Plan Review Details - Permit 15020941
Plan Review Stops For Permit 15020941
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-07-21 Cont ID  
Sent By jwitmer Date 2015-07-21 Time 15:26 Rev Time 0.00
Received By jwitmer Date 2015-07-21 Time 15:26 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-06-25 Cont ID  
Sent By jwitmer Date 2015-06-25 Time 16:24 Rev Time 0.00
Received By jwitmer Date 2015-06-25 Time 15:45 Sent To  
Notes
2015-06-25 16:24:36BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15020941
 ADD: 633 5TH ST.
 CONT: BUILT SOLID CONSTRUCTION
 TEL: (561)333-2593
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: THURS. JUNE 25/ 2015
 ACTION: DENIED
  
 1) COMPLIED.
  
 2) 2ND REQUEST. MISSING SOILS REPORT WITH THE MINIMUM
 SAFE BEARING VALUE. 2010 FBC-B 1803.5.2 QUESTIONABLE
 SOIL. WHERE THE CLASSIFICATION, STRENGTH OR
 COMPRESSIBILITY OF THE SOIL IS IN DOUBT OR WHERE A
 LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS
 CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL BE
 PERMITTED TO REQUIRE THAT A GEOTECHNICAL INVESTIGATION
 BE CONDUCTED.
  
 3-8) COMPLIED.
  
 9) 2ND REQUEST. SHEET A-1 SHOWS A NEW RAMP WITH A
 HEIGHT OF 6 INCHES AND A 6 INCH STEP ADJACENT TO THE
 RAMP.THE 2010 FBC-B 1003.5 WHERE CHANGES IN ELEVATION
 OF LESS THAN 12 INCHES IN A MEANS OF EGRESS SLOPED
 SURFACES SHALL BE USED, NOT A STEP.
 NOTE IF THE FINISH FLOOR IS 6 INCHES OR LESS THAN
 HANDRAILS ARE NOT REQUIRED. IF WHEN IN THE FIELD THE
 RAMP IS EITHER GREATER THAN 6 INCHES IN HEIGHT OR 72
 INCHES IN LENGTH HANDRAILS WILL BE REQUIRED PER 1010.8
 WITH THE REQUIRED BACKING FOR HANDRAILS.
  
 10) 2ND REQUEST. SHEET A-1 SHOWS IN THE AREA OF WORK
 (2) EXTERIOR DOORWAYS WITH A 4INCH DROP, BOTH DOORS ARE
 SHOWN TO BE REQUIRED EXITS. PLEASE REVIEW:
 2010 FBC-B 1008.1.5 FLOOR ELEVATION. THERE SHALL BE A
 FLOOR OR LANDING ON EACH SIDE OF A DOOR. SUCH FLOOR OR
 LANDING SHALL BE AT THE SAME ELEVATION ON EACH SIDE OF
 THE DOOR. LANDINGS SHALL BE LEVEL EXCEPT FOR EXTERIOR
 LANDINGS, WHICH ARE PERMITTED TO HAVE A SLOPE NOT TO
 EXCEED 1 UNIT VERTICAL IN 50 UNITS HORIZONTAL
 (2-PERCENT SLOPE).
  
 11-14) COMPLIED.
  
 15) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561) 805-6715
 FAX: (561)805-6676
 E-MAIL: [email protected]
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-03-13 Cont ID  
Sent By jwitmer Date 2015-03-13 Time 12:31 Rev Time  
Received By jwitmer Date 2015-03-12 Time   Sent To  
Notes
2015-03-13 10:21:07BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15020941
 ADD: 633 5TH ST.
 CONT: BUILT SOLID CONSTRUCTION
 TEL: (561)333-2593
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 IMPORTANT NOTICE: EFFECTIVE MARCH 30, 2015
 ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED
 ELECTRONICALLY
 UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS
 SUBMISSION OPTIONS ARE AS FOLLOWS:
 1 UPLOAD VIA THE PROJECT DOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL
 SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED
 NAMING CONVENTION FOR EACH DOCUMENT
 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER
 DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE
 REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT
 TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS
 ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES
 AVAILABLE
  
