Plan Review Details - Permit 15030233
Plan Review Stops For Permit 15030233
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-03-05 Cont ID  
Sent By shill Date 2015-03-05 Time 18:46 Rev Time 0.00
Received By shill Date 2015-03-05 Time 18:46 Sent To  
Notes
2015-03-05 18:52:06****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. EXISTING CONDITIONSA RE CONFUSING. IF THIS IS
 RELATED TO A MASTER PERMIT, THIS PERMIT SHOULD BE
 REFERENCED ON THE PERMIT APPLICATION. A NOC FROM
 ANOTHER PROJECT WAS PROVIDED. ARE YOU A SUB TO THIS
 CONTRACTOR? WHY WASN'T THIS SUBMITTED AS A REVISION TO
 THE MASTER PERMIT?
  
 BOTH CONCRETE AND WOOD ARE STATED AS SUBSTRATES. IF
 THIS IS RELATED TO NEW CONSTRUCTION, REVIEW BY DESIGNER
 OF RECORD IS REQUIRED.
  
 HOW WILL PANELS BE INSTALLED ON THE THIRD FLOOR? WHERE
 WILL THEY BE STORED? WHO WILL BE RESPONSIBLE FOR
 INSTALLATION?
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-03-05 Cont ID  
Sent By shill Date 2015-03-05 Time 18:52 Rev Time 0.00
Received By shill Date 2015-03-05 Time 15:04 Sent To  
Notes
2015-03-05 15:04:16ROUTED TO BLDG $5000 & UNDER