Plan Review Details - Permit 15030033
Plan Review Stops For Permit 15030033
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-03-25 Cont ID  
Sent By jwitmer Date 2015-03-25 Time 14:21 Rev Time 0.00
Received By jwitmer Date 2015-03-25 Time 13:00 Sent To  
Notes
2015-03-25 13:35:15BUILDING PLAN REVIEW
 PERMIT: 15030033
 ADD: 1300 FLORIDA MANGO RD BAY # 17
 CONT: COMPLETE SOLUTIONS
 TEL: (561)337-7793
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 IMPORTANT NOTICE: EFFECTIVE MAY 11, 2015
 ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED
 ELECTRONICALLY
 UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS
 SUBMISSION OPTIONS ARE AS FOLLOWS:
 1 UPLOAD VIA THE PROJECT DOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL
 SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED
 NAMING CONVENTION FOR EACH DOCUMENT
 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER
 DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE
 REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT
 TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS
 ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES
 AVAILABLE
  
  
  
  
 NOTICE!!!!!!! ) NOTICE: CHAPTER 553.80(2)(B) FLORIDA
 STATUTES STATES THAT A LOCAL GOVERNMENT SHALL IMPOSE A
 FEE OF FOUR TIMES THE FEE FOR PLAN REVIEW, IF PLANS ARE
 REJECTED (3) OR MORE TIMES FOR REPEATED FAILURE TO
 CORRECT A CODE VIOLATION.
  
  
  
  
 2ND REVIEW
 DATE: WED. MARCH 25/2015
 ACTION: DENIED
  
 1A) 2ND REQUEST. (2) SHEETS(A1 & E1, P1) INDICATE 4
 SHEETS WHILE SHEET A-2 INDICATES 2OF 3 SHEETS IN PLANS.
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 107.2.1 DISCREPANCY IN
 PLANS, ADDITIONAL INFORMATION IS REQUIRED.
  
 1B) 2ND REQUEST. SHEET A2, 2OF 4. DISCREPANCY IN PLANS
 AND PERMIT APPLICATION. THE PERMIT APPLICATION
 INDICATES WORK IS TO BE COMPLETED IN BAY # 17. THE
 PLANS SHOW ONE WALL BEING REMOVED IN BAY # 17 AND THE
 MAJORITY OF THE WORK BEING COMPLETED IN BAY 18.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED FOR THE
 LOCATION OF WORK TO BE COMPLETED UNDER THIS PERMIT.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. L.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION...
  
 2) SHEET A2, 2OF 4. IN BAY # 18 WHERE THE MAJORITY
 OFTHE WORK IS SHOWN THERE IS A BAY WITH 2 LARGE GARAGE
 DOORS THAT SEPERATE THE OFFICE AREA FROM THE WAREHOUSE
 AREA. THE DESIGNER OF RECORD INDICATES THIS WALL TO BE
 A 1 HOUR FIRE RATED WALL WITH WALL SECTION DETAIL. NOTE
 THE DOORS LOCATED IN THIS WALL DO NOT INDICATE THERE
 FIRE RATING NOR CLASSIFICATION. PLEASE SEE 2010 FBC-B
 TABLE 715.4.
  
 3) 2ND REQUEST. SHEET A2, 2OF 4. IN BAY # 18 WHERE THE
 NEW OFFICES ARE BEING BUILT AS WELL AS THE LARGER
 STORAGE AREA TO THE LEFT OF THE OFFICE, THE DESIGN OF
 RECORD HAS NOT DECLARED A OCCUPANCY.
 2010 FBC-B 302.1 GENERAL.
 STRUCTURES OR PORTIONS OF STRUCTURES SHALL BE
 CLASSIFIED WITH RESPECT TO OCCUPANCY IN ONE OR MORE OF
 THE GROUPS LISTED BELOW. A ROOM OR SPACE THAT IS
 INTENDED TO BE OCCUPIED AT DIFFERENT TIMES FOR
 DIFFERENT PURPOSES SHALL COMPLY WITH ALL OF THE
 REQUIREMENTS THAT ARE APPLICABLE TO EACH OF THE
 PURPOSES FOR WHICH THE ROOM OR SPACE WILL BE OCCUPIED.
 STRUCTURES WITH MULTIPLE OCCUPANCIES OR USES SHALL
 COMPLY WITH SECTION 508 MIXED OCCUPANCIES.SEE TABLE
 508.4. THE WAREHOUSE WALL ADJOINING THE KITCHEN DOES
 NOT SHOW ANY FIRE RATING?
  
 4) COMPLIED.
  
