Plan Review Details - Permit 15030134
Plan Review Stops For Permit 15030134
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-04-14 Cont ID  
Sent By shill Date 2015-04-14 Time 07:36 Rev Time 0.00
Received By shill Date 2015-04-14 Time 07:36 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-03-14 Cont ID  
Sent By shill Date 2015-03-14 Time 15:52 Rev Time 0.00
Received By shill Date 2015-03-14 Time 15:52 Sent To  
Notes
2015-03-14 15:57:00****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. REVISE PLAN TO INCLUDE OCCUPANCY CLASSIFICATION, FBC
 CHAPTER 3, BUILDING SIZE, AND BUILDING TYPE FBC CHAPTER
 6.
  
 2. PROVIDE A SPECIFICATION FOR THE FLOOR. PROPOSED WORK
 NOT CLEAR. "WOOD FLOORING" AND "PLYWOOD FLOORING" ARE
 BOTH SPECIFIED ON THE APPLICATION. PROVIDE A DETAIL,
 FBC 107.
  
 3. FLOOR PLAN TO INDICATE LOCATION AND SCOPE OF
 FLOORING WORK, FBC 107.
  
 4. PLANS TO INCLUDE THE PRINTED NAME AND SIGNATURE OF
 THE INDIVIDUAL TAKING RESPONSIBILITY FOR THE DESIGN,
 FBC 107.
  
 5. FBC 2010 EXISTING BUILDING 401.4, A DESIGN
 PROFESSIONAL OR OWNER MUST ELECT ONE OR A COMBINATION
 OF LEVELS OF ALTERATION PURSUANT TO SECTIONS 403, 404
 AND 405 OF THIS CODE.
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-04-14 Cont ID  
Sent By shill Date 2015-04-14 Time 07:36 Rev Time 0.00
Received By shill Date 2015-04-08 Time 11:46 Sent To B
Notes
2015-04-09 11:47:09TO S. HILLS DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-03-14 Cont ID  
Sent By shill Date 2015-03-14 Time 15:57 Rev Time  
Received By shill Date   Time   Sent To  
Notes
2015-03-04 13:43:34ROUTED TO MISC 1
  
  