Plan Review Details - Permit 15030012
Plan Review Stops For Permit 15030012
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-03-12 Cont ID  
Sent By jwitmer Date 2015-03-12 Time 07:53 Rev Time 0.00
Received By jwitmer Date 2015-03-12 Time 07:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-03-03 Cont ID  
Sent By jwitmer Date 2015-03-03 Time 09:28 Rev Time 0.00
Received By jwitmer Date 2015-03-03 Time 09:28 Sent To  
Notes
2015-03-03 09:43:17 
 BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15030012
 ADD: 419 15TH ST.
 CONT: PACE ROOFING
 TEL: (561)642-8840
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE:
 ACTION: DENIED
  
 IMPORTANT NOTICE: EFFECTIVE MARCH 30, 2015
 ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED
 ELECTRONICALLY
 UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS
 SUBMISSION OPTIONS ARE AS FOLLOWS:
 1 UPLOAD VIA THE PROJECT DOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL
 SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED
 NAMING CONVENTION FOR EACH DOCUMENT
 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER
 DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE
 REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT
 TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS
 ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES
 AVAILABLE
  
 1) PLEASE NOTE THE PERMIT APPLICATION INDICATES WORK TO
 BE COMPLETED ON A 3 STORY BUILDING. THE ENGINNERING
 SHEET FOR THE FLAT ROOF ENHANCED FASTENING SCHEDULE FOR
 ZONES 2 & 3 INDICATES A SINGLE STORY BUILDING OF 15
 FEET, WHEN LOOKING AT THE ADDRESS FOR THIS REPORT IT IS
 FOR A DIFFERENT PROPERTY, 4805 S, DIXIE HWY. THE
 SUBMITTED FLORIDA ROOFING REPORT FL 16730 HAS DIFFERENT
 SUB-SYSTEMS HIGHLIGHTED AND DIFFERENT PAGES THAN THE
 ENHANCED FASTENING ENGINEERING SHEET. 107.2.1.3
 ADDITIONAL INFORMATION REQUIRED, THERE IS A DISCREPANCY
 IN PAPERWORK.
  
 JAMES WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561) 805-6715
 FAX: (561)805-6676
 E-MAIL: [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-03-12 Cont ID  
Sent By   Date 2015-03-12 Time   Rev Time 0.00
Received By jgomez Date 2015-03-10 Time 18:12 Sent To  
Notes
2015-03-10 18:12:55RE-SUBMITTAL SENT TO JIM WITMER FOR REVIEW. JG.