Plan Review Details - Permit 15020858
Plan Review Stops For Permit 15020858
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-09-08 Cont ID  
Sent By jwitmer Date 2015-09-08 Time 16:38 Rev Time 0.00
Received By jwitmer Date 2015-09-08 Time   Sent To  
Notes
2015-09-08 16:37:54BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15020858
 ADD: 525 PALM ST. SUITE B
 CHANGE OF OCCUPANCY
 CONT: TBD
 TEL: (561)667-3661
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. SEPT. 08/2015
 ACTION: DENIED
  
 1) PLEASE NOTE THIS IS A CHANGE OF OCCUPANCY AND WILL
 REQUIRE ADDITIONAL INFORMATION FOR THE COMPLETION OF
 THE CERTIFICATE OF OCCUPANCY.
  
 1A) DESCREPANCY IN PLANS. THE LIFE SAFETY PLAN SHOWS
 THIS OCCUPANCY TO BE AN EDUCATIONAL OCCUPANCY OCCUPANT
 LOAD FIGURED AT 20 SQ. FT./ OCCUPANT. THE DESCREPANCY
 IS IN THE OCCUPANCY TO THE NORTH. SHEET A1 AND LS 1
 BOTH SHOW THE TENANT TO THE NORTH A BUSINESS OCCUPANCY
 WHERE AS THERE IS A EXPIRED PERMIT TO CHANGE THE
 OCCUPANCY FROM BUSINESS TO A3 A CHURCH (14081038). NOTE
 EXPIRED THE PERMIT NEVER GOT A FINAL 104. 9/25/2014
 FINAL INSPECTION 104 RESULTS ARE A INCOMPLETE, NEVER
 CALLED BACK IN.
  
 THE PLANS MAYBE CORRECT WITH THE BUSINESS OCCUPANCY IF
 THE USAGE OF THE TENANT SPACE TO THE NORTH IS NOT A
 A3-OCCUPANCY A CHURCH.
  
 2) COMPLIED. SPRINKLERED BUILDING, OCCUPANT LOAD LESS
 THAN 50 SINGLE EXIT REQUIRED.
  
 3) PLEASE SEE PLUMBING COMMENTS ABOUT THE USE OF
 RESTROOMS. THE EDUCATIONAL OCCUPANCY DOES NOT SHOW ANY
 RESTROOMS WITHIN THEIR TENANCY.
 YOU CAN NOT GO THROUGH THE STORAGE OCCUPANCY TO GAIN
 ACCESS IN THE A-3 CHURH OCCUPANCY. THE OCCUPANT IS
 GOING INTO A MORE DANGEROUS OCCUPANCY BEING A S-2
 STORAGE OCCUPANCY . 2010 FBC-B 1014.2(4) EGRESS THROUGH
 ENTERVENING SPACES, EGRESS SHALL NOT PASS THROUGH
 STORAGE ROOMS.
  
 4) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561) 805-6715
 FAX: (561)805-6676
 E-MAIL: [email protected]
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-03-14 Cont ID  
Sent By jwitmer Date 2015-03-14 Time 09:47 Rev Time  
Received By jwitmer Date 2015-03-14 Time 08:45 Sent To  
Notes
2015-03-14 09:47:11 
 BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15020858
 ADD: 525 PALM ST. SUITE B
 CHANGE OF OCCUPANCY
 CONT: TBD
 TEL: (561)667-3661
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 IMPORTANT NOTICE: EFFECTIVE MARCH 30, 2015
 ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED
 ELECTRONICALLY
 UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS
 SUBMISSION OPTIONS ARE AS FOLLOWS:
 1 UPLOAD VIA THE PROJECT DOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL
 SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED
 NAMING CONVENTION FOR EACH DOCUMENT
 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER
 DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE
 REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT
 TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS
 ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES
 AVAILABLE
  
 1ST REVIEW
 DATE: SAT. MARCH 14/ 2015
 ACTION: DENIED
  
 1) PLEASE NOTE THIS IS A CHANGE OF OCCUPANCY AND WILL
 REQUIRE ADDITIONAL INFORMATION FOR THE COMPLETION OF
 THE CERTIFICATE OF OCCUPANCY.
  
