2015-03-03 09:03:11 | 3/3/2015 |
| PROJECT: 7712 MARTIN AVE |
| PERMIT#: 15020846 |
| CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| 1ST ELECTRICAL PLAN REVIEW |
| ACTION: DENIED |
| |
| 1) WPB AMENDMENTS TO 107, NEC 240.4 |
| INDICATE ON THE PLAN THE LOCATION OF THE ELECTRICAL |
| SERVICE AND ELECTRICAL PANEL. INCLUDE THE SIZE OF THE |
| MAIN AT THE ELECTRICAL SERVICE AND THE SIZE OF THE |
| ELECTRICAL PANEL. |
| |
| 2) NEC215.5 |
| PROVIDE AN ELECTRICAL RISER DIAGRAM INDICATING THE SIZE |
| OF THE MAIN OCPD THE AVAILABLE FAULT CURRENT, THE SIZE |
| AND TYPE OF SERVICE RACEWAYS AND FEEDER SIZES. |
| |
| 3) WPB AMENDMENTS TO 107 |
| INDICATE ON THE PLAN WHAT ELEMENTS, CIRCUITS AND |
| DEVICES THAT ARE EXISTING TO REMAIN AND WHAT SPECIFIC |
| ELEMENTS, CIRCUITS AND DEVICES THAT ARE PROPOSED TO BE |
| NEW. |
| |
| 4) WPB AMENDMENTS TO 107 |
| INDICATE A WIRING METHOD PROPOSED FOR ANY NEW WORK. |
| |
| 4) NEC 240.4, 240.24, 310.16 |
| INDICATE THE CIRCUIT SIZE(OCPD) REQUIRED AND WIRE SIZE |
| AND TYPE CONNECTED TO THE OCPD TO BE RATED AND APPROVED |
| FOR THE LOAD TO BE SERVED. |
| |
| 5) NEC 408.4 |
| EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE LEGIBLY |
| IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND SPECIFIC |
| PURPOSE OR USE. INDICATE ON THE PANEL SCHEDULE ANY |
| CIRCUITS THAT ARE EXISTING TO REMAIN AND THE CIRCUITS |
| THAT ARE NEW OR PROPOSED TO BE INSTALLED. |
| |
| 6) NEC 220.12 OR 220.14 AS APPLICABLE. NEC 220.16(2), |
| LOADS FOR NEW CIRCUITS OR EXTENDED CIRCUITS IN |
| PREVIOUSLY WIRED DWELLING UNITS SHALL BE CALCULATED IN |
| ACCORDANCE WITH EITHER THE NEC 220.12 OR 220.14, AS |
| APPLICABLE. NEC 220.16(2) |
| |
| 7) FBC-RESIDENTIAL 314 AND 315. |
| WHEN ALTERATIONS, REPAIRS, OR ADDITIONS REQUIRING A |
| PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE |
| ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL |
| DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS |
| LOCATED AS REQUIRED FOR NEW DWELLINGS. |
| |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| |
| ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| REVIEW. |
| |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |