Plan Review Details - Permit 15020847
Plan Review Stops For Permit 15020847
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2015-04-30 Cont ID  
Sent By shill Date 2015-04-30 Time 08:09 Rev Time 0.00
Received By shill Date 2015-04-30 Time 08:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2015-04-13 Cont ID  
Sent By misc2 Date 2015-04-13 Time 12:04 Rev Time 0.00
Received By dhayes Date 2015-04-13 Time 11:53 Sent To B
Notes
2015-04-13 12:06:03CORRECT NOTE ON E-101 THAT STATES "TO MAIN BREAKER"
 CHANGE TO READ "TO GROUNDED NEUTRAL BUSS"

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-03-13 Cont ID  
Sent By dhayes Date 2015-03-13 Time 10:26 Rev Time 0.00
Received By dhayes Date 2015-03-13 Time 10:14 Sent To Z
Notes
2015-03-13 10:26:223/13/2015
 PROJECT: SITE LIGHTING
 PERMIT#: 15020847
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 2ND ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) 505.2.4 EXTERIOR LIGHTING CONTROLS.
 LIGHTING FOR ALL EXTERIOR APPLICATIONS NOT EXEMPTED IN
 SECTION 505.1 SHALL HAVE AUTOMATIC CONTROLS CAPABLE OF
 TURNING OFF EXTERIOR LIGHTING WHEN SUFFICIENT DAYLIGHT
 IS AVAILABLE OR WHEN THE LIGHTING IS NOT REQUIRED
 DURING NIGHTTIME HOURS. LIGHTING NOT DESIGNATED FOR
 DUSK-TO-DAWN OPERATION SHALL BE CONTROLLED BY EITHER A
 COMBINATION OF A PHOTOSENSOR AND A TIME SWITCH, OR AN
 ASTRONOMICAL TIME SWITCH. A TIME SWITCH IS NOTED ON
 SHEET E101 HOWEVER THERE IS NO NOTES OR PRODUCT
 APPROVAL ON TIME SWITCH THAT INDICATE COMPLIANCE WITH
 FBC 505.2. PROVIDE PRODUCT APPROVAL ON TIME SWITCH.
  
 2) 2010 FBC-BUILDING SECTION 1609
 PROVIDE ENGINEERED WIND LOAD CALCULATIONS FOR ALL LIGHT
 POLE CONFIGURATIONSINCLUDING LUMINAIRE IN COMPLIANCE
 WITH THE FBC 1609.
  
 3) NEC 215.5
 PROVIDE A LOAD CALCULATION FOR THE ELECTRICAL PANELS
 AND SERVICE PROPOSED TO FEED THE LIGHT POLES.
  
 4) VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS
 HAS A FAULT CURRENT RATING THAT IS SUFFICIENT AT
 NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE
 INTERRUPTED. NEC 110.9
  
 5) PROVIDE SAFETY LABELING FOR ARC FLASH PROTECTION FOR
 THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC
 110.16.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-03-06 Cont ID  
Sent By dhayes Date 2015-03-06 Time 15:04 Rev Time 0.00
Received By dhayes Date 2015-03-06 Time 15:04 Sent To  
Notes
2015-03-06 15:29:253/6/2015
 PROJECT: SITE LIGHTING
 PERMIT#: 15020847
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) 505.2.4 EXTERIOR LIGHTING CONTROLS.
 LIGHTING FOR ALL EXTERIOR APPLICATIONS NOT EXEMPTED IN
 SECTION 505.1 SHALL HAVE AUTOMATIC CONTROLS CAPABLE OF
 TURNING OFF EXTERIOR LIGHTING WHEN SUFFICIENT DAYLIGHT
 IS AVAILABLE OR WHEN THE LIGHTING IS NOT REQUIRED
 DURING NIGHTTIME HOURS. LIGHTING NOT DESIGNATED FOR
 DUSK-TO-DAWN OPERATION SHALL BE CONTROLLED BY EITHER A
 COMBINATION OF A PHOTOSENSOR AND A TIME SWITCH, OR AN
 ASTRONOMICAL TIME SWITCH.
  
 2) 2010 FBC-BUILDING SECTION 1609
 PROVIDE WIND LOAD CALCULATIONS FOR ALL LIGHT POLES
 INCLUDING LUMINAIRE IN COMPLIANCE WITH THE FBC 1609
  
 3) WPB AMENDMENTS TO FBC 107
 PROVIDE A SITE PLAN INDICATING THE LOCATION OF THE
 ELECTRICAL PANELS INTENDED TO BE USED AS THE POWER
 SOURCE FOR THE PROPOSED LIGHT POLES. INDICATE THE
 EXISTING ELECTRICAL SYSTEM LOAD AND VOLTAGE
  
 4) NEC 408.4
 PROVIDE A PANEL SCHEDULE TO INDICATE THE LIGHTING
 CIRCUITS PROPOSED TO FEED THE LIGHT POLES. INDICATE ANY
 EXISTING CIRCUITS AND THE PROPOSED CIRCUITS FOR THE NEW
 LIGHTS.
  
 5) NEC 215.5
 PROVIDE A LOAD CALCULATION FOR THE ELECTRICAL PANELS
 AND SERVICE PROPOSED TO FEED THE LIGHT POLES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-04-30 Cont ID  
Sent By shill Date 2015-04-30 Time 08:09 Rev Time 0.00
Received By shill Date 2015-04-03 Time 07:41 Sent To  
Notes
2015-04-03 07:41:28TO ZONING
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-03-24 Cont ID  
Sent By dhayes Date 2015-03-24 Time 12:30 Rev Time 0.00
Received By jroach Date 2015-03-12 Time 16:58 Sent To  
Notes
2015-03-12 17:00:21THE INITIAL ELECTRICAL REVIEW WAS FOR THE WRONG SITE
 LIGHTING PROJECT. THE WRONG SUBMITTAL DOCUMENTS WERE IN
 THIS PACKAGE IN ERROR. THE CORRECT PACKAGE IS NOW IN
 THIS PACKAGE FOR A NEW REVIEW. PER STEVEN KENNEDY.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-03-06 Cont ID  
Sent By dhayes Date 2015-03-06 Time 15:04 Rev Time 0.00
Received By dhayes Date 2015-02-25 Time 14:54 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2015-04-21 Cont ID  
Sent By jroach Date 2015-04-21 Time 14:44 Rev Time 0.00
Received By jroach Date 2015-04-21 Time 14:44 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2015-04-07 Cont ID  
Sent By jroach Date 2015-04-07 Time 14:54 Rev Time 0.00
Received By jroach Date 2015-04-07 Time 14:54 Sent To E
Notes
2015-04-07 14:55:17ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 04.07.2015
 PERMIT NO.: 15020847
 ADDRESS: 1101 SOUTH FLAGLER DRIVE
 CONTRACTOR/CONTACT: DON SHARKEY
 TELEPHONE NO.: 561.863.0010
 SCOPE OF REVIEW: SITE LIGHTING.
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. THE PROPERTY SHALL BE RE-PLATTED. IMPORTANT - ZONING
 HAS NO OBJECTION TO THE PLANS SUBMITTED. AS SOON AS THE
 PLAT IS APPROVED BY THE CITY COMMISSION (4/13/2015),
 ZONING WILL SIGN-OFF ON THIS PERMIT APPLICATION.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1448
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.WPB.ORG
  

Review Stop Z ZONING
Rev No 1 Status F Date 2015-03-24 Cont ID  
Sent By jroach Date 2015-03-24 Time 12:30 Rev Time 0.00
Received By jroach Date 2015-03-24 Time 12:30 Sent To  
Notes
2015-03-24 12:30:29ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 03.24.2015
 PERMIT NO.: 15020847
 ADDRESS: 1101 SOUTH FLAGLER DRIVE
 CONTRACTOR/CONTACT: DON SHARKEY
 TELEPHONE NO.: 561.863.0010
 SCOPE OF REVIEW: SITE LIGHTING.
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. THE PROPERTY SHALL BE RE-PLATTED.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1448
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved