| PROJECT: SITE LIGHTING |
| PERMIT#: 15020847 |
| CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| 2ND ELECTRICAL PLAN REVIEW |
| ACTION: DENIED |
| |
| 1) 505.2.4 EXTERIOR LIGHTING CONTROLS. |
| LIGHTING FOR ALL EXTERIOR APPLICATIONS NOT EXEMPTED IN |
| SECTION 505.1 SHALL HAVE AUTOMATIC CONTROLS CAPABLE OF |
| TURNING OFF EXTERIOR LIGHTING WHEN SUFFICIENT DAYLIGHT |
| IS AVAILABLE OR WHEN THE LIGHTING IS NOT REQUIRED |
| DURING NIGHTTIME HOURS. LIGHTING NOT DESIGNATED FOR |
| DUSK-TO-DAWN OPERATION SHALL BE CONTROLLED BY EITHER A |
| COMBINATION OF A PHOTOSENSOR AND A TIME SWITCH, OR AN |
| ASTRONOMICAL TIME SWITCH. A TIME SWITCH IS NOTED ON |
| SHEET E101 HOWEVER THERE IS NO NOTES OR PRODUCT |
| APPROVAL ON TIME SWITCH THAT INDICATE COMPLIANCE WITH |
| FBC 505.2. PROVIDE PRODUCT APPROVAL ON TIME SWITCH. |
| |
| 2) 2010 FBC-BUILDING SECTION 1609 |
| PROVIDE ENGINEERED WIND LOAD CALCULATIONS FOR ALL LIGHT |
| POLE CONFIGURATIONSINCLUDING LUMINAIRE IN COMPLIANCE |
| WITH THE FBC 1609. |
| |
| 3) NEC 215.5 |
| PROVIDE A LOAD CALCULATION FOR THE ELECTRICAL PANELS |
| AND SERVICE PROPOSED TO FEED THE LIGHT POLES. |
| |
| 4) VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS |
| HAS A FAULT CURRENT RATING THAT IS SUFFICIENT AT |
| NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE |
| INTERRUPTED. NEC 110.9 |
| |
| 5) PROVIDE SAFETY LABELING FOR ARC FLASH PROTECTION FOR |
| THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC |
| 110.16. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| |
| ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| REVIEW. |
| |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| 561-805-6717 OR [email protected] |