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2015-06-13 Cont ID  
Sent By tlarge Date 2015-06-13 Time 05:42 Rev Time 0.00
Received By tklarge Date 2015-06-13 Time 05:18 Sent To  
Notes
2015-06-13 05:35:571) SHT. 4 OF 6 SHOWS A WATER DISPENSER. IS THIS NEW AND
 MEANT TO COMPLY WITH FPC TABLE 403.1? IF SO, IT IS NOT
 ACCEPTABLE. A DRINKING FOUNTAIN IS REQUIRED FOR THIS
 OCCUPANCY AND FOOTNOTE "E" AT THE BOTTOM OF TABLE 403.1
 STATES THAT THE MINIMUM NUMBER OF REQUIRED DRINKING
 FOUNTAINS SHALL COMPLY WITH TABLE 403.1 AND THE FLORIDA
 BUILDING CODE, ACCESSIBILITY. SECTION 211.2 OF THE FAC
 REQUIRES A MINIMUM OF 2 DRINKING FOUNTAINS. CLARIFY.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-03-31 Cont ID  
Sent By tklarge Date 2015-03-31 Time 08:56 Rev Time 0.00
Received By tklarge Date 2015-03-31 Time 07:28 Sent To  
Notes
2015-03-31 08:55:431) SHT. A-1 - THE CLEARANCE AROUND THE WATER CLEARANCE
 SHALL BE 60 INCHES MINIMUM MEASURED PERPENDICULAR FROM
 THE SIDE WALL AND 56 INCHES MINIMUM(59 INCHES IF FLOOR
 MOUNTED WATER CLOSET) MEASURED PERPENDICULAR FROM THE
 REAR WALL PER SEC. 604.3.1 OF THE 2010 FL. ACCESS.
 CODE. AS DESIGNED, THE RESTROOM IS NOT WIDE ENOUGH.
 MINIMUM WIDTH SHALL BE 85 INCHES.
 2) SHT. A-2 - THE GRAB BARS SHALL BE LOCATED A MINIMUM
 OF 33 INCHES AND 36 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR MEASURED TO THE TOP OF THE GRIPPING SURFACE PER
 2010 FAC SEC.609.4.
 3) THE SEAT HEIGHT OF THE WATER CLOSET SHALL COMPLY
 WITH FAC SEC.604.4. SHOW THE HEIGHT ON THE PLAN.
 4) THE LOCATION OF THE WATER CLOSET SHALL COMPLY WITH
 THE 2010 FAC SEC.604.2.
 5) TOILET PAPER DISPENSER SHALL COMPLY WITH FAC SEC.
 604.7.
 6) MINIMUM KNEE AND TOE CLEARANCES SHALL BE PROVIDED
 UNDER THE LAVATORY PER THE 2010 FAC SEC.306.2 & 306.3.
 7) SHT. P-1, NOTE # 5 REFERS TO A SHOWER YET NO SHOWER
 IS SHOWN ON THE PLANS. CLARIFY.
 8) SHT. A-1 - THE TOILET ROOM SHOWS A CABINET ON THE
 BACKSIDE DOOR WHICH WOULD INTERFERE WITH THE DOOR
 OPENING. CLARIFY.
 9) THE DEMO PLAN LINES AND HARD TO SEE FOR THE OBJECTS
 TO BE REMOVED. CLEARLY SHOW THE DEMO DETAILS ON THE
 PLANS. WPB AMEND. TO 2010 FBC SEC. 107.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2015-07-08 Cont ID  
Sent By aaponte Date 2015-07-08 Time 16:01 Rev Time 0.00
Received By aaponte Date 2015-07-08 Time 16:01 Sent To  
Notes
2015-07-08 16:05:28PROVISO: EXISTING 5' WIDE SIDEWALK EASEMENT SHALL BE
 MAINTAINED CLEAR OF ANY OBSTRUCTION.
 THIS PERMIT DOES NOT INCLUDE ANY WORK ON THE PAVED AREA
 LOCATED ON THE BACK OF THE BUILDING.

Review Stop Z ZONING
Rev No 2 Status F Date 2015-06-23 Cont ID  
Sent By aaponte Date 2015-06-23 Time 12:27 Rev Time 0.00
Received By aaponte Date 2015-06-23 Time 12:27 Sent To  
Notes
2015-06-23 12:31:10THE PROPOSED RAMP MAY BE ENCROACHING INTO THE CITY'S
 RIGHT OF WAY AND WITHIN THE MINIMUM REQUIRED SETBACK OF
 10 FEET AS MEASURED FROM THE BACK OF THE CURB.
 PLEASE PROVIDE A SURVEY OF THE PROPERTY.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.

Review Stop Z ZONING
Rev No 1 Status P Date 2015-03-13 Cont ID  
Sent By aaponte Date 2015-03-13 Time 09:40 Rev Time 0.00
Received By aaponte Date 2015-03-13 Time 09:28 Sent To  
Notes
***NONE***