 5) 2ND REQUEST. SHEET A2, 2OF 4. IN THE NEW OFFICES
 THERE IS GLAZING NEXT TO THE OFFICE DOORS, SHOW
 COMPLIANCE WITH 2010 FBC-B 406.4 HAZARDOUS LOCATIONS.
 THE FOLLOWING SHALL BE CONSIDERED SPECIFIC HAZARDOUS
 LOCATIONS REQUIRING SAFETY GLAZING MATERIALS:
 6. GLAZING IN AN INDIVIDUAL FIXED OR OPERABLE PANEL
 ADJACENT TO A DOOR WHERE THE NEAREST EXPOSED EDGE OF
 THE GLAZING IS WITHIN A 24-INCH (610 MM) ARC OF EITHER
 VERTICAL EDGE OF THE DOOR IN A CLOSED POSITION AND
 WHERE THE BOTTOM EXPOSED EDGE OF THE GLAZING IS LESS
 THAN 60 INCHES (1524 MM) ABOVE THE WALKING SURFACE.
  
 6) 2ND REQUEST. PLEASE SHOW COMPLIANCE WITH 2010 FBC-B
 1203.1 BUILDINGS SHALL BE PROVIDED WITH NATURAL
 VENTILATION IN ACCORDANCE WITH SECTION 1203.4, OR
 MECHANICAL VENTILATION IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, MECHANICAL.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561) 805-6715
 FAX: (561)805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-03-03 Cont ID  
Sent By jwitmer Date 2015-03-03 Time 07:30 Rev Time  
Received By jwitmer Date 2015-03-03 Time 06:31 Sent To  
Notes
2015-03-03 07:25:06BUILDING PLAN REVIEW
 PERMIT: 15030033
 ADD: 1300 FLORIDA MANGO RD BAY # 17
 CONT: COMPLETE SOLUTIONS
 TEL: (561)337-7793
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 IMPORTANT NOTICE: EFFECTIVE MAY 11, 2015
 ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED
 ELECTRONICALLY
 UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS
 SUBMISSION OPTIONS ARE AS FOLLOWS:
 1 UPLOAD VIA THE PROJECT DOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL
 SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED
 NAMING CONVENTION FOR EACH DOCUMENT
 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER
 DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE
 REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT
 TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS
 ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES
 AVAILABLE
  
 1ST REVIEW
 DATE: TUES. MARCH 03/2015
 ACTION: DENIED
  
 1A) PLANS INDICATE 4 PAGES, ONLY (3) SUBMITTED.
  
 1B) SHEET A2, 2OF 4. DISCREPANCY IN PLANS AND PERMIT
 APPLICATION. THE PERMIT APPLICATION INDICATES WORK IS
 TO BE COMPLETED IN BAY # 17. THE PLANS SHOW ONE WALL
 BEING REMOVED IN BAY # 17 AND THE MAJORITY OF THE WORK
 BEING COMPLETED IN BAY 18.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED FOR THE
 LOCATION OF WORK TO BE COMPLETED UNDER THIS PERMIT.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. L.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION...
  
 2) SHEET A2, 2OF 4. IN BAY # 18 WHERE THE MAJORITY
 OFTHE WORK IS SHOWN THERE IS A BAY WITH 2 LARGE GARAGE
 DOORS THAT SEPERATE THE OFFICE AREA FROM THE WAREHOUSE
 AREA. THE DESIGNER OF RECORD INDICATES THIS WALL TO BE
 A 1 HOUR FIRE RATED WALL WITH WALL SECTION DETAIL. NOTE
 THE DOORS LOCATED IN THIS WALL DO NOT INDICATE THERE
 FIRE RATING NOR CLASSIFICATION. PLEASE SEE 2010 FBC-B
 TABLE 715.4.
  
 3) SHEET A2, 2OF 4. IN BAY # 18 WHERE THE NEW OFFICES
 ARE BEING BUILT AS WELL AS THE LARGER STORAGE AREA TO
 THE LEFT OF THE OFFICE, THE DESIGN OF RECORD HAS NOT
 DECLARED A OCCUPANCY.
 2010 FBC-B 302.1 GENERAL.
 STRUCTURES OR PORTIONS OF STRUCTURES SHALL BE
 CLASSIFIED WITH RESPECT TO OCCUPANCY IN ONE OR MORE OF
 THE GROUPS LISTED BELOW. A ROOM OR SPACE THAT IS
 INTENDED TO BE OCCUPIED AT DIFFERENT TIMES FOR
 DIFFERENT PURPOSES SHALL COMPLY WITH ALL OF THE
 REQUIREMENTS THAT ARE APPLICABLE TO EACH OF THE
 PURPOSES FOR WHICH THE ROOM OR SPACE WILL BE OCCUPIED.
 STRUCTURES WITH MULTIPLE OCCUPANCIES OR USES SHALL
 COMPLY WITH SECTION 508 MIXED OCCUPANCIES.SEE TABLE
 508.4. THE WAREHOUSE WALL ADJOINING THE KITCHEN DOES
 NOT SHOW ANY FIRE RATING?
  
 4) SHEET A2, 2OF 4. THE PLANS INDICATE A KITCHEN, THERE
 IS NO SINK, RANGE/ STOVE OR HOOD IF THIS AREA IS TO BE
 CONSIDERED A KITCHEN. 2010 FBC-B F] 903.2.11.5
 COMMERCIAL COOKING OPERATIONS. AN AUTOMATIC SPRINKLER
 SYSTEM SHALL BE INSTALLED IN COMMERCIAL KITCHEN EXHAUST
 HOOD AND DUCT SYSTEM WHERE AN AUTOMATIC SPRINKLER
 SYSTEM IS USED TO COMPLY WITH SECTION 904.
  
 5) SHEET A2, 2OF 4. IN THE NEW OFFICES THERE IS GLAZING
 NEXT TO THE OFFICE DOORS, SHOW COMPLIANCE WITH 2010
 FBC-B 406.4 HAZARDOUS LOCATIONS.
 THE FOLLOWING SHALL BE CONSIDERED SPECIFIC HAZARDOUS
 LOCATIONS REQUIRING SAFETY GLAZING MATERIALS:
 6. GLAZING IN AN INDIVIDUAL FIXED OR OPERABLE PANEL
 ADJACENT TO A DOOR WHERE THE NEAREST EXPOSED EDGE OF
 THE GLAZING IS WITHIN A 24-INCH (610 MM) ARC OF EITHER
 VERTICAL EDGE OF THE DOOR IN A CLOSED POSITION AND
 WHERE THE BOTTOM EXPOSED EDGE OF THE GLAZING IS LESS
 THAN 60 INCHES (1524 MM) ABOVE THE WALKING SURFACE.
  
 6) PLEASE SHOW COMPLIANCE WITH 2010 FBC-B 1203.1
 BUILDINGS SHALL BE PROVIDED WITH NATURAL VENTILATION IN
 ACCORDANCE WITH SECTION 1203.4, OR MECHANICAL
 VENTILATION IN ACCORDANCE WITH THE FLORIDA BUILDING
 CODE, MECHANICAL.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561) 805-6715
 FAX: (561)805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-03-03 Cont ID  
Sent By rlecky Date 2015-03-03 Time 13:40 Rev Time 0.00
Received By rlecky Date 2015-03-03 Time 13:05 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2015-03-25 Cont ID  
Sent By pleduc Date 2015-03-25 Time   Rev Time 0.00
Received By pleduc Date 2015-03-25 Time 09:47 Sent To  
Notes
2015-03-25 09:55:07THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THE NARRATIVE DESCRIPTION FROM THE RE-SUBMITTAL FORM
 STATES CORRECTIONS AS REQUESTED PER PLAN EXAMINER'S AND
 REMOVE KITCHETTE AREA.
  
 THE PREVIOUS COMMENTS FROM FIRE PREVENTION HAVE NOT
 BEEN ADDRESSED AND THE PLAN INDICATE A KITCHENETTE AREA
 REMINAING. THE PLANS ARE THE SAME PLANS THAT WERE
 SUBMITTED PREVIOUSLY WITH NO CHANGES.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-03-05 Cont ID  
Sent By pleduc Date 2015-03-05 Time   Rev Time 0.00
Received By pleduc Date 2015-03-05 Time 10:31 Sent To PC
Notes
2015-03-05 10:50:41THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 SHEET A-1, THERE IS INCORRECT REFERENCE TO FIRE CODES -
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
  
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2010 EDITION.
  
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2010 EDITION.
  
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2009 EDITION.
  
 FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 10, 2010 EDITION.
  
 ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION.
  
 SHEET A-1 REFERNECES THAT THE BUILDING IS SPRINKLERS -
 THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF THE
 FIRE ALARM AND SPRINKLER SYSTEM FOR CODE COVERAGE AND
 COMPLIANCE.
  
 PLEASE INDICATE ON THE PLANS THAT THE LIFE SAFETY
 SYSTEMS, FIRE ALARM AND/OR FIRE SPRINKLER SHALL REMAIN
 ACTIVE THROUGHOUT THE CONSTRUCTION PERIOD.
  
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  
 SHEET E-1, P-1 INDICATES A PIECE OF EQUIPMENT IN THE
 KITCHEN AREA MARK WITH A RED LETTER "F". WHAT IS THIS
 PIECE OF EQUIRPMENT? WHAT ADDITONAL PIECES OF EQUIPMENT
 PROPOSED FOR THE KITCHEN? WHAT IS THE PROPOSED COOKING
 IN THIS KITCHEN? COOKING MEETING THE PROTECTION
 REQUIREMENTS CONTAINED WITHIN NFPA 96 SHALL COMPLY WITH
 THAT CODE..
  
 SHEET A-2 DOES NOT INDICATE ANY EXIT SIGNS WITHIN THE
 KITCHEN AREA. THIS AREA HAS ACCESS TO 2 EXITS. ONE
 ADDITIONAL EXIT SIGN SHALL BE ADDED TO THE KITCHEN AREA
 AT THE AREA OF THE CORRIDOR.
  
 SHEET A-2 INDICATES THE ADDITION OF A NEW WALL
 SEPARATING THE KITCHEN AND THE WAREHOUSE. PLEASE
 PROVIDE THE REQUIRED FIRE RATING OF THIS WALL AND THE
 DOOR.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-03-25 Cont ID  
Sent By jwitmer Date 2015-03-25 Time 14:21 Rev Time 0.00
Received By jwitmer Date 2015-03-18 Time 18:41 Sent To B
Notes
2015-03-20 18:35:09RE-SUBMITTAL SENT TO B29 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-03-05 Cont ID  
Sent By pleduc Date 2015-03-05 Time   Rev Time  
Received By pleduc Date 2015-03-02 Time   Sent To  
Notes
2015-03-03 06:50:24B29

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2015-03-03 Cont ID  
Sent By   Date 2015-03-03 Time   Rev Time  
Received By   Date 2015-03-03 Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2015-03-25 Cont ID  
Sent By jwitmer Date 2015-03-25 Time 13:36 Rev Time 0.00
Received By jwitmer Date 2015-03-25 Time   Sent To  
Notes
2015-03-25 13:41:02MECHANICAL PLAN REVIEW
 PERMIT: 15030033
 ADD: 1300 FLORIDA MANGO RD BAY # 17
 CONT: COMPLETE SOLUTIONS
 TEL: (561)337-7793
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 IMPORTANT NOTICE: EFFECTIVE MAY 11, 2015
 ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED
 ELECTRONICALLY
 UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS
 SUBMISSION OPTIONS ARE AS FOLLOWS:
 1 UPLOAD VIA THE PROJECT DOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL
 SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED
 NAMING CONVENTION FOR EACH DOCUMENT
 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER
 DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE
 REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT
 TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS
 ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES
 AVAILABLE
  
 2ND REVIEW.
 WED./ MARCH 25/ 2015
 DENIED.
  
 1) NEW OFFICES, NO FRESH AIR, NO MECHANICAL PLANS NOR
 ENERGY CALCULATION WERE SUBMITTED. THE ELEECTRICAL
 SHEET INDICATES AIR HANDLERS ON CIRCUITS 5 & 7, AND THE
 COMPRESSORS ON CIRCUITS 2 & 4.
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION107.3.5 MINIMUM PLAN
 REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.4 MECHANICAL
 2. EQUIPMENT
 3. EQUIPMENT LOCATION
 4. MAKE-UP AIR
 5. ROOF-MOUNTED EQUIPMENT
 6. DUCT SYSTEMS
 7. VENTILATION
  
 2) 2010 FBC-M 401.2 VENTILATION REQUIRED. EVERY
 OCCUPIED SPACE SHALL BE VENTILATED BY NATURAL MEANS IN
 ACCORDANCE WITH SECTION 402 OR BY MECHANICAL MEANS IN
 ACCORDANCE WITH SECTION 403.
  
 3) 2010 FBC-ENERGY 503.1 GENERAL. MECHANICAL SYSTEMS
 AND EQUIPMENT SERVING THE BUILDING HEATING, COOLING OR
 VENTILATING NEEDS SHALL COMPLY WITH SECTION 503.2
 (REFERRED TO AS THE MANDATORY PROVISIONS) AND SECTION
 503.3 (SIMPLE SYSTEMS).
  
 4) 2010 FBC-ENERGY 502.1.1 INSULATION AND FENESTRATION
 CRITERIA. 502.1.1.1 SHELL BUILDINGS, RENOVATIONS AND
 ALTERATIONS. THE BUILDING THERMAL ENVELOPE SHALL MEET
 THE REQUIREMENTS OF TABLE 502.1.1.1(1) OR TABLE
 502.1.1.1(2). SEE SECTION 101.4.3.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-03-03 Cont ID  
Sent By jwitmer Date 2015-03-03 Time   Rev Time 0.00
Received By jwitmer Date 2015-03-03 Time   Sent To  
Notes
2015-03-03 06:54:04NEW OFFICES, NO FRESH AIR, NO MECHANICAL PLANS NOR
 ENERGY CALCULATION WERE SUBMITTED.