Plan Review Details - Permit 15020728
Plan Review Stops For Permit 15020728
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-04-03 Cont ID  
Sent By pleduc Date 2015-04-03 Time   Rev Time 0.00
Received By pleduc Date 2015-04-03 Time 11:18 Sent To PC
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status   Date 2015-03-30 Cont ID  
Sent By hmoser Date 2015-02-28 Time 12:39 Rev Time 0.00
Received By hmoser Date 2015-03-27 Time 19:10 Sent To  
Notes
2015-03-27 19:10:28SENT TO H MOSER

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-04-03 Cont ID  
Sent By pleduc Date 2015-04-03 Time   Rev Time 0.00
Received By pleduc Date 2015-02-28 Time 08:06 Sent To  
Notes
2015-02-24 10:47:43ROUTED TO MECHANICAL OVER $5K

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-03-30 Cont ID  
Sent By hmoser Date 2015-03-30 Time 12:41 Rev Time 0.00
Received By hmoser Date 2015-03-30 Time 12:41 Sent To FIRE
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-03-30 Cont ID  
Sent By hmoser Date 2015-02-28 Time 12:39 Rev Time 0.00
Received By hmoser Date 2015-02-28 Time 08:06 Sent To  
Notes
2015-02-28 08:11:19DUCT PLAN IS NOT STAMPED BY THE ENGINEER .
 PER SECTION 107 FBC. 2010
 MARK ALL ROOMS ON THE PLAN SO KITCHEN CAN BE FOUND.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676