Plan Review Details - Permit 15020846
Plan Review Stops For Permit 15020846
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-03-03 Cont ID  
Sent By sciard Date 2015-03-03 Time 13:42 Rev Time 0.00
Received By sciard Date 2015-03-03 Time 13:42 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-03-03 Cont ID  
Sent By dhayes Date 2015-03-03 Time 08:53 Rev Time 0.00
Received By dhayes Date 2015-03-03 Time 08:53 Sent To  
Notes
2015-03-03 09:03:113/3/2015
 PROJECT: 7712 MARTIN AVE
 PERMIT#: 15020846
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) WPB AMENDMENTS TO 107, NEC 240.4
 INDICATE ON THE PLAN THE LOCATION OF THE ELECTRICAL
 SERVICE AND ELECTRICAL PANEL. INCLUDE THE SIZE OF THE
 MAIN AT THE ELECTRICAL SERVICE AND THE SIZE OF THE
 ELECTRICAL PANEL.
  
 2) NEC215.5
 PROVIDE AN ELECTRICAL RISER DIAGRAM INDICATING THE SIZE
 OF THE MAIN OCPD THE AVAILABLE FAULT CURRENT, THE SIZE
 AND TYPE OF SERVICE RACEWAYS AND FEEDER SIZES.
  
 3) WPB AMENDMENTS TO 107
 INDICATE ON THE PLAN WHAT ELEMENTS, CIRCUITS AND
 DEVICES THAT ARE EXISTING TO REMAIN AND WHAT SPECIFIC
 ELEMENTS, CIRCUITS AND DEVICES THAT ARE PROPOSED TO BE
 NEW.
  
 4) WPB AMENDMENTS TO 107
 INDICATE A WIRING METHOD PROPOSED FOR ANY NEW WORK.
  
 4) NEC 240.4, 240.24, 310.16
 INDICATE THE CIRCUIT SIZE(OCPD) REQUIRED AND WIRE SIZE
 AND TYPE CONNECTED TO THE OCPD TO BE RATED AND APPROVED
 FOR THE LOAD TO BE SERVED.
  
 5) NEC 408.4
 EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE LEGIBLY
 IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND SPECIFIC
 PURPOSE OR USE. INDICATE ON THE PANEL SCHEDULE ANY
 CIRCUITS THAT ARE EXISTING TO REMAIN AND THE CIRCUITS
 THAT ARE NEW OR PROPOSED TO BE INSTALLED.
  
 6) NEC 220.12 OR 220.14 AS APPLICABLE. NEC 220.16(2),
 LOADS FOR NEW CIRCUITS OR EXTENDED CIRCUITS IN
 PREVIOUSLY WIRED DWELLING UNITS SHALL BE CALCULATED IN
 ACCORDANCE WITH EITHER THE NEC 220.12 OR 220.14, AS
 APPLICABLE. NEC 220.16(2)
  
 7) FBC-RESIDENTIAL 314 AND 315.
 WHEN ALTERATIONS, REPAIRS, OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS.
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-03-03 Cont ID  
Sent By sciard Date 2015-03-03 Time 13:42 Rev Time 0.00
Received By sciard Date 2015-03-03 Time 13:42 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status F Date 2015-03-03 Cont ID  
Sent By dhayes Date 2015-03-03 Time 09:13 Rev Time 0.00
Received By dhayes Date 2015-02-25 Time 08:53 Sent To  
Notes
2015-02-25 15:43:29ROUTED TO ELECTRICAL


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved