Plan Review Stops For Permit 15020691 |
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
F |
Date |
2015-02-25 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2015-02-25 |
Time |
05:50 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2015-02-25 |
Time |
05:16 |
Sent To |
|
|
Notes |
2015-02-25 05:50:04 | THERE WAS NO GAS DRAWING SHOWN ON THE ORIGINAL PLAN. | | 1) THE ORIGINAL FLOOR PLAN SHOWED THE GAS FIREPLACE TO | | BE REMOVED AND THE GAS DRAWING SHOWS THE FIREPLACE TO | | REMAIN. CLARIFY. | | 2) SUBMIT MANUFACTURER'S SPECIFICATIONS SHEETS & | | INSTALLATION INSTRUCTIONS FOR ALL GAS APPLIANCES. | | APPLIANCES SHALL BE LISTED AND LABELED PER THE 2010 | | FUEL GAS CODE SEC. 301.3. | | 3) SIZE THE PIPE DROPS TO THE GAS RANGE AND THE | | FIREPLACE AND INDICATE THE TYPE OF PIPE FOR BOTH DROPS. | | 40 SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR ALL | | APPLIANCES IN ACCORDANCE WITH THE 2010 FUEL GAS CODE | | SEC.304. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | | | |
|
|