 1ST REVIEW
 DATE: FRI. MARCH 13/ 2015
 ACTION: DENIED
  
 1) THE ARCHITECT OF RECORD FOR THIS PROJECT HAS ON HER
 TITLE BLOCK INDICATED THAT : DRAWINGS ARE SIGNED ND
 SEALED FOR STRUCTURE ONLY.
 DOES THE ARCHIEC TO RECORD HAVE A ENGINEERING LICENSE
 AND REGISTRATION IN THE STATE OF FLORIDA?
 ARCHITECTS SEAL 61G1-16.003 USE OF SEAL.
 AN ARCHITECT OR INTERIOR DESIGNER SHALL NOT USE HIS
 SEAL OR DO ANY OTHER ACT AS AN ARCHITECT OR INTERIOR
 DESIGNER UNLESS HOLDING AT THE TIME A CERTIFICATE OF
 REGISTRATION AND ALL REQUIRED RENEWALS THEREOF.
  
 61G1-16.003 USE OF SEAL.
 THE PERSONAL SEAL, SIGNATURE AND DATE OF THE ARCHITECT
 OR INTERIOR DESIGNER SHALL APPEAR ON ALL ARCHITECTURAL
 OR INTERIOR DESIGN DOCUMENTS TO BE FILED FOR PUBLIC
 RECORD AND SHALL BE CONSTRUED TO OBLIGATE HIS PARTNERS
 OR HIS CORPORATION. A CORPORATE SEAL ALONE IS
 INSUFFICIENT. DOCUMENTS SHALL BE SIGNED PERSONALLY AND
 SEALED BY THE RESPONSIBLE ARCHITECT OR INTERIOR
 DESIGNER. FINAL OFFICIAL RECORD DOCUMENTS (NOT
 TRACINGS, ETC.) SHALL BE SO SIGNED. THE SIGNING AND
 SEALING OF THE SPECIFICATION INDEX SHEETS SHALL BE
 CONSIDERED ADEQUATE. ALL DRAWING SHEETS AND PAGES SHALL
 BE SO SIGNED AND SEALED. AN ARCHITECT OR INTERIOR
 DESIGNER SHALL NOT AFFIX, OR PERMIT TO BE AFFIXED, HIS
 SEAL OR NAME TO ANY PLAN, SPECIFICATIONS, DRAWINGS, OR
 OTHER RELATED DOCUMENT WHICH WAS NOT PREPARED BY HIM OR
 UNDER HIS RESPONSIBLE SUPERVISING CONTROL AS PROVIDED
 IN RULE CHAPTER 61G1-23, F.A.C. AN ARCHITECT OR
 INTERIOR DESIGNER SHALL NOT USE HIS SEAL OR DO ANY
 OTHER ACT AS AN ARCHITECT OR INTERIOR DESIGNER UNLESS
 HOLDING AT THE TIME A CERTIFICATE OF REGISTRATION AND
 ALL REQUIRED RENEWALS THEREOF.
  
 ENGINEERING 471.003 471.003?QUALIFICATIONS FOR
 PRACTICE; EXEMPTIONS. (3) HOWEVER, NO ENGINEER SHALL
 PRACTICE ARCHITECTURE OR USE THE DESIGNATION
 ?ARCHITECT? OR ANY TERM DERIVED THEREFROM, AND NO
 ARCHITECT SHALL PRACTICE ENGINEERING OR USE THE
 DESIGNATION ?ENGINEER? OR ANY TERM DERIVED THEREFROM.
  
 2) MISSING SOILS REPORT WITH THE MINIMUM SAFE BEARING
 VALUE. 2010 FBC-B 1803.5.2 QUESTIONABLE SOIL. WHERE THE
 CLASSIFICATION, STRENGTH OR COMPRESSIBILITY OF THE SOIL
 IS IN DOUBT OR WHERE A LOAD-BEARING VALUE SUPERIOR TO
 THAT SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING
 OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A
 GEOTECHNICAL INVESTIGATION BE CONDUCTED.
  
 3) THE ENERGY DOCUMENTS SUBMITTED SHOW A ELITE SOFTWARE
 PROGRAM. UNDER THE 2010 FBC- ENERGY SHALL COMPLY WITH :
 103.2.1.2.1 BUILDING THERMAL ENVELOPE ALTERNATIVE.
 AN ACCURATELY COMPLETED COMMERCIAL BUILDING FORM 502
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO
 DEMONSTRATE CODE COMPLIANCE BY THIS METHOD.
  
 103.2.2.2 SIMULATED PERFORMANCE ALTERNATIVE, COMMERCIAL
 AND HIGH-RISE RESIDENTIAL.
 AN ACCURATELY COMPLETED COMMERICAL BUILDING FORM 506
 (GENERATED BY COMMISSION APPROVED SOFTWARE)
 DEMONSTRATING THAT CODE COMPLIANCE HAS BEEN ACHIEVED
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL FOR
 COMPLIANCE BY SECTION 506.
 06.3.2 ENVELOPE LIMITATION.
 FOR NEW BUILDINGS OR ADDITIONS, THE BUILDING ENERGY
 COST BUDGET METHOD RESULTS SHALL NOT BE SUBMITTED FOR
 BUILDING PERMIT APPROVAL TO THE CODE OFFICIAL PRIOR TO
 SUBMITTAL FOR APPROVAL OF THE BUILDING ENVELOPE DESIGN.
  
 4A) NOTE THE WINDOW AND DOOR PRODUCT APPROVALS
 SUBMITTED, DOES NOT HAVE THE SHOP DRAWING STAMP OF
 APPROVAL FROM THE DESIGNER OF RECORD.
 SHOP DRAWING STAMP OF APPROVAL
 106.3* PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY DCA RULE 9N-3 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 4B) ROOFING PRODUCT APPROVAL, 2 DIFFERENT ROOFING
 SHINGLE NOAS WERE SUBMITTED, NOA:14-1022.20 GAF
 TIMBERLINE & NOA 11-0913.12 TAMCO ELITE GLASS-SEAL ROOF
 SHINGLES. THE TAMCO ELITE SHINGLE DOES HAVE THE SHOP
 DRAWING STAMP OF APPROVAL. WHICH IS TO BE INSTALLED?
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 5) SHEET A-5 INDICATES THIS TO BE THE FOUNDATION PLAN.
 THERE ARE NO NOTES IN REGARD TO THE MINIMUM BEARING
 VALUE OF THE SOIL, VAPOR BARRIER REQUIREMENTS NOR THE
 TYPE OF TERMITE TREATMENT FOR THE SLAB.
 1816.1 TERMITE PROTECTION.
 1910.1 MINIMUM SLAB PROVISIONS.
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION,
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 STRUCTURAL REQUIREMENTS SHALL INCLUDE:
 SOIL CONDITIONS/ANALYSIS
 TERMITE PROTECTION
 DESIGN LOADS
 WIND REQUIREMENTS
  
 6) SHEET A-5 INDICATES IN A WALL SECTION SHEET S-1
 DETAIL 1 MISSING THERE IS NO S-1 SHEET. 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED.
  
 7) MISSING BEAM SCHEDULE, THE COLUMN SCHEDULE IS
 PRINTED TWICE. NOT THERE IS ALSO NO LINTEL SCHEDULE FOR
 WINDOWS NOR IS THERE A TRUSS LAYOUT WITH THE LOADS TO
 BE RESISTED, GRAIVITY, UPLIFT OR LATERAL LOADS.
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION,
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 STRUCTURAL REQUIREMENTS SHALL INCLUDE:
 DESIGN LOADS
 WIND REQUIREMENTS
 BUILDING ENVELOPE
 WALL SYSTEMS
 ROOF SYSTEMS TRUSSES, DROPPED TRUSSES FOR GABLE
 OVERHANG OF 2 FT
 MWFRS MAIN WIND FORCE RESISTING SYSTEM
  
 8) THE COVERSHEET LIST THE NEW ADDITION AS A BUSINESS
 OCCUPANCY. 2010 FBC-B 1004.1.1 AREAS WITHOUT SEATING
 NEED TO BE EVALUATED IN THE WORST CASE SCENARIO, THIS
 AREA MAY BE USED AS A SUNDAY SCHOOL CLASS, AS A
 FELLOWSHIP HALL OR FOR OTHER FUNCTIONSOF A A3
 OCCUPANCY. SEE TABLE 1004.1.1 AREAS WHERE UN
 CONCENTRATED SEATING TABLE AND CHAIRS PLEASE USE 15
 NET.
  
 9) SHEET A-1 SHOWS A NEW RAMP WITH A HEIGHT OF 6
 INCHES. NOTE IF THE FINISH FLOOR IS 6 INCHES OR LESS
 THAN HANDRAILS ARE NOT REQUIRED. IF WHEN IN THE FIELD
 THE RAMP IS EITHER GREATER THAN 6 INCHES IN HEIGHT OR
 72 INCHES IN LENGTH HANDRAILS WILL BE REQUIRED PER
 1010.8 WITH THE REQUIRED BACKING FOR HANDRAILS.
  
 10) SHEET A-1 SHOWS INTHE AREA OF WORK (2) EXTERIOR
 DOORWAYS WITH A 4INCH DROP, BOTH DOORS ARE SHOWN TO BE
 REQUIRED EXITS. NOTE WITH THE ASSEMBLY OCCUPANCY THIS
 AREA WILL HAVE A OCCUPANT LOAD GREATERTHAN 50 REQUIRING
 (2) EXITS. PLEASE REVIEW:
  
 2010 FBC-B 1008.1.5 FLOOR ELEVATION. THERE SHALL BE A
 FLOOR OR LANDING ON EACH SIDE OF A DOOR. SUCH FLOOR OR
 LANDING SHALL BE AT THE SAME ELEVATION ON EACH SIDE OF
 THE DOOR. LANDINGS SHALL BE LEVEL EXCEPT FOR EXTERIOR
 LANDINGS, WHICH ARE PERMITTED TO HAVE A SLOPE NOT TO
 EXCEED 1 UNIT VERTICAL IN 50 UNITS HORIZONTAL
 (2-PERCENT SLOPE).
  
 11) SHEET A-1 DOES NOT SHOW THE DOOR HARDWARE FOR THE
 NEW DOOR OPENINGS. 2010 FBC-B 1008.1.9.1, 1008.1.9.3
 AND 1008.1.10.
  
 12) SHEET A-2 INDICATES THE USE OF EAVE VENTS BUT DOES
 NOT SHOW COMPLIANCE WITH THE UPPER PORTION OF THE ROOF
 BEING VENTED. 2010 FBC-B 1203.2 ATTIC SPACES. THE NET
 FREE VENTILATING AREA SHALL NOT BE LESS THAN 1/300 OF
 THE AREA OF THE SPACE VENTILATED, WITH 50 PERCENT OF
 THE REQUIRED VENTILATING AREA PROVIDED BY VENTILATORS
 LOCATED IN THE UPPER PORTION OF THE SPACE TO BE
 VENTILATED AT LEAST 3 FEET (914 MM) ABOVE EAVE OR
 CORNICE VENTS WITH THE BALANCE OF THE REQUIRED
 VENTILATION PROVIDED BY EAVE OR CORNICE VENTS.
  
 13) SHEET A-2 ALSO FAILS TTO SHOW COMPLIANCE WITH 2010
 FBC-B 1209.2 ATTIC SPACES.
 AN OPENING NOT LESS THAN 20 INCHES BY 30 INCHES (559 MM
 BY 762 MM) SHALL BE PROVIDED TO ANY ATTIC AREA HAVING A
 CLEAR HEIGHT OF OVER 30 INCHES (762 MM). A 30-INCH (762
 MM) MINIMUM CLEAR HEADROOM IN THE ATTIC SPACE SHALL BE
 PROVIDED AT OR ABOVE THE ACCESS OPENING.
  
 14) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 15) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561) 805-6715
 FAX: (561)805-6676
 E-MAIL: [email protected]
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-06-09 Cont ID  
Sent By rlecky Date 2015-06-09 Time 11:56 Rev Time 0.00
Received By rlecky Date 2015-06-09 Time 11:44 Sent To  
Notes
2015-06-04 14:21:29NEW DRAWINGS SUBMITTED. JG.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-04-23 Cont ID  
Sent By rlecky Date 2015-04-23 Time 14:56 Rev Time 0.00
Received By rlecky Date 2015-04-23 Time 14:26 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2015-06-10 Cont ID  
Sent By cranford Date 2015-06-10 Time 12:14 Rev Time 0.00
Received By cranford Date 2015-06-09 Time 14:30 Sent To  
Notes
2015-06-10 12:14:11APPLICANT CLARIFIED APPLICATION WAS FOR 400 SF BUILDING
 ADDITION ONLY.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2015-04-27 Cont ID  
Sent By Mgonzale Date 2015-04-27 Time   Rev Time 1.00
Received By mgonzale Date 2015-04-27 Time   Sent To I
Notes
2015-04-27 11:28:55RESPOND TO COMMENTS IN WRITING:
  
 1. SUBMIT A PROPERTY SURVEY. LIMITS OF EXISTING PARKING
 AND NORTH ENTRANCE DRIVE LIES WITHIN THE PROPERTY TO
 THE NORTH. IF THE PROPERTIES HAVE SAME OWNERS THEN A
 "UNITY OF TITLE" WILL BE REQUIRED.
  
 2. FROM THE PLANS SUBMITTED WE ARE UNABLE TO DETERMINE
 HOW MUCH IMPROVEMENTS WILL BE MADE TO CURB, PARKING AND
 SITE AS A WHOLE. DEPENDING ON THE SCOPE OF THE WORK AN
 ENGINEERING DEVELOPMENT APPROVAL FROM THE CITY OF WEST
 PALM BEACH PUBLIC WORKS DEPARTMENT IS REQUIRED FOR ALL
 PROJECTS INVOLVING OR AFFECTING THE CITY OF WEST PALM
 BEACH STREET RIGHT-OF-WAYS, EASEMENTS, POTABLE WATER
 SYSTEM, SANITARY SEWER SYSTEM, STORMWATER SYSTEM, SOLID
 WASTE COLLECTION, OR PEDESTRIAN AND VEHICULAR TRAFFIC.
 THIS INCLUDES ANY WORK THAT INCREASES IMPERVIOUS AREAS;
 CHANGES THE DIRECTION, VELOCITY, OR TIMING OF
 STORMWATER DISCHARGE; OR CREATES A CONDITION OF
 ENVIRONMENTAL CONCERN.
  
 SHOULD YOU REQUIRE FURTHER INFORMATION AS TO SUBMITTING
 FOR ENGINEERING DEVELOPMENT APPROVAL, APPLICATION FORMS
 CAN BE DOWNLOADED AT
 HTTP://WPB.ORG/ENGINEERING/FORMS-AND-PUBLICATIONS/
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-06-05 Cont ID  
Sent By pleduc Date 2015-06-05 Time   Rev Time 0.00
Received By pleduc Date 2015-06-05 Time 13:56 Sent To  
Notes
2015-06-04 14:15:52NEW DRAWINGS SUBMITTED. JG.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-03-05 Cont ID  
Sent By pleduc Date 2015-03-05 Time   Rev Time 0.00
Received By pleduc Date 2015-03-05 Time 12:15 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2015-07-16 Cont ID  
Sent By fmittner Date 2015-07-16 Time 10:31 Rev Time 0.00
Received By fmittner Date 2015-07-16 Time 10:31 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status F Date 2015-07-10 Cont ID  
Sent By fmittner Date 2015-07-10 Time 16:01 Rev Time 0.00
Received By fmittner Date 2015-07-10 Time 16:01 Sent To  
Notes
2015-07-10 16:02:04STILL NEEDS TO SUBMIT COA

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2015-03-19 Cont ID  
Sent By fmittner Date 2015-03-19 Time 09:23 Rev Time 0.00
Received By fmittner Date 2015-03-19 Time 09:23 Sent To  
Notes
2015-03-19 09:30:19ADDITION TO HISTORIC STRUCTURE REQURIES SUBMITTAL OF
 CERTIFICATE OF APPROPRIATENESS APPLICATION. WINDOWS
 SHALL BE SAME PROPORTIONS AS ORIGINAL. QUESTIONS
 CONTACT FRIEDERIKE MITTNER, CITY HISOTRIC PRESERVATION
 PLANNER AT 822-1457.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-07-21 Cont ID  
Sent By jwitmer Date 2015-07-21 Time 15:26 Rev Time 0.00
Received By jwitmer Date 2015-07-16 Time 13:39 Sent To  
Notes
2015-07-16 13:40:39ON CCOLE DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-07-10 Cont ID  
Sent By cpuell Date 2015-07-10 Time 17:21 Rev Time 0.00
Received By cpuell Date 2015-06-04 Time 14:27 Sent To  
Notes
2015-06-04 14:28:25RE-SUBMITTAL SENT TO C13 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-04-28 Cont ID  
Sent By cranford Date 2015-04-28 Time 13:55 Rev Time 0.00
Received By cranford Date 2015-02-27 Time 09:07 Sent To  
Notes
2015-02-28 09:08:41C13

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2015-07-21 Cont ID  
Sent By jwitmer Date 2015-07-21 Time 15:02 Rev Time 0.00
Received By jwitmer Date 2015-07-21 Time 14:59 Sent To  
Notes
2015-07-21 15:02:27IMPACT FEES
 JUNE 08/2015
 MU-2015-11062
 FEES: $ 864.37
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2015-06-25 Cont ID  
Sent By jwitmer Date 2015-06-25 Time 15:42 Rev Time 0.00
Received By jwitmer Date 2015-06-25 Time 15:42 Sent To  
Notes
2015-06-25 15:44:39PALM BEACH COUNTY IMPACT FEE OFFICE
 RECEIPT NO. 2015-0519-71
 TRACKING # MU-2015011062-0000
 FEES: $864.37

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-03-12 Cont ID  
Sent By jwitmer Date 2015-03-12 Time 15:26 Rev Time  
Received By jwitmer Date 2015-03-12 Time   Sent To  
Notes
2015-03-12 15:26:34BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2015-07-22 Cont ID  
Sent By ccole Date 2015-07-22 Time 06:46 Rev Time 0.00
Received By ccole Date 2015-07-22 Time 06:46 Sent To  
Notes
2015-07-22 06:52:49MECHANICAL APPROVED WITH EXCEPTION.
 REVISIONS TO THE APPROVED PLANS FOR THE ITEMS LISTED
 BELOW SHALL BE SUBMITTED, REVIEWED AND APPROVED PRIOR
 TO 1ST INSPECTION.
  
 1) THE MECHANICAL CLOSET LOUVERED DOOR #2 SHALL BE OF
 NON-COMBUSTIBLE MATERIALS: THE DOOR SCHEDULE IS
 INDICATING A WOOD DOOR- REFERENCE SECTIONS 202, 602,
 AND 603.1 FBC-10 MECHANICAL.
 2) INDICATE HOW THE O/A DAMPER IS BEING CONTROLLED-
 REFER TO SECTION 503.2.5.4 FBC-10 ENERGY CONSERVATION.
 3) THE TOILET EXHAUST FAN FOR BATH-1 SHALL HAVE A
 MINIMUM EXHAUST CAPACITY OF 100 CFM'S PER TABLE 403.3
 FOOTNOTE E. 50 CFM PER TOILET OR URINAL.
 4) PROVIDE TIE DOWN ENGINEERING FOR THE AC CONDENSERS-
 SECTION 301.12 FBC-10 MECHANICAL
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2015-07-17 Cont ID  
Sent By ccole Date 2015-07-17 Time 07:29 Rev Time 0.00
Received By ccole Date 2015-07-17 Time 07:29 Sent To  
Notes
2015-07-17 07:31:482ND REVIEW: FBC 2010 MECHANICAL
 PERMIT #15020941
 7/17/15.
  
 NOTE: I HAVE RE-PRINTED THE COMMENTS FROM THE PREVIOUS
 (1ST) REVIEW BELOW. THE PLANS WERE RE-SUBMITTED WITHOUT
 THE REQUESTED CORRECTIONS.
  
 1ST REVIEW: FBC 2010 MECHANICAL
 6/26/15
  
 1) THE MECHANICAL CLOSET LOUVERED DOOR #2 SHALL BE OF
 NON-COMBUSTIBLE MATERIALS: THE DOOR SCHEDULE IS
 INDICATING A WOOD DOOR- REFERENCE SECTIONS 202, 602,
 AND 603.1 FBC-10 MECHANICAL.
 2) INDICATE HOW THE O/A DAMPER IS BEING CONTROLLED-
 REFER TO SECTION 503.2.5.4 FBC-10 ENERGY CONSERVATION.
 3) THE TOILET EXHAUST FAN FOR BATH-1 SHALL HAVE A
 MINIMUM EXHAUST CAPACITY OF 100 CFM'S PER TABLE 403.3
 FOOTNOTE E. 50 CFM PER TOILET OR URINAL.
 4) PROVIDE TIE DOWN ENGINEERING FOR THE AC CONDENSERS-
 SECTION 301.12 FBC-10 MECHANICAL
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2015-06-26 Cont ID  
Sent By ccole Date 2015-06-26 Time 13:51 Rev Time 0.00
Received By ccole Date 2015-06-26 Time 13:50 Sent To  
Notes
2015-06-26 14:57:531ST REVIEW: FBC 2010 MECHANICAL
 6/26/15
  
 1) THE MECHANICAL CLOSET LOUVERED DOOR #2 SHALL BE OF
 NON-COMBUSTIBLE MATERIALS: THE DOOR SCHEDULE IS
 INDICATING A WOOD DOOR- REFERENCE SECTIONS 202, 602,
 AND 603.1 FBC-10 MECHANICAL.
 2) INDICATE HOW THE O/A DAMPER IS BEING CONTROLLED-
 REFER TO SECTION 503.2.5.4 FBC-10 ENERGY CONSERVATION.
 3) THE TOILET EXHAUST FAN FOR BATH 1 SHALL HAVE A
 MINIMUM EXHAUST CAPACITY OF 100 CFM'S PER TABLE 403.3
 FOOTNOTE E. 50 CFM PER TOILET OR URINAL.
 4) PROVIDE TIE DOWN ENGINEERING FOR THE AC CONDENSERS-
 SECTION 301.12
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-04-01 Cont ID  
Sent By hmoser Date 2015-04-01 Time 13:52 Rev Time 0.00
Received By hmoser Date 2015-04-01 Time 12:02 Sent To  
Notes
2015-04-01 13:52:46PLANS DENIED
 1) PROVIDE EXHAUST FOR BATHROOMS. PER TABLE 403.3 FBC
 (M) 2010
 2) PROVIDE OUTSIDE AIR DUCT ON PLANS WITH AUTOMATIC
 DAMPER. PER
 SECTION 503.2.5.4 SHUTOFF DAMPER CONTROLS FLORIDA
 ENERGY CODE
 2010 FBC (M)
 3) PROVIDE MANUFACTURES INSTALLATION INSTRUCTIONS ON
 AIR CONDITIONING
 EQUIPMENT. PER SECTION 304.1 GENERAL.
 4) REFER TO SECTION 606.2.1 SUPPLY AIR, 606.3
 INSTALLATION AND 606.4.1 SUPERVISION
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-07-08 Cont ID  
Sent By tklarge Date 2015-07-08 Time 07:19 Rev Time 0.00
Received By tklarge Date 2015-07-08 Time 06:26 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-04-03 Cont ID  
Sent By tklarge Date 2015-04-03 Time 03:45 Rev Time 0.00
Received By tklarge Date 2015-04-02 Time 05:59 Sent To  
Notes
2015-04-02 07:00:571) SUBMIT DETAIL OF BREAKROOM SINK. SINK SHALL COMPLY
 W/ FAC SEC.212 & 606.
 2) SHOW THE DIMENSIONS ( L X W) OF THE TOILET ROOMS ON
 SHEET A-3.1.
 3) SHT. D-1 - THE BREAK ROON SINK COUNTERTOP SHALL BE
 AT A HEIGHT OF 34INCHES MAXIMUM ABOVE THE FINISH FLOOR
 PER THE 2010 FAC SEC.212 7 606.
 4) THE TOILET ROOMS DO NOT APPEAR TO BE WIDE ENOUGH TO
 PROVIDE THE REQUIRED CLEAR FLOOR SPACE FOR THE WATER
 CLOSET AND THE SPACING OF THE FIXTURES. A MINIMUM WIDTH
 OF 85 INCHES IS REQUIRED WHEN THE LAVATORY AND WATER
 CLOSET ARE ON THE SAME WALL. CLARIFY.
 5) SHT. A-1 - THE LOCATION OF THE URINAL IN THE MEN'S
 RESTROOM DOES NOT APPEAR TO PROVIDE THE REQUIRED
 PRIVACY AS SPECIFIED IN THE 2010 FPC SEC.310.5.THE LINE
 OF SIGHT TO THE URINAL WHEN THE DOOR IS OPEN IS CLEAR
 TO THE URINAL.
 6) SHT.A-3.1 - THE GRAB BARS SHALL BE MEASURED TO THE
 TOP OF THE GRIPPING SURFACE OF THE GRAB BAR PER THE
 2010 FAC SEC.609.4. SEE DETAILS #2 & # 4 ON SHT. A3-1.
 7) SHT.A-3.1 - DETAIL #6 - THE LAVATORY CLEARANCES
 SHALL COMPLY WITH THE FAC SEC.606.3 (MAXIMUM 34" TO THE
 RIM OF THE LAVATORY).
 8) SHT. A-3.1 - DETAIL #8 SHOWS AN OPTIONAL CUP
 DISPENSER. THIS IS NOT PERMNITTED PER THE 2010 FAC
 SEC.211.2. A MINIMUM OF 2 DRINKING FOUNTAINS ARE
 REQUIRED.
 9) SHT. P-1 - ETAIL #3 - THE LAVATORY IN THE MEN'S
 RESSTROOM STALL IS NOT VENTED PER THE 2010 FPC
 SEC.901.2, 901.2.1.
 10) THE SANITARY SHOWS 3" VTR'S FOR 2" STACKS.LARIFY.
 11) THE URINAL IS NOT ON THE SANITARY RISER.
 12) CLEANOUTS ARE REQUIRED IN THE BASE OF ALL STACKS.
 2010 FPC SEC.708.3.4.
 13) SUBMIT A WATER RISER DIAGRAM FOR REVIEW. WPB AMEND.
 TO 2010 FBC SEC. 107.3.5.1.3.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2015-06-25 Cont ID  
Sent By aaponte Date 2015-06-25 Time 11:44 Rev Time 0.00
Received By aaponte Date 2015-06-24 Time 17:18 Sent To  
Notes
2015-06-25 13:21:43PROVISO: A LANDSCAPE PERMIT SHALL BE SUBMITTED FOR
 APPROVAL PRIOR TO CO. LA PLANS SHALL BE SIGNED AND
 SEALED BY A LA ARCHITECT.
 STAFF RECOMMENDS ALEXANDER PALMS ALONG THE WEST
 ELEVATION INSTEAD OF TREES. A SMALL FLOWERING TREE
 SHALL BE PLANTED INFRONT OF THE MAIN ENTRANCE.
 IRRIGATION SHALL BE PROVIDED.

Review Stop Z ZONING
Rev No 1 Status F Date 2015-03-19 Cont ID  
Sent By fmittner Date 2015-03-19 Time 11:10 Rev Time 0.00
Received By aaponte Date 2015-03-19 Time 11:10 Sent To  
Notes
2015-03-19 11:16:451. PROPOSED ADDITION EXCEED 50% OF THE VALUE OF THE
 EXISTING STRUCTURE, THEREFORE LANDSCAPE IMPROVEMENTS
 WILL BE REQUIRED ON THE PROPERTY.
 2. A HEDGE AND TREES SHALL BE PROVIDED ALONG THE EAST
 SIDE OF THE PARKING LOT, AND THE SOUTH SIDE WHERE
 MISSING.
 3. TREES ARE REQUIRED EVERY 30 FEET.
 FOR ADDITINAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.
2015-03-10 13:49:303/10/15