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.3.5 MINIMUM PLAN
 REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS
 SHALL BE DETERMINED. PLEASE REVIEWOCCUPANCY LOAD/EGRESS
 REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD
 GROSS
 NET
 MEANS OF EGRESS
 EXIT ACCESS
 EXIT
 EXIT DISCHARGE
 STAIRS CONSTRUCTION/GEOMETRY AND PROTECTION
 DOORS
 EMERGENCY LIGHTING AND EXIT SIGNS
 SPECIFIC OCCUPANCY REQUIREMENTS
 CONSTRUCTION REQUIREMENTS
 HORIZONTAL EXITS/EXIT PASSAGEWAYS
 MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED (SEE
 TABLE 503).
 BLDG. IS FIRE SPRINKLERED OR NOT
 LIFE SAFETY SHALL BE DETERMINED AND SHALL INCLUDE THE
 FOLLOWING ININFORMATION:
 OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD
 GROSS OR NET
 MEANS OF EGRESS
 EXIT ACCESS
 EXIT
 EXIT DISCHARGE
 DOORS
 SPECIFIC OCCUPANCY REQUIREMENTS :DAYCARE
 CONSTRUCTION REQUIREMENTS MINIMUM BLDG TYPE
  
 2) IN REVIEWING THESE PLANS THE 2010 FBC-B OCCUPANCY
 LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD
 GROSS
 NET
 MEANS OF EGRESS
 EXIT ACCESS
 EXIT
 EXIT DISCHARGE
 STAIRS CONSTRUCTION/GEOMETRY AND PROTECTION
 DOORS
 EMERGENCY LIGHTING AND EXIT SIGNS
 SPECIFIC OCCUPANCY REQUIREMENTS
 CONSTRUCTION REQUIREMENTS
 HORIZONTAL EXITS/EXIT PASSAGEWAYS
  
 2) IN REVIEWING THESE PLANS THE OCCUPANCY
 CLASSIFICATION IS DEFINED UNDER SECTION 2010 FBC-B
 303.1 EXCEPTION # 5. ACCESSORY RELIGIOUS EDUCATIONAL
 ROOMS AND RELIGIOUS AUDITORIUMS WITH OCCUPANT LOADS OF
 LESS THAN 100 ARE NOT CONSIDERED SEPARATE OCCUPANCIES.
 THERE FOR THIS OCCUPANCY SHALL BE CLASSIFIED AS A A3
 OCCUPANCY. UNLESS THIS SAME EDUCATIONAL ROOMS WILL BE
 USED AS A DAYCARE FACILITY DURING THE WORK WEEK. PLEASE
 INDICATE AS SUCH, BECAUSE IT WILL THEN FALL UNDER THE
 FBC-B CHAPTER 436 DAY-CARE OCCUPANCIES. NOTE IF THIS
 AREA IS DAYCARE IT WILL BE CONSIDERED A MIXED USE
 OCCUPANCY BETWEEN DAYCARE AND EDUCATIONAL, THE MOST
 STRINGENT REQUIEMENTS OF EITHER OCCUPANCY WILL BE THE
 CODE SECTION REQUIRED TO ACHIEVE.
  
 3) IT IS ASSUMED THIS BUILDING IS NOT FIRE SPRINKLERED,
 IN DOING SUCH WITH THE A3 OCCUPANCY 930 SQ FT/ 15= 62
 OCCUPANTS AND WILL REQUIRE 2 EXITS 1/2 THE DIAGONAL
 DISTANCE OF THE ROOM APART. THE 1/2 THE DIAGONAL
 DISTANCE IS APPROXIMATELY 26 FT APART AND THE DOORS ARE
 ONLY 18 FT APART. PLEASE SEE THE 2010 FBC-B TABLE
 1015.1 WILL REQUIRED 2 EXITS SINCE THE OCCUPANT LOAD IS
 GREATER THAN 49 OCCUPANTS.
  
 4) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561) 805-6715
 FAX: (561)805-6676
 E-MAIL: [email protected]
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-10-05 Cont ID  
Sent By albarran Date 2015-10-05 Time 19:25 Rev Time 0.00
Received By albarran Date 2015-10-05 Time 19:08 Sent To  
Notes
2015-10-05 19:55:45PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE SECOND ELECTRICAL REVIEW OF
 THE ABOVE MENTIONED JOB. BELOW ARE THE COMMENTS WITH
 REGARDS TO THE REQUIRED CORRECTIONS. THE PLANS SHALL BE
 REVISED TO ADDRESS FOLLOWING ITEMS; ONCE CORRECTED
 SHALL BE RESUBMITTED FOR ANOTHER REVIEW.
 THE PREVIOUSLY REQUIRED ITEMS AS REQUESTED FROM THE
 PREVIOUS ELECTRICAL PLANS REVIEW BACK IN FEBRUARY OF
 THIS YEAR HAVE NOT BEEN ADDRESSED AND A RESPONSE OF NO
 MEANING HAS BEEN SUBMITTED INSTEAD.
 FOR A SUCCESSFUL ELECTRICAL PLANS REVIEW YOU SHALL
 SUBMIT THE FOLLOWING:
 1. YOU SHALL INDICATE ON AN ELECTRICAL FLOOR PLAN THE
 LOCATION OF ALL OVER CURRENT PROTECTION DEVICES
 (PANELS) AS WELL AS ALL THE MAIN BREAKERS IF LOCATED
 ELSEWHERE.
 2. YOU SHALL PROVIDE A SITE SPECIFIC ELECTRICAL LOAD
 CALC.
 3. YOU SHALL SUBMIT A SITE SPECIFIC ELECTRICAL RISER
 DIAGRAM INCLUDING WIRING SIZING.
 4. YOU SHALL PROVIDE A PANEL SCHEDULE/CIRCUIT DIRECTORY
 AS REQUIRED BY NEC
 5. YOU SHALL INCLUDE ON THE ELECTRICAL FLOOR PLAN THE
 LOCATION OF ALL EMERGENCY AND EXIT LIGHTS.
 REGARDLESS OF WHAT YOUR ARCHITECT CLAIMS, FOR REASONS
 OF LIFE SAFETY THERE ARE DIFFERENT ELECTRICAL AND FIRE
 ALARM REQUIREMENTS FROM ASSEMBLY OCCUPANCY TO REGULAR
 BUSINESS OCCUPANCY. THEREFORE THERE MAY BE WIRING
 METHODS WITHIN THE PREMISES THAT THOUGH PERMITTED IN A
 BUSINESS ENVIRONMENT, WILL BE AGAINST CODE IN AN
 ASSEMBLY ENVIRONMENT. THE SAME HOLDS TRUE FOR THE FIRE
 ALARM AND EMERGENCY LIGHTING REQUIREMENTS.
 FURTHERMORE, LET ME CLARIFY THAT THIS WAS NEVER PASSED
 OR APPROVED BY THE FIRE PLANS EXAMINER, IF YOU READ HIS
 NOTES, HE INSTRUCTED YOU TO SUBMIT A SEPARATE FIRE
 ALARM DRAWING FOR APPROVAL AS THE FIRE ALARM HAS TO BE
 ON A STAND-ALONE PERMIT WITH ITS OWN SUBMITTAL
 DOCUMENTS.
 PLEASE REVISE YOUR PLANS ACCORDING FOR A SMOOTH AND
 SUCCESSFUL REVIEW.
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DO NOT HESITATE
 TO CONTACT ME.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-02-28 Cont ID  
Sent By dhayes Date 2015-02-25 Time 11:28 Rev Time 0.00
Received By dhayes Date 2015-02-25 Time 11:28 Sent To  
Notes
2015-02-28 11:28:422/28/2015
 PROJECT: CHANGE OF OCCUPANCY; BRIDGE CHURCH SCHOOL
 PERMIT#: 15020858
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 ELECTRICAL PLANS HAVE NOT BEEN PROVIDED WITH THIS
 SUBMITTAL BUT THE MINIMUM CONDITIONS OF THE NEC MUST BE
 MET AND INDICATED ON THE PLANS SUBMITTED FOR CODE
 COMPLIANCE. PLEASE INDICATE COMPLIANCE WITH THE
 FOLLOWING:
  
 1) NEC 240.24 (B) OCCUPANCY.
 EACH OCCUPANT SHALL HAVE READY ACCESS TO ALL
 OVERCURRENT DEVICES PROTECTING THE CONDUCTORS SUPPLYING
 THAT OCCUPANCY. INDICATE ON THE PLANS THE LOCATIONS OF
 ALL ELECTRICAL PANEL
  
 2) NEC 518 ASSEMBLY OCCUPANCY.
 WIRING METHODS AND ELECTRICAL SYSTEMS SHALL BE
 INSTALLED IN COMPLIANCE WITH THE MINIMUM CONDITIONS
 FOUND IN THE NEC ARTICLE 518.
  
 3) NEC 422.52 ELECTRIC DRINKING FOUNTAINS.
 ELECTRIC DRINKING FOUNTAINS SHALL BE PROTECTED WITH
 GROUND FAULT CIRCUIT INTERRUPTER PROTECTION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-03-13 Cont ID  
Sent By wjolin Date 2015-03-13 Time 12:41 Rev Time 0.00
Received By wjolin Date 2015-03-13 Time 12:40 Sent To  
Notes
2015-03-13 12:41:30SUBMIT PLANS FOR FIRE ALARM SYSTEM WITH SMOKE
 DETECTION.
  
 ROY LINDOW
 [email protected]
 561.804.4754

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-10-05 Cont ID  
Sent By albarran Date 2015-10-05 Time 19:55 Rev Time 0.00
Received By albarran Date 2015-08-19 Time 08:58 Sent To  
Notes
2015-10-05 19:57:3110/5/15 THIS SUBMITTAL CONTINUES TO IGNORE THE CODE
 REQUIREMENTS. CONTRACTOR HAS BEEN NOTIFIED VIA EMAIL.
 SENT TO SMALL DENIED BIN "B". MA
  
2015-08-20 08:58:25B22

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-03-21 Cont ID  
Sent By hmoser Date 2015-03-21 Time 10:09 Rev Time 0.00
Received By hmoser Date 2015-02-25 Time 11:31 Sent To  
Notes
2015-02-28 11:31:35B!3

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2015-09-08 Cont ID  
Sent By jwitmer Date 2015-09-08 Time 16:49 Rev Time 0.00
Received By jwitmer Date 2015-09-08 Time 16:49 Sent To  
Notes
2015-09-08 16:49:53BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-03-14 Cont ID  
Sent By jwitmer Date 2015-03-14 Time 09:47 Rev Time 0.00
Received By jwitmer Date 2015-03-14 Time 09:47 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2015-09-01 Cont ID  
Sent By ccole Date 2015-09-01 Time 07:41 Rev Time 0.00
Received By ccole Date 2015-09-01 Time 07:41 Sent To  
Notes
2015-09-01 07:59:032ND REVIEW: FBC 2010 MECHANICAL
 PERMIT #15020858
 9/1/12015
  
 1) AS PREVIOUSLY REQUESTED IN THE 1ST REVIEW ON
 3/21/15, PROVIDE FRESH AIR CALCULATIONS ON THE PLAN IN
 COMPLIANCE WITH TABLE 403.3 FBC-10 MECHANICAL. INDICATE
 ON THE PLAN THE REQUIRED AMOUNT OF VENTILATION AIR IN
 CFM'S, AND THE AMOUNT BEING PROVIDED BY THE EXISTING
 SYSTEM- SEE SECTION 909.1 FBC-10 EXISTING BUILDING
 CODE.
 2) PLEASE SHOW THE LAYOUT OF THE EXISTING AC SYSTEM ON
 THE PLAN AND PROVIDE DETAILS- LOCATIONS OF THE AIR
 HANDLER AND CONDENSER, COOLING AND HEATING CAPACITIES
 OF THE SYSTEM, SUPPLY AND RETURN AIR DUCT RUNS, AND
 LOCATIONS OF DUCT SMOKE DETECTORS AND FIRE DAMPERS IF
 APPLICABLE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-03-21 Cont ID  
Sent By hmoser Date 2015-03-21 Time 10:07 Rev Time 0.00
Received By hmoser Date 2015-03-21 Time 09:41 Sent To  
Notes
2015-03-21 10:07:52PLAN DENIED
 1) IN REGARDS TO SMOKE DUCT DETECTORS REFER TO
 SECTION 606.3 INSTALLATION AND 606.4.1 SUPERVISION
 2) FRESH AIR WILL BE REQUIRED ON THE PLAN.
  
 PLAN REVUE BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 2 Status F Date 2015-09-05 Cont ID  
Sent By tklarge Date 2015-09-05 Time 03:00 Rev Time 0.00
Received By tklarge Date 2015-09-04 Time 05:58 Sent To  
Notes
2015-09-05 02:59:571) AS PREVIOUSLY, THIS IS A CHANGE OF OCCUPANCY. PLEASE
 REFER TO THE PREVIOUS COMMENT MADE BY JIM WITMER.
 BUILDING PLAN REVIEWER REGARDING THIS OCCUPANCY TYPE.
 SEC. 303. EXCEPTION #5 OF THE 2010 FBC CLEARLY STATES
 "ACCESSORY RELIGIOUS EDUCATIONAL ROOMS AND RELIGIOUS
 AUDITORIUMS WITH OCCUPANT LOADS OF LESS THAN 100 ARE
 NOT CONSIDERED SEPARATE OCCUPANCIES" SO I DON'T
 UNDERSTAND HOW THIS COULD BE DEEMED AN EDUCATIONAL
 OCCUPANCY. SECTION 305 OF THE 2010 FBC ALSO STATES
 THIS. THE OCCUPANCY TYPE SHALL DETERMINE THE TYPE AND
 NUMBER OF SANITARY FACILITIES REQUIRED. SINCE THE
 DESIGN PROFESSIONAL IS CALLING THIS AN EDUCATIONAL
 OCCUPANCY, ADDITIONAL INFORMATION SHALL BE SUBMITTED TO
 DETERMINE IF THIS WOULD INDEED BE DEEMED AN EDUCATIONAL
 OCCUPANCY.THE NUMBER AND TYPE OF SANITARY FACILITIES
 CANNOT BE DETERMINED UNTIL THE OCCUPANCY OF THIS SPACE
 IS DETERMINED. WPB AMEND. TO FBC SEC. 107.2.1.
 2) THE COVER SHEET ON THE PLANS SHOWS ONE OF THE
 ADJACENT TENANTS (CHURCH?) AS AN ASSEMBLY OCCUPANCY AND
 ON SHEET A1 AND THE LIFE SAFETY PLAN THE SAME ADJACENT
 TENANT IS SHOWN AS A BUSINESS OCCUPANCY. WHICH IS IT?
 WHERE IS THE CHURCH LOCATED? IDENTIFY THE SPACE WHERE
 THE CHURCH IS LOCATED.
 3) SHOW THE CLEAR INSIDE DIMENSIONS ( L X W ) OF THE
 TOILET ROOM. THE FBC-ACCESSIBILITY CODE SEC.604.3.1
 REQUIRES A CLEAR FLOOR SPACE OF A MINIMUM OF 60 INCHES
 IN WIDTH BY 56 INCHES DEEP FOR A WATER CLOSET. THE
 LAVATORY CANNOT ENCROACH INTO THIS CLEAR FLOOR SPACE.
 THIS WOULD REQUIRE A MINIMUM WIDTH OF THE TOILET ROOM
 TO BE 85". SEC. 906.1 OF THE 2010 FBC-EXISTING BUILDING
 CODE REQUIRES COMPLIANCE WITH THE ACCESSIBILITY CODE
 WHEN A CHANGE OF OCCUPANCY OCCURS.
 4) AS PREVIOUSLY NOTED, A MINIMUM OF TWO DRINKING
 FOUNTAINS ARE REQUIRED BY THE 2010 FBC-ACCESSIBILITY
 CODE SEC. 211.2. A WATER COOLER DOES NOT MEET THE CODE
 REQUIREMENT. AT A MINIMUM, A HI-LO TYPE DRINKING
 FOUNTAIN SHALL BE REQUIRED.
 5) THE DESIGN PROFESSIONAL IS CALLING THIS AN
 EDUCATIONAL OCCUPANCY YET THE LIFE SAFETY PLAN HAS THE
 SANITARY FACILITIES BASED ON AN A-3 OCCUPANCY.CLARIFY.
 6) THE ARCHITECT'S RESPONSE TO THE PLUMBING CODE
 REQUIREMENTS FOR THE REQUIRED NUMBER OF SANITARY
 FACILITIES THAT SEPARATE FACILITIES FOR EACH SEX ARE
 LOCATED IN THE CHURCH NEXT DOOR AND THAT PERMANENT
 ACCESS WILL BE PROVIDED TO THE TENANT IS UNACCEPTABLE.
 SECTION 403.3.1 CLEARLY PROHIBITS ACCESS TO THE
 FACILITIES THROUGH STORAGE ROOMS, CLOSETS AND
 KITCHENS.THE PATH OF TRAVEL TO THE FACILITIES IN THE
 CHURCH CLEARLY GOES THROUGH A STORAGE AREA AND A
 CLOSET. THE SAME APPLIES TO THE LOCATION OF ALL THE
 REQUIRED PLUMBING FIXTURES FOR THIS NEW SPACE.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-03-17 Cont ID  
Sent By tklarge Date 2015-03-17 Time 09:18 Rev Time 0.00
Received By tklarge Date 2015-03-17 Time 06:57 Sent To  
Notes
2015-03-17 08:52:131) THIS FACILITY IS DEEMED A CHANGE OF OCCUPANCY FROM
 BUSINESS TO A-3. THE NEW OCCUPANCY SHALL COMPLY WITH
 SECTION 910.1 OF THE 2010 FL. EXISTING BUILDING CODE
 AND TABLE 403.1 OF THE 2010 FL. PLUMBING CODE. SEPARATE
 SANITARY FACILITIES ARE REQUIRED FOR THA MALES AND
 FEMALES PER THE 2010 FPC SEC.403.1. A MINIMUM OF ONE
 WATER CLOSET AND ONE LAVATORY IS REQUIRED FOR EACH SEX
 PER TABLE 403.1 OF THE 2010 FL. PLUMBING CODE.
 2) A SERVICE SINK IS REQUIRED IN THE FACILITY PER ABLE
 403.1 OF THE 2010 FL. PLUMBING CODE.
 3) A MINIMUM OF TWO DRINKING FOUNTAINS ARE REQUIRED PER
 THE 2010 FL. ACCESSIBILITY CODE SEC. 211.2. ONE
 FOUNTAIN SHALL COMPLY WITH FAC SEC.602.1 THROUGH
 SEC.602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH
 SEC. 602.7. SEE EXCEPTION FOR SINGLE DRINKING
 FOUNTAIN.SHOW THE LOCATION OF THE DRINKING FOUNTAINS ON
 THE FLOOR PLAN.
 4) THE DRINKING FOUNTAINS SHALL BE PROVIDED WITH CLEAR
 FLOOR SPACE AND KNEE AND TOE CLEARANCE PER THE 2010 FL.
 ACCESSIBILITY CODE SECS. 305 & 306. SHOW THE REQUIRED
 CLEAR FLOOR SPACE ON THE PLAN.
 5) THE TOILET ROOMS SHALL COMPLY WITH SEC. 213.2 AND
 SEC. 603 OF THE 2010 FAC.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2015-03-20 Cont ID  
Sent By sgraham Date 2015-03-20 Time 12:35 Rev Time 0.00
Received By sgraham Date 2015-03-20 Time 12:35 Sent To  
Notes
2015-03-10 14:03:093/10/15